Lancaster Water Treatment X FACTOR LX15 Series Installation, Operating And Service Manual

Electronic water softener with the x-factor control valve commercial series

Advertisement

F I L T E R
INSTALLATION, OPERATING AND
SERVICE MANUAL
ELECTRONIC WATER SOFTENER WITH
THE X-FACTOR CONTROL VALVE
COMMERCIAL SERIES
LX15, LX2 & LX2QC
Congratulations on purchasing your new Lancaster Water Filter. This unit is designed to give you
many years of trouble free service. For servicing and future inspection purposes, please file this
booklet with your important documents.
In the event that you need assistance for servicing your water softener, please first contact the
professional contractor who installed the system.
PAGE 1

Advertisement

Table of Contents
loading

Summary of Contents for Lancaster Water Treatment X FACTOR LX15 Series

  • Page 1 ™ F I L T E R INSTALLATION, OPERATING AND SERVICE MANUAL ELECTRONIC WATER SOFTENER WITH THE X-FACTOR CONTROL VALVE COMMERCIAL SERIES LX15, LX2 & LX2QC Congratulations on purchasing your new Lancaster Water Filter. This unit is designed to give you many years of trouble free service.
  • Page 2: Table Of Contents

    TABLE OF CONTENTS Job Specifications ......................... 2 Inspection, Mineral Loading and Assembly ................... 3 Pre-Installation Review ......................... 4 General Installation and Service Warnings .................. 4 Bypass Valve Operation ....................... 5 Installation Instructions, Diagrams ....................6-9 Placing Filter into Service ......................10 General Operation ........................
  • Page 3: Inspection, Mineral Loading And Assembly

    INSPECTION, MINERAL LOADING AND ASSEMBLY Commercial water filters are shipped in multiple cartons: - mineral tank with bottom distributor and riser pipe - control valve - optional alternator valve or no hard water bypass valve - bag(s) of gravel support bed (for 21" diameter and larger mineral tanks) - bags of water mineral mineral Quantity of components are specific for the individual type filtering system ordered.
  • Page 4: Pre-Installation Review

    GENERAL INSTALLATION PRE-INSTALLATION AND SERVICE WARNINGS REVIEW The control valve and fittings are not designed to support This water filter is not to be used for treating water the weight of the system or the plumbing. that is microbiologically unsafe or of unknown quality without adequate disinfection before or after Do not use Vaseline, oils, other hydrocarbon lubricants or treatment.
  • Page 5: Bypass Valve Operation

    BYPASS VALVE (valves shown with optional meters) NORMAL OPERATION BYPASS OPERATION BYPASS VALVE BYPASS VALVE CLOSED OPEN INLET VALVE OUTLET VALVE INLET VALVE OUTLET VALVE OPEN OPEN CLOSED CLOSED DIAGNOSTIC MODE BYPASS VALVE OPEN INLET VALVE OUTLET VALVE OPEN CLOSED Normal Operation: Water flows through the control valve during service and also allows the control valve to isolate the media bed during the regeneration cycle.
  • Page 6: Installation Instructions, Diagrams

    INSTALLATION INSTRUCTIONS (All electrical & plumbing should be done in accordance to all local codes) 1. LOCATION: Place the filter where you want to install it, making sure it is on a clean, level and firm surface. The plug-in power adaptor is for dry locations only. Use an uninterrupted electrical outlet installed within 15 feet of the filter. Locate the filter so the distance between the drain and the filter is as short as possible.
  • Page 7 Series LX15 Injector LXCV15 Control Valve Inlet 1 1/2 Thread Specific model overall dimensions 1.93 TOT C L are available- Consult factory. 1.86 Outlet 1 1/2 Thread Drain Flow Control Regenerant Drain Port 1 1/4 NPT 8.60 6.44 3.25 3.25 1.50 4-8 UN Series LX2...
  • Page 8 SINGLE: ONE WATER FILTER WITH OPTIONAL METER. BACKWASH INITIATION CHOICES: METER IMMEDIATE, METER DELAYED, METER DELAYED + IMMEDIATE (WITH OPTIONAL METER ONLY), DAYS OVERRIDE (1-28), AUXILIARY INPUT (SEE CUSTOM PROGRAMMING AND APPLICATION MANUAL). BYPASS VALVE INLET OUTLET VALVE VALVE FLEXIBLE CONNECTORS UNION TYPE CONNECTORS ARE RECOMMENDED ARE RECOMMENDED...
  • Page 9 TYPICAL TWIN PARALLEL SYSTEM INSTALLATION DIAGRAM TWIN PARALLEL: TWO IDENTICAL FILTERS , EACH WITH ITS OWN OPTIONAL METER (IF ORDERED) TWIN PARALLEL: TWO IDENTICAL SOFTENERS, EACH WITH ITS OWN METER, ONLY ONE BRINE TANK. DAYS OVERRIDE OR METER DELAYED REGENERATION USED WITH OFFSET BACKWASH TIMES. METER DELAYED REGENERATION USED WITH OFFSET REGENERATION TIMES.
  • Page 10: Placing Filter Into Service

