Download Print this page

Siemens SIPROTEC 5 Hardware Description Manual page 17

Hide thumbs Also See for SIPROTEC 5:

Advertisement

6.4
Relay Outputs
Standard Relay (Type S)
Making capacity
Breaking capacity
AC and DC contact voltage
Permissible current per contact (continuous)
Permissible current per contact (switching on and
holding)
Short-time current across closed contact
Total permissible current for contacts connected to
common potential
Switching time OOT (Output Operating Time)
Additional delay of the output medium used
Max. rated data of the output contacts in accordance
with UL certification
Interference suppression capacitors across the
contacts
Fast Relay (Type F)
Making capacity
Breaking capacity
AC and DC contact voltage
Permissible current per contact (continuous)
Permissible current per contact (switching on and
holding)
Short-time current across closed contact
Total permissible current for contacts connected to
common potential
Switching time OOT (Output Operating Time)
Additional delay of the output medium used
Rated data of the output contacts in accordance with
UL certification
SIPROTEC 5, Hardware Description, Manual
C53000-G5040-C002-F, Edition 06.2019
Max. 1000 W (L/R = 40 ms)
Max. 3600 VA (power factor ≤ 0.35, 50 Hz to 60 Hz)
Max. 30 W (L/R = 40 ms)
Max. 360 VA (power factor ≤ 0.35, 50 Hz to 60 Hz)
250 V
5 A
30 A for 1 s (make contact)
250 A for 30 ms
5 A
Make time: typical: 8 ms; maximum: 10 ms
Break time: typical: 2 ms; maximum: 5 ms
DC 24 V, 5 A, General Purpose
DC 48 V, 0.8 A, General Purpose
DC 240 V, 0.1 A, General Purpose
AC 240 V, 5 A, General Purpose
AC 120 V, 1/6 hp
AC 250 V, 1/2 hp
B300
R300
4.7 nF, ± 20 %, AC 250 V
Max. 1000 W (L/R = 40 ms)
Max. 3600 VA (power factor ≤ 0.35, 50 Hz to 60 Hz)
Max. 30 W (L/R = 40 ms)
Max. 360 VA (power factor ≤ 0.35, 50 Hz to 60 Hz)
250 V
5 A
30 A for 1 s (make contact)
250 A for 30 ms
5 A
Make time: typical: 4 ms; maximum: 5 ms
Break time: typical: 2 ms; maximum: 5 ms
DC 24 V, 5 A, General Purpose
DC 48 V, 0.8 A, General Purpose
DC 240 V, 0.1 A, General Purpose
AC 120 V, 5 A, General Purpose
AC 250 V, 5 A, General Purpose
AC 250 V, 0.5 hp
B300
R300
Technical Data
6.4 Relay Outputs
213

Advertisement

loading