LG B30AWYN7G5A Manual page 46

Ceiling concealed duct. inverter 50hz/r410a 5csb0-02b(replace: 5csb0-02a)
Table of Contents

Advertisement

Ceiling Concealed Duct
11. E.S.P.(External Static Pressure) setting for
11.2 Wide Wired Remote Controller
How to Set E.S.P?
CAUTION:
• If you set ESP incorrectly, the air conditioner may malfunction.
• This setting must be carried out by a certificated-technician.
Function code,
ESP code
ESP value
❊ When setting ESP value on the product without very weak wind or power wind function, it may not work.
36 _ Inverter
50Hz/R410A
If pressing
button long for 3
1
seconds, it enters into remote
controller setter setup mode.
- If pressing once shortly, it enters
into user setup mode. Please press
more than 3 seconds for sure.
2
If entering into ESP setup mode by using
button, it indicates as the picture
below.
Select ESP fan step by pressing
3
button. (01: very low, 02: low,
03: medium, 04: high, 05: power)
Move to ESP value setting by pressing
4
button.
(It is 000 when delivering
from the warehouse.)
Press
button to setup ESP value.
5
(It is possible to setup ESP
value from 1 to 255, and 1 is
the smallest and 255 is the
biggest.)
ESP step
Function Code
ESP value