Toshiba MMU-AP0057MH-E Installation Manual page 18

Air conditioner (multi type), indoor unit
Hide thumbs Also See for MMU-AP0057MH-E:
Table of Contents

Advertisement

3
Specify CODE No. [
] with temp. setup
/
buttons.
4
Select SET DATA [
] with timer time
/
buttons.
5
Push
button. When the display changes
from flashing to lit, the setup is completed.
• To change settings of another indoor unit,
2
repeat from Procedure
.
• To change other settings of the selected indoor
3
unit, repeat from Procedure
.
Use
button to clear the settings.
To make settings after
button was pushed,
2
repeat from Procedure
.
6
When settings have been completed, push
button to determine the settings.
When
button is pushed, "SETTING" flashes
and then the display content disappears and the
air conditioner enters the normal stop mode.
(While "SETTING" is flashing, no operation of the
remote controller is accepted.)
 Installing indoor unit on high
ceiling
When an indoor unit is installed on a ceiling higher than
the standard height, make the high-ceiling setting for
air volume adjustment.
• Follow the basic operation procedure
1
2
3
4
5
6
(
).
3
• For the CODE No. in Procedure
, specify [5d].
4
• Select the SET DATA for Procedure
from the
"Height list of ceiling possible to be installed" table on
page 8 in this manual.
33-EN
 When wireless remote
controller is used
Change the high-ceiling setting with the DIP switch on
the receiver section P.C. board.
For details, refer to the manual of the wireless remote
controller kit. The settings can also be changed with
the switch on the indoor microcomputer P.C. board.
* Once the setting is changed, setting to 0001 or 0003
is possible, however setting to 0000 requires a
setting data change to 0000 using the wired remote
controller (separately sold) with the normal switch
setting (factory default).
SW501-2
SW501-1
MCU
(IC501)
SET DATA
SW501-1
SW501-2
0000
OFF
OFF
(Factory default)
0001
ON
OFF
0003
OFF
ON
◆ To restore the factory defaults
To return the DIP switch settings to the factory defaults,
set SW501-1 and SW501-2 to OFF, connect a
separately sold wired remote controller, and then set
the data of CODE No. [5d] to "0000".
– 17 –
 Filter sign setting
According to the installation condition, the lighting time
of the filter sign (Notification of filter cleaning) can be
changed.
Follow to the basic operation procedure
1
2
3
4
5
6
(
).
3
• For the CODE No. in Procedure
, specify [01].
4
• For the [SET DATA] in Procedure
, select the SET
DATA of filter sign lighting time from the following
table.
SET DATA
Filter sign lighting time
0000
None
0001
150 H
0002
2500 H (Factory default)
0003
5000 H
0004
10000 H
 To secure better effect of
heating
When it is difficult to obtain satisfactory heating due to
installation place of the indoor unit or structure of the
room, the detection temperature of heating can be
raised. Also use a circulator or other device to circulate
heat air near the ceiling.
Follow to the basic operation procedure
1
2
3
4
5
6
(
).
3
• For the CODE No. in Procedure
, specify [06].
4
• For the set data in Procedure
, select the SET
DATA of shift value of detection temperature to be
set up from the table below.
SET DATA
Detection temp shift value
0000
No shift
0001
+1 °C
+2 °C
0002
(Factory default)
0003
+3 °C
0004
+4 °C
0005
+5 °C
0006
+6 °C
34-EN