    PLACING FILTER INTO SERVICE Do not plug the transformer into the receptacle yet. Make sure inlet and outlet valves are to their closed positions. If using optional bypass, open bypass valve. Turn on main water supply. Open a cold water faucet. This will clear the line of any debris (solder, pipe dope, etc.) that may be in the line.
  • Page 11: Set Time Of Day

    SET TIME OF DAY Current time of day needs to be entered during initial installation, and adjusted when daylight saving time begins or ends. If an extended power outage occurs and depletes the on-board non-rechargeable coin cell battery, when power resumes the time of day should be reset and battery replaced.
  • Page 12: Low Battery

    LOW BATTERY A non-rechargeable coin cell battery is located on the circuit board, used only to maintain the time of day during power outages (all other information will be stored in memory no matter how long the power outage). The screen displays LOW BATTERY when the battery needs to be replaced.
  • Page 13: Specifications

    X FACTOR COMMERCIAL SERIES GENERAL SPECIFICATIONS Operating Pressure; Max (PSI) CAUTION: the filter cannot be subject to a vacuum due to loss of pressure (such as a water main break or submersible well pump check valve failure). Water Operating Temp; 40 to 110 Min to Max (°F) CAUTION: do not locate the filter where it or its connections (including the drain line and overflow lines) will ever be...
  • Page 14: Parts Diagrams

    X-FACTOR FRONT COVER AND DRIVE ASSEMBLY Drawing No. Order No. Description Quantity V3692-02LW LP Front Cover Assembly V3107-01 Motor Drive Bracket, Spring Clip, Drive Gear 12x36 and V3106-01 Drive Gear Cover V3757LP-BOARD PC Board When replacing the battery, align Correct positives and push down to fully seat.
  • Page 15 LX15 SERIES LXCV15 Control Valve Drive Cap Assembly, Downflow Piston, Spacer Stack Assembly and Main Body Drawing No. Order No. Description Quantity V3004 Drive Cap Assembly V3135 O-ring 228 V3407 Piston Downflow Assembly V3423 Backplate Dowel V3430 Spacer Stack Assembly V3178LP Back Plate V3419...
  • Page 16 LX2 SERIES LXCV2 Control Valve Drive Cap Assembly, Downflow Piston, Regenerant Piston, Spacer Stack Assembly and Main Body Drawing No. Order No. Description Quantity V3729 Brine Piston Assembly V3725 Piston Downflow Assembly V3452 O-ring 230 V3728 Drive Cap Assembly V3724 Washer Flat SS 1/4 V3642 Bolt BHCS S/S 1/4-20X1.25...
  • Page 17 LX2QC SERIES LXCV2QC Quick Connect Control Valve Drive Cap Assembly, Downflow Piston, Regenerant Piston, Spacer Stack Assembly and Main Body Drawing No. Order No. Description Quantity V3726 Brine Piston Assembly V3725 Piston Downflow Assembly V3452 O-ring 230 V3728 Drive Cap Assembly V3724 Washer Flat SS 1/4 V3642...
  • Page 18 LX2QC SERIES V3064 4 Inch Base Asy Drawing No. Order No. Description Quantity V3202-01 Base V3281 O-Ring 348 V3055 Flange Base Asy Drawing No. Order No. Description Quantity V3444 Screw Hexcap 5/16-18 x 2 SS V3293 Washer SS 5/16 Flat V3445 Washer Split Lock 5/16 SS V3447...
  • Page 19 LX15 SERIES LXCV15 Injector Valve Body and Injector Drawing No. Order No. Description Quantity V3967 Injector Body, Welded Assembly V3441 O-ring -226 V3968*** Injector Feed Tube V3177-01 Injector Screen V3969**** Injector Draw Tube V4349 Injector Cap (V3176 on valves prior to 4./5/2020) V3152 O-ring -135 V3010-152...
  • Page 20 LX2 & LX2QC SERIES LXCV2 and LXCV2QC Injector Valve Body Drawing No. Order No. Description Quantity V3477 Injector Cap WS1.5", 2" and 2"QC Drawings and Service Manual ge 32 V3152 O-Ring 135 V3727 Injector Body Assembly WS2 Injector Valve Body, ReÀ ll Flow Control and Injector See page 22 Injector Drawing No.
  • Page 21 Drain Line Flow Controls Page 40 WS1.5", 2" and 2"QC Drawings and Service Manual See drain line flow control washer section for available flow selections. Inline Plastic, 9 - 25 GPM PVC Elbow, 0.7-10 GPM Drain Line Flow Controls All drain line Á ow control housings are shipped without Á ow control washers. Item Part# Description...
  • Page 22 Drain Line Flow Control Washers Drain Line Flow Controls Order No. Description V3162-007 0.7 GPMDrain line flow control V3162-XXX V3162-010 1.0 GPMDrain line flow control V3162-xx Flow Rate V3162-013 1.3 GPMDrain line flow control Identi cation V3162-017 1.7 GPMDrain line flow control 5/8"...
  • Page 23 Optional Meter Assembly for 1.5” and 2” Valves (not included) Page 42 WS1.5", 2" and 2"QC Drawings and Service Manual Note: Be sure the proper meter size is programmed in the software. Standard meter cable used for spacing up to 3” between valve body and meter body, longer distance requires longer Meter Assembly for WS1.5 and WS2 Valves cable # V3221.
  • Page 24: Service Instructions

