Page 1
Installation, use and maintenance manual Gitié ARAY Integrated package for outdoor installation with absorption heat pump and gas condensing boiler...
Page 2
The rights of those who have legitimately filed the registered trademarks contained within this publication are not affected. With the aim of continuously improving the quality of its products, Robur S.p.A. reserves the right to modify the data and contents of this Installation, use and maintenance manual without prior notice.
INDEX OF CONTENTS Introduction 3.11 AY00-120 unit combustion products exhaust ................p. 4 ..................... p. 29 Recipients ................p. 4 3.12 Possible flue ..............p. 29 Control device ..............p. 4 3.13 AY00-120 Unit flue gas condensate discharge II Symbols and definitions ..........p. 4 ..................... p. 30 II.1 Key to symbols ..............
AY00-120 boiler. DDC Control (Direct Digital Controller) = optional Robur adjust- WARNING ment device to control one or more Robur appliances (GAHP heat pumps, GA chillers and AY00-120 boilers) in ON/OFF mode. RB100/RB200 Devices (Robur Box) = optional interface devices...
Page 5
Warnings Electrocution hazard personnel. In case of danger, switch off the electrical power and gas Disconnect the electrical power supply before any oper- supplies only if this can be done in total safety. ation on appliance components. Do not entrust children, persons with physical, sensory ...
Warnings Routine maintenance Any other applicable law, standard and regulation. ▶ Proper maintenance assures the efficiency and good op- III.3 EXCLUSIONS OF LIABILITY AND eration of the appliance over time. WARRANTY Maintenance must be performed according to the man- ufacturer's instructions (see Chapter 7 ...
Features and technical data FEATURES AND TECHNICAL DATA The Gitié ARAY package consists of a heat pump GAHP-AR and a Ionization flame control box. ▶ condensing boiler AY00-120. Double shutter electric gas valve. ▶ Antifreeze functions for hydraulic circuit. ▶ FEATURES 1.1.2 AY00-120 Unit features...
Features and technical data DIMENSIONS Figure 1.1 Size (Standard ventilation) Figure 1.2 Dimensions (silenced fan)
Page 9
Features and technical data Figure 1.3 Service plate 2-pipe group (KIT/2 C0 and C1) - Detail of water/gas fittings Outlet water fitting Ø 1 1/2"F Inlet water fitting Ø 1 1/2"F Boiler condensate drain AY00-120 Gas fitting Ø 3/4"M Figure 1.4 Service plate 4-pipe group (base version and KIT/4 C1) - Detail of water/gas fittings AY - Water outlet fitting Ø...
Features and technical data COMPONENTS Figure 1.5 Internal components - front view Fan (silenced version) Oil pump Tapping point for flue analisys Water delivery fitting: 1 1/4"F Gas valve Water return fitting: 1 1/4"F Combustion air hose Gas connection...
Page 11
Features and technical data Figure 1.6 Version components BASE version (2 independent circuits without circulating pumps) Kit/4 C1 (2 independent circuits with onboard circulating pumps) Kit/2 C0 (single circuit with two 2-way motorised valves) Kit/2 C1 (single circuit with onboard circulating pumps) Installation, use and maintenance manual –...
Page 12
Features and technical data Figure 1.7 Internal components - left side view Ø 80mm flue gas exhaust Flame sensor / ignition electrodes PT1000 flue exhaust temperature probe Electrical panel...
Page 13
Features and technical data Figure 1.8 Internal components - right side view TG generator temperature probe Defrosting valve Safety valve