Panasonic DPS-400 Series Instruction Manual

Panasonic DPS-400 Series Instruction Manual

Head separated digital pressure sensor controller

Advertisement

Quick Links

Head Separated Digital Pressure Sensor Controller
DPS-400 Sreies
Thank you very much for purchasing Panasonic products. Please read this Instruc-
tion Manual carefully and thoroughly for the correct and optimum use of this product.
Kindly keep this manual in a convenient place for quick reference.
Never use this product in a device for personnel protection.
In case of using devices for personnel protection, use products which meet laws and standards,
such as OSHA, ANSI or IEC etc., for personnel protection applicable in each region or country.
1
PART DESCRIPTION
Select 1 indicator (Yellow)
Select 2 indicator (Yellow)
Comparative output 1 op-
Comparative output 2 op-
eration indicator (Orange)
eration indicator (Orange)
MODE indicator: RUN (Green)
MODE indicator: ZERO (Yellow)
Decimal point
mark (Note 1, 2)
MODE indicator: NO / NC (Yellow)
Digital display (Green / Red)
Notes: 1) 7KH DERYH ¿JXUH VKRZV WKH FRPSRXQG SUHVVXUH W\SH RU YDFXXP SUHVVXUH W\SH DPS-401. Positions of the decimal
point mark and the pressure unit on the name plate for positive pressure type DPS-402 GLIIHU IURP WKH DERYH ¿JXUH
2) The decimal point is used in RUN mode, threshold value setting mode, or peak / bottom hold function. It is
not used in other modes.
2
MOUNTING
How to mount
1. Fit the rear part of the mounting section of the
controller on a DIN rail.
2. Press down the rear part of the mounting section
RI WKH XQLW RQ WKH ',1 UDLO DQG ¿W WKH IURQW SDUW RI
the mounting section to the DIN rail.
How to remove
1. Push the controller forward.
2. Lift up the front part of the controller to remove it.
Note: Take care that if the front part is lifted without pushing the controller forward, the hook on the rear portion of the
mounting section is likely to break.
3
CONNECTION OF PRESSURE SENSOR HEAD
Make sure that the power supply is OFF while connecting or removing the pres-
sure sensor head DPH-100 series (optional).
This product can automatically recognize the connected pressure sensor head.
When the pressure sensor head is replaced, the threshold value and the zero-
adjustment value change. Therefore, set those values again.
How to connect
Insert the connector of the pressure sensor head
DPH-100 series (optional) into the connector area
for the pressure sensor head of this product.
How to disconnect
Pressing the release lever attached to the connec-
tor of the pressure sensor head, pull out the con-
nector.
Note: Do not pull by holding the cable without pressing the release lever, as this can cause cable break or connector break.
<Terminal arrangement>
Terminal No.
1
1
Pressure sensor head power supply
2
2
3
3
4
4
Model discrimination signal
4
CONTROLLER CASCADING
Make sure that the power supply is OFF while adding or removing the series
connection type.
In case 2 or more the series connection types are connected in cascade, make
sure to mount them on a DIN rail.
The maximum 11 the controllers using sub cables CN-72-C RSWLRQDO FDQ EH
added to a controller using a main cable CN-74-C RSWLRQDO 
When connecting 2 or more in cascade, use the sub cable for the second series
connection type onwards.
For mounting and removing the controller, refer to "
INSTRUCTION MANUAL
MJE-DPS400 No.0027-91V
WARNING
Jog switch
Press: Threshold value setting
MODE key
&RQ¿UP VHWWLQJ FRQWHQWV
Turn: Threshold value setting
Select Modes
Select setting items
Cancel during setting
MODE indicator: OUT (Yellow)
MODE indicator: CUSTOM (Yellow)
MODE indicator: PRO (Yellow)
Pressure unit (Note 1)
2. Press down
35mm width DIN rail
1. Push forward
2. Lift up
Connector area for the
pressure sensor head
Connector of the pressure
sensor head
DPH-100 series (Optional)
Release lever
Terminal name
Analogue input
0V
MOUNTING."
2
How to cascade
1. Mount the controllers, one by one, on the
DIN rail.
2. Slide the controllers next to each other,
and connect the quick-connection ca-
bles.
3. Mount the end plates MS-DIN-E (option-
al) at both the ends to hold the control-
OHUV EHWZHHQ WKHLU ÀDW VLGHV
4. 7LJKWHQ WKH VFUHZV WR ¿[ WKH HQG SODWHV
How to remove
1. Loosen the screws of the end plates.
2. Remove the end plates.
3. Slide the controllers and remove them
one by one.
5
I/O CIRCUIT DIAGRAM
Note: The quick-connection sub cable does not have +V (brown) and 0V (blue). The power is supplied from the con-
nector of the main cable.
<Terminal arrangement>
1
2
4
1. Fit
3
6
COMPARATIVE OUTPUT CHANNEL SWITCHING
Press the MODE key for 2 sec. or more to switch the
comparative output 1 / 2.
Comparative output 1 can be set when the Select 1 in-
dicator (yellow) lights up, and the comparative output 2
can be set when the Select 2 indicator (yellow) lights up.
7
OUTPUT MODE AND OUTPUT OPERATION
The EASY mode, window comparator mode, hysteresis mode, forced ON output
mode, or forced OFF output mode can be selected individually as the comparative
output mode 1 or the comparative output 2.
However, the comparative output 2 cannot be set to the window comparator
mode.
For details, refer to "
EASY mode
The comparative output ON / OFF state can be controlled in this mode.
SL
0
Comparative
ON
output
OFF
Note: Hysteresis can be set to "
For setting method, refer to <PRO 1: Hysteresis setting> in "
Window comparator mode
In this mode, the ON or OFF state of the comparative output is controlled with a
pressure in the set range.
2_SL
1_SL
0
Comparative
ON
output
OFF
Notes: 1) Hysteresis can be set to "
For setting method, refer to <PRO 1: Hysteresis setting> in "
2) Window comparator mode cannot be used as the comparative output 2.
For details, refer to "
End plate
MS-DIN-E (Optional)
(Brown) +V (Note)
Load
(Black) Comparative output 1
(White) Comparative output 2
(Blue) 0V (Note)
Terminal No.
Terminal name
1
+V
2
Comparative output 1
3
0V
4
Comparative output 2
OUTPUT MODE."
12
H (Hysteresis)
H: Hysteresis (Note)
In case of compound pressure type or positive pres-
sure type, hysteresis is set to the lower pressure side.
In case of vacuum pressure type, hyster-
esis is set to the lower vacuum side.
" (1% F.S.), "
" (2% F.S.) or "
" (5% F.S.).
14
PRO MODE."
H (Hysteresis)
H: Hysteresis (Note 1)
H (Hysteresis)
In case of compound pressure type or positive pres-
sure type, hysteresis is set to the lower pressure side.
In case of vacuum pressure type, hyster-
esis is set to the lower vacuum side.
" (1% F.S.), "
" (2% F.S.) or "
14
PRO MODE."
12
OUTPUT MODE."
Communication window
Sub cable
CN-72-C 2SWLRQDO
Slide
Main cable
CN-74-C 2SWLRQDO
End plate
MS-DIN-E (Optional)
Slide
Load
+
12 to 24V DC
±10%
-
Select 1 indi-
Select 2 indi-
cator (Yellow)
cator (Yellow)
" (5% F.S.).

