Download Print this page

Bosch DS240 Installation Instructions Manual page 4

Bosch power tools smoke alarm - beam smoke detector user manual

Advertisement

6.0
WIRING
Only apply power after all connections have been made
and inspected.
CAUTION
• Wire the transmitter and receiver terminals as follows (see
Figure 6 ).
NOTE: Do not install on verified fire circuits.
Alarm Loop
Fire Alarm
Control Panel
Power Loop –
Power Loop +
Figure 6 - Wiring a Single Unit
NOTE: Do not coil excess wiring inside the units.
• Transmitter Terminals 1 & 2:
Input power terminals. See Section 2.0 Specifications on page 1
for the operating voltages of the DS240 and DS241.
• Receiver Terminals 1, 2 & 3:
Form "C" Auxiliary relay contacts. Terminals 1 & 2 will open on fire
alarm; Terminals 2 & 3 will close (short) on fire alarm.
• Receiver Terminals 4 & 5:
Normally Open Fire alarm contacts will close (short) on fire
alarm.
• Receiver Terminals 6 & 7:
Normally Closed Trouble contacts will open for trouble alarm.
• Receiver Terminals 8 & 9:
Input power terminals. See Section 2.0 Specifications on page 1
for the operating voltages of the DS240 and DS241.
NOTE: Resetting from a fire alarm requires power to the receiver to
be interrupted for at least one second. If not provided by the
fire panel, it can be accomplished by installing a switch in
series with Terminal 9.
Remote Indicator Plate
The DIS2000 Remote Indicator Plate is shipped with the DS240/
DS241 as a standard accessory. Although the Remote Indicator Plate
is not required, the manufacturer recommends its installation to
provide a means of checking the condition of the detector from ground
level.
If a DIS2000 or DIS240 Remote Indicator Plate will be used, install
the Remote Indicator Connector to the receiver now (see Figure 7).
NOTE: The DIS240 remote indicator should be located no further
than 100 ft (31 m) from the receiver and wired with 18 AWG
(1.2 mm) or larger wire. The DIS2000 may be wired up to
500 ft (152 m) from the receiver.
Page 4
P/N: 22066P
Receiver
AUX.
FIRE
TRBL
RELAY
ALARM
ALARM
VDC
ALARM
+
1
2
3
4
5
6
7
8
9
End of Line
resistor
1
2
+
Transmitter
• Slide the Remote Indicator Connector over the pins just to the
right of the receiver's terminal strip.
Fire Alarm
Control Panel
Figure 7 - Connecting the DIS2000 Remote Indicator Plate
NOTE: If connecting a DIS240 Remote Test/Indicator Plate,
consult the DIS240 Installation Instructions (P/N: 24171).
7.0
SET-UP
Before starting this section, confirm that all connections have been
made and are secure, then apply power to both units.
• Press the Aim Mode button (directly above the green LED) on the
transmitter (see Figure 8 ). This allows the transmitter to power
up while its cover is off.
Figure 8 - Cutout View of Transmitter Circuit Board Showing
- Check the transmitter's green LED. It should be flashing on
and off.
© 2004 Bosch
DS240/DS241 Receiver
Fire
Trouble
10 to 32
Alarm
Alarm
VDC
– +
Remote Indicator
4
5
6
7
8
9
Plate Connector
Alarm Loop
EOL
Power Loop –
Power Loop +
DIS2000
Violet
Voltage Monitor
Black
Ground (–)
Red
Red LED
Yellow
Yellow LED
Green
Green LED
AIM MODE
BUTTON
GREEN
LED
Aim Mode Button Location
DS240/DS241 Installation Instructions

Advertisement

loading

This manual is also suitable for:

Ds241