Wireless settings menu
WIRELESS
M
Through the wireless settings menu you can set the master ID and sensor ID.
Calibration menu
CALIBRATION
M
All the measurements can be tuned through the calibration menu. The humidity tuning is available only in RH models.
ML-SER tool display shows how much the current value is tuned.
Produal Oy
Keltakalliontie 18, 48770 Kotka FINLAND
 
OK
OK
1
Modbus ID
MASTER ID
Master ID (MID)
[1...63]
IMPORTANT: The device wireless network settings are made by using either FLSER or ML-SER
commissioning tool. When the wireless settings are made with one tool, the other tool cannot be used to
change or check the wireless settings.
OK
OK
0
Modbus ID
Offset: CO2ppm
CO
tuning
2
[±200 ppm]
The CO
value can be adjusted by 10 ppm steps.
2
The temperature value can be adjusted by 0.1 °C steps.
The humidity value can be adjusted by 1 % steps.
Tel: +358 10 219 9100 / Fax: +358 5 230 9210
Information is subject to change without prior notice.
OK
1
SENSOR ID
Sensor ID (SID)
[OFF / 1...99]
OK
On
0.0
ABC-Logic
Offset: °C
ABCLogic calibration
Temperature measurement
[On / Off]
tuning [±3,0 °C]
USER GUIDE
OK
OK
0
Offset: %RH
Humidity measurement
tuning [±5 %RH]