Operation; Proof Test Procedure - Pepperl+Fuchs HiD2035 Manual

Functional safety current driver/repeater
Table of Contents

Advertisement

Functional Safety HiD2035, HiD2036

Operation

5
Operation
Danger!
Danger to life from missing safety function
If the safety loop is put out of service, the safety function is no longer guaranteed.
• Do not deactivate the device.
• Do not bypass the safety function.
• Do not repair, modify, or manipulate the device.
Operating the device
1. Observe the safety instructions in the instruction manual.
2. Observe the information in the manual.
3. Use the device only with devices that are suitable for this safety application.
4. Correct any occurring safe failures within 8 hours. Take measures to maintain
the safety function while the device is being repaired.
5.1

Proof Test Procedure

According to IEC/EN 61508-2 a recurring proof test shall be undertaken to reveal
potential dangerous failures that are not detected otherwise.
Check the function of the subsystem at periodic intervals depending on the
applied PFD
See chapter 3.4.
It is under the responsibility of the plant operator to define the type of proof test
and the interval time period.
Equipment required:
• Digital multimeter with an accuracy better than 0.1 %
Use for the proof test of the intrinsic safety side of the device a special digital
multimeter for intrinsically safe circuits.
If intrinsically safe circuits are operated with non-intrinsically safe circuits,
they must no longer be used as intrinsically safe circuits.
• Variable power supply 0 V DC ... 30 V DC
• Process calibrator with current source and current sink function with an
accuracy better than 20 µA
in accordance with the characteristic safety values.
avg
15

Advertisement

Table of Contents
loading

This manual is also suitable for:

Hid2036

Table of Contents