    Service Instructions 1) Drive Assembly Disassembly and Inspection: Remove the valve cover to access the drive assembly. The drive brac ket must be removed to access the drive cap assembly and the piston or the drive gear cover. It is not necessary to remove the PC board from the drive bracket to remove the drive bracket.
  • Page 25 Replace the motor if necessary. Do not lubricate the motor or the gears. To reinstall the motor, move the spring clip loop to the right and hold. Gently turn the motor while inserting so that the gear on the motor meshes with the gears under the drive gear cover.
  • Page 26 3) Main Piston and Regenerant Piston Disassembly and Inspection: Attached to the drive cap assembly is the main piston and depending on the configuration, a regenerant piston. The regenerant piston (the small diameter one behind the main piston) is removed from the main piston by unsnapping it from its disassembly latch.
  • Page 27: Troubleshooting

    TROUBLESHOOTING Problem Possible Cause Solution a. No power at electric outlet a. Repair outlet or use working outlet b. Control valve Power Adapter not plugged b. Plug Power Adapter into outlet or into outlet or power cord end not connect power cord end to PC Board connected to PC board connection connection 1.
  • Page 28 Problem Possible Cause Solution a. Bypass valve in bypass position optional a. Turn bypass handles to place bypass in service position b. Meter is not connected to meter b. Connect meter to three pin connection connection on PC Board if meter is labeled METER on PC Board installed c.
  • Page 29 Problem Possible Cause Solution a. Foreign material is lodged in control valve a. Open up control valve and pull out piston assembly and seal/ stack assembly for inspection. Press NEXT and REGEN buttons for 3 seconds to resynchronize software with piston position or disconnect power supply from PC Board for 5 seconds and then reconnect.
  • Page 30 Problem Possible Cause Solution a. Press NEXT and REGEN buttons for a. Control valve programmed for ALT A or B, nHbP, SEPS, or AUX MAV with out 3 seconds to resynchronize software having a MAV or NHBP valve attached to with piston position or disconnect operate that function power supply from PC Board for 5...
  • Page 31 NOTES PAGE 31...
  • Page 32 A DIVISION OF C-B TOOL CO. 1340 MANHEIM PIKE ● LANCASTER PA 17601-3196 ● TEL:717-397-3521 ● FAX: 717-392-0266 www.lancasterwatergroup.com ● E-mail: info@lancasterwatergroup.com 4/20 PAGE 32...