Advertisement

loading

Summary of Contents for Panasonic DPS-400 Series

  • Page 1 MS-DIN-E (Optional) Thank you very much for purchasing Panasonic products. Please read this Instruc- OHUV EHWZHHQ WKHLU ÀDW VLGHV tion Manual carefully and thoroughly for the correct and optimum use of this product.
  • Page 2 Hysteresis mode Key lock function The comparative output ON / OFF state can be controlled with randomly set hys- The key lock function prevents key operations so that the conditions set in each set- teresis in this mode. ting mode are not inadvertently changed. If operating the jog switch or MODE key after key lock is set, “...
  • Page 3 CUSTOM MODE Item Default setting Description Sets response time. Response time “ ´  V ³ ´  V ³ ”: 1ms, “ ”: 5ms When MODE indicator: CUST (yellow) lights up, response Jog switch setting “ ”: 10ms, “ ”: 50ms, “...
  • Page 4 Phone: +81-568-33-7861 FAX: +81-568-33-8591 Europe Headquarter: Panasonic Electric Works Europe AG Rudolf-Diesel-Ring 2, D-83607 Holzkirchen, Germany Phone: +49-8024-648-0 US Headquarter: Panasonic Electric Works Corporation of America 629 Central Avenue New Providence, New Jersey 07974 USA Phone: +1-908-464-3550 PRINTED IN JAPAN...

This manual is also suitable for: