GENERAL WIRING DIAGRAM

4
Optional Surge
Suppressor
Optional Potential
Transformers for
voltages above 600 V
A
0
B
0
C
0
LOAD
1
NOTE: The use of potential transformers
has not been evaluated by UL
!
IMPORTANT INSTALLATION NOTE
• This unit accepts 1.0V full-scale output Current
Transformers (CTs) only.
• Do not use 0-5A OUTPUT Current Transformers
(e.g., 200:5 type CTs) without H-6902B Adapter.
Consult Factory
• Enclose unit by bolt and nut or use a padlock to
secure.
2
L-1
ØA
L-2
ØB
L-3
ØC
For use with single or three phase AC circuits only, 120 to
600 VAC, 50–60 Hz. For single phase operation, connect L-1
and L-2 only. Maximum current consumption 50 mA.
FUSES: 600 V 1/4 AMP, 100 KAIC
VERIS INDUSTRIES, INC.
1-800-354-8556
L-1
L-2
H-6000 SERIES
L-3
kW/kWH TRANSDUCER
C
®
NRTL/C
LINE VOLTAGE
3
UNDERVOLTAGE SET
% of full voltage
(For 208V, add 10%
to scale, i.e. 85 = 95%)
MAX. PULSE/SEC.
kWH
WHT
ØA
BLK
PULSE (N.O.)
WHT
kW
ØB
PHASE
4-20 mA
BLK
Loss/Reversal
WHT
PHASE LOSS
On-Normal
ØC
BLK
N.C.
Orient CT arrow
towards load
Observe polarity
(color coding) of
wiring for CTs
LINE
5892
kWH
®
16
kW (mA)
6
®
DC Supply
Voltage
+
-
5
kWH Pulse
Output
Under Voltage/Phase Loss
(Opens on alarm)
NOTE: Consult factory for
single phase installation
1
Accepts 1.0 V output CTs only!
Size CT appropriately for you applications
CT rating must be greater than maximum current monitored.
Orient CT arrow towards load
Observe polarity (color coding) of wiring for CTs
2
To interface with 5A output CTs, consult factory.
Mandatory Fuse or breaker per NEC.
Max. current draw is 50 mA. Installer must ensure
compliance with local and national codes (fuse rating
3
100 KAIC max.)
Line Voltage Selector.
Set to match line voltage
4
Undervoltage/phase Set-point.
Phase loss output opens on alarm when below set
percentage.
5
KWH Consumption Pulse Rate Selection
Sets maximum pulses per second at full scale operation.
Set for desired rate compatible with your automation
system.
6
Optional KW/KWH displays.
See OPTIONAL DISPLAYS section.
KW Demand Analog 4-20 mA Output
7
Provides instaneous KW demand analog output for input
to automtion system.
Requires external 12- 24 VDC supply.
8
Install Resistor for KW Voltage Output
For automation systems requiring a voltage, rather than
current, KW analog output, install appropriately sized
resistor as shown.
2
-
7
+