Huawei SUN2000-55KTL Series Quick Manual page 12

Hide thumbs Also See for SUN2000-55KTL Series:
Table of Contents

Advertisement

Installing DC Input Power Cables (Cold Forming Metal Contact)
Positive metal terminal
Negative metal terminal
Recommended: PV cable
that meets the 1500 V
standard
Installing DC Input Power Cables (Stamping Forming Metal Contact)
Positive metal terminal
Negative metal terminal
Recommended: PV cable
that meets the 1500 V
standard
If the voltage is a negative value, the DC input polarity is incorrect. Correct the polarity.
If the voltage is greater than 1500 V DC, too many PV modules configured to the same string.
Remove some PV modules.
Only after at least one PV string correctly connects to the MPPT1 circuit, can the SUN2000
enable the DC input detection function. Therefore, you are required to connect DC input power
cables to the MPPT1 circuit first.
UTXTC0001
(Amphenol)
Ensure that the cable
cannot be removed after
crimped.
Use a multimeter
to measure the
DC voltage.
UTXTC0002
(Amphenol)
Ensure that the cable
cannot be removed after
crimped.
Use a multimeter
to measure the
DC voltage.
11
Positive connector
Negative
Click
connector
Ensure
that the
locking
nut is
secured.
UTXTWA001
(Amphenol)
Positive connector
Negative
Click
connector
Ensure
that the
locking
nut is
secured.
UTXTWA001
(Amphenol)

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sun2000-60ktl series