The transmitter can convert the input signal into a current or voltage
signal ("nominal output range"):
0 ... 5 V
0 ... 10 V
0 ... 20 mA
4 ... 20 mA
The start value adjusted for the measuring range (see page 18) is rep-
resented by the lower limit of the nominal output range. The adjusted
end value is represented by the upper limit of the nominal output
range. Within the usable signal range (see table below), the input
value is correctly represented by the output signal.
When the input signal lies outside the usable signal range, the output
signal is set to a substitute value. This is signaled by the error LED.

Nominal Output Range

0 ... 5 V
0 ... 10 V
0 ... 20 mA
4 ... 20 mA

Measuring Ranges

A 20220P0/...
Usable Signal Range
0 ... 5.125 V
0 ... 10.25 V
0 ... 20.5 mA
3.8 ... 20.5 mA
35