Siemens Sentron SB TP01 Series Information And Instruction Manual page 26

Systems breaker
Table of Contents

Advertisement

System Configuration
The SEQUENCE CONFIG screen will open with both the posi-
tive and negative sequence boxes highlighted. When the Up
key is pressed, positive sequence is selected (checked).
When the Down
key is pressed, negative sequence is
selected (checked). Pressing the Enter
light to the ALARM ON INCORRECT SEQUENCE check box.
When the Up
key is pressed, the alarm is enabled
(checked). When the Down
abled (unchecked). Another press of the Enter
the highlight back to the positive and negative sequence
check boxes. Pressing the Escape
the screen and, (if changes were made) the standard change
confirmation screen will be displayed. If the Alarm box is
checked and the system phase sequence does not match the
selected phase sequence configuration, an alarm will be
issued. This is a local alarm only and is not reported via
ACCESS communication, but will activate the Alarm Relay if
installed.
A PHASE SEQUENCE ALARM screen will be displayed any
time the phase sequence alarm is active. Pressing any key will
exit the alarm screen and return the user to the normal menu
screens. The user can then change the phase sequence con-
figuration or disable the phase sequence alarm if desired.
Thirty seconds after the last key press, if the alarm is still
active, the phase sequence alarm screen will again be
displayed.
22
key moves the high-
key is pressed, the alarm is dis-
key moves
key at any time will exit
Potential Transformer Rating
To inform the trip unit which potential transformer (PT) is used
in your system, select PT Rating from the System Configura-
tion menu. The following screen appears:
Make sure the PT installed in the system matches the PT Rating
(line-to-line) setting. Use the table below for various system
voltages:
Table 4.1 PT Ratings
For System Voltage of:
120/208V, 120/240V, 220V
277/480V, 415V
575V
Use the Up
or Down
value. When finished, press Escape
to accept the change.
Short Circuit Protection
The short time and instantaneous overcurrent protective func-
tions can be enabled or disabled from the System Configura-
tion menu. To specify the extent of such short circuit protection
required in your system, select Short Circuit Prot from the
System Configuration menu. The following screen appears:
For short circuit protection either short time, or instantaneous
tripping, or both can be chosen. Select these types of protec-
tion by pressing the Up
appears in the desired box(es). When the desired box(es) are
checked, press Escape
the change.
Select This PT Rating:
240V
480V
600V
Arrow keys to select the desired
, and then press Enter
or Down
Arrow key until a check
, and then press Enter
to accept