Supply Characteristics:
Supply Voltage ( )
Supply Variation
Power Consumption (Max.)
Operating Frequency
Battery Backup
LED Indication
Settings:
Day
Hour
Minute
Clock Format
Reset
Modes
Programming
Relay Output Characteristics:
Contact Arrangement
Contact Rating
Incandescent Lamps
Inductive Load (Cos o = 0.6)
/
Contact Material
Minimum Switching Load
Mechanical Life
Electrical Life
Minimum Switching Time
(V)
Utilization Category AC-15 Ue Rated Voltage
(A)
Ie Rated Current
(V)
Utilization Category DC-13 Ue Rated Voltage
Ie Rated Current
(A)
Others:
Clock Accuracy
LCD Display
Number of keys
Operating Temperature Range
Storage Temperature Range
Humidity (Non-Condensing)
Maximum Operating Altitude
Pollution Degree
Degree of Protection
Mounting
Enclosure
Weight (Unpacked)
EMI/EMC:
Harmonic Current Emissions
Voltage Flicker & Fluctuation
ESD
Radiated Susceptibility
Electrical Fast Transients
Surge
Conducted Susceptibility
Power Frequency Magnetic Field
Voltage Dips and Interruption (AC)
Conducted Emission
Radiated Emission
Safety:
Test Voltage between Input and Output
Impulse Voltage between Input and Output
Single fault
Insulation Resistance
Leakage Current
Environmental Testing:
Cold Heat
Dry Heat
Vibration
Repetitive Shock
Non-repetitive Shock
110 to 240 VAC
-20% to +10% of
(
)
6 VA
50/60 Hz
Approx. 6 years running reserve
Red LED for Relay Status
Annual clock with calendar up to 31.12.2099
00-23
00-59
Either AM/PM (12 h) or 24 h Clock
Programs and clock are reset to default
Auto/manual switching option
Based on:
1) Latitude/Longitude precision to the minute, with time zone.
2) Option for both Sunrise/set & Twilight rise/set.
3) DST feature- 1 hour (with indication on the screen).
4) Weekly OFF.
5) Offset facility.
6) OFF Hours
1 C/O (SPDT)
16 A (NO) and
5 A (NC)
@ 240 VAC / 24 VDC
1000 W
6 A @ 250 VAC
AgSnO
2
40 mA at 24 VDC
3
50 X 10
30,000 cycles @ rated load
1 min
120 / 240
3.0 / 1.5
24 / 125 / 250
2.0 / 0.22 / 0.1
+/- 1 s/day @ 25°C.
3 Lines Text LCD
6 keys with 1 recessed reset button
-10°C to + 55°C
-10°C to + 60°C
95% Rh
2000 m
2
IP-20 for Terminals; IP-40 for Enclosure
Base / Din Rail
Flame Retardant UL-94V0
110 g max
IEC 61000-3-2
Ed. 3.0 (2005-11) Class A
IEC 61000-3-3
Ed. 2.0 (2008-06) Class A
IEC 61000-4-2
Ed. 1.2 (2001-04) Level II
IEC 61000-4-3
Ed. 3.0 (2006-02) Level III
IEC 61000-4-4
Ed. 2.0 (2004-07) Level IV
IEC 61000-4-5
Ed. 2.0 (2005-11) Level IV
IEC 61000-4-6
Ed. 2.2 (2006-05) Level III
IEC 61000-4-8
Ed. 1.1 (2001-03)
IEC 61000-4-11 Ed. 2.0 (2004-03) Class B
CISPR 14-1
Ed. 5.0 (2005-11) Class B
CISPR 14-1
Ed. 5.0 (2005-11) Class B
IEC 60947-5-1
Ed. 3.0 (2003-11) 2 kV
IEC 60947-5-1
Ed. 3.0 (2003-11) Level IV
IEC 61010-1
Ed. 2.0 (2001-02)
UL 508
Ed. 17 (1999-01) > 2000
M
UL 508
Ed. 17 (1999-01) < 3.5 mA
IEC 60068-2-1
Ed. 6.0 (2007-03)
IEC 60068-2-2
Ed. 5.0 (2007-07)
IEC 60068-2-6
Ed. 7.0 (2007-12) 5 g
IEC 60068-2-27 Ed. 4.0 (2008-02) 40 g, 6 ms
IEC 60068-2-27 Ed. 4.0 (2008-02) 30 g, 15 ms
FAQ's (FREQUENTLY ASKED QUESTIONS):
Q.1:In the event of power failure, do I lose all settings in the
device?
A.1:No, the battery has a power reserve of approx 6 years at
operating temperature range. In the absence of mains supply,
we can program the device as per the requirement. However,
during power failure, the relay or LED will not operate but the
on the screen
relay status can be observed
.
Q.2:What is Manual switching (override)? When do we use it?
A.2:When it is desired to switch ON/OFF the output before the
actual event i.e. (ON/OFF event), manual override can be used.
Press the MAN key for 3 s to toggle between ON Auto & Auto
mode when relay (output) is OFF and to toggle between Auto OFF
or Auto mode when the output is ON.
Q.3:What should I do to reset all settings and Clock?
A.3:Press the Reset (RST) key. All settings will set to default
and the clock will be reset to 00:00 & the date will be set to
01/01/2000.
Q.4:How should I change clock format from 12 h to 24 h?
A.4:Press '
' & 'MAN' key to switch from 12 h to 24 h clock
format and vice versa.
Q.5:How does ON AUTO and AUTO OFF feature help?
A.5:ON AUTO / AUTO OFF feature is used to immediately switch
the output ON / OFF respectively, overriding the current output
condition. If the output ON time is 6:15 p.m. & we want to switch
ON the output earlier, at 5:30 p.m. then set the mode as 'ON
Auto'. The output will be switched ON immediately. The mode will
automatically change to 'Auto' at 6:15 p.m. which is the next auto
event. Similarly the output can be switched OFF earlier than the
output OFF time using the Auto OFF feature.
Q.6:I want to switch OFF the output of Astro for a particular time
interval without affecting the main program. Which feature
should I use?
A.6:You can use 'OFF-Hours' feature to switch OFF the output for
a particular time period. To set OFF Hour feature, select'OTH'
menu and then select 'OFHR'.
Q.7:How can I switch the output 'ON' 30 min after sunset?
A.7:Use the Offset feature to change the ON time or OFF time of
the output. To set offset, select 'OUT' menu and then select
'OFSR' to set offset for rise & 'OFSS' to set offset for set. To switch
ON the output 30 min after sunset, set 'OFSS' as 'POS' (positive)
and enter the time as 30 min.
Q.8:I'm using Astro for my company's street lights and I want
these lights to be switched OFF from Saturday evening to
Monday morning. Which feature should I use?
A.8:You can use the Weekly-OFF feature for this purpose. To use
this feature, select 'OTH' menu and then select 'WOFF'. Then
select 'SA' as the start day. Enter the start time in hours and
minutes. Similarly, enter 'MO' as the end day and time in hours
and minutes. If you have selected same day & time for start as
well as end, then 'WOFF' is not applicable.
NOTE:
1. If DST is applicable in your region, first set the DST and
then set the clock.
2. Due to properties of some lamps, it might take a few
minutes for the lamps to illuminate completely even after
the output has been switched ON.
3. Product innovation being a continuous process, we reserve
the right to alter specifications without prior notice.
CAUTION:
1. Always follow instructions stated in this manual.
2. Before installation ensure that the specifications agree with
the intended application.
3. Installation should be done by skilled electrician only.
4. Inductive loads should be equipped with interference
supressors like varistors, RC snubbers.
5. Use of contactors is recommended if load exceeds the
contact rating.
ASTRONOMICAL TIME SWITCH
Astro
Mini
T2DDT7
Cat. No. :
RoHS
T2DDT8
OVERALL DIMENSIONS:
Base / Din Rail Mounting
36.0
L
N
ESC
OK
RST
MAN
17.0
18
15
16
65.0
CONNECTION DIAGRAM:
TS
NO
NC
L
N
18
15
16
P
LOAD
N
TERMINAL DETAILS :
0.54 N.m (5 Lb.in)
Terminal screw - M2.5
3.5 mm
1 x 0.2....3.3 mm
Solid Wire
1 x 24 to 12
AWG
Use Copper Conductors Only, 60/75° C.
Viewing the Output ON & OFF Time for the Day
To view OFF & ON time for the day, press '
' & '
respectively. This is possible only when the device is in run
mode & not in edit mode.
Ouptut OFF
Output ON
Time
Time
SA
00:00
07:07
18:10
ON
ON
AUTO
OFF
Setting AM/PM (12 Hour) or 24 Hour Display
To change the time format from 12 h to 24 h & vice versa,
press '
' & 'MAN' keys simultaneously.
CITY CODE CHART*
To view the city code chart number, press 'ESC' key 4 times.
In case the city code chart is lost or misplaced, order the city
code chart by sending an email to:
marketing@gicindia.com or sales@gicindia.com or
download it from: www.gicindia.com
'
TLL002_11
Need help?
Do you have a question about the Astro Mini and is the answer not in the manual?
Questions and answers