Download Print this page

Produal HDHFL User Manual page 2

Advertisement

7.
Connect the power supply.
"OK" flashes on the FLSER display. When the flashing stops, the transmitter is ready to start the communication
with the FLTA base station.
8.
FLSER tool starts to display the communication signal strengths between the FLSER and transmitter.
The bigger number indicates the strength of the received signal sent by FLSER and the smaller number the
strength of received signal sent by the transmitter.
RSSI = Received Signal Strength Indication:
1...2 = poor
3...5 = satisfactory
6...9 = good
10. Go to the FLTA base station and check that the signal strengths are adequate.
11. Set the FLSER tool switch to the OFF position.
The transmitter starts to communicate with the FLTA base station.
Reading the transmitter information from FLTA base station
The transmitter information can be read from the FLTA base station in three ways:
INDICATOR LIGHT FUNCTIONS
A. Green indicator light
B. Red indicator light
The indicator lights are on for 0.5 seconds during the device start-up.
The green indicator light flashes when the device sends information to the base station. The red indicator light turns on
when the message transmit to the base station fails 20 consecutive times.
Produal Oy
Keltakalliontie 18, 48770 Kotka FINLAND
 
8
RSSI 9
From the display
21.0
Temperature
6 TE°C
720
CO
level
2
6 LUX
56.0
Humidity (only in RH models)
6 RH%
Through the analogue outputs
Via Modbus
Tel: +358 10 219 9100 / Fax: +358 5 230 9210
Information is subject to change without prior notice.
USER GUIDE
HDHFL
info@produal.fi
www.produal.com
2 (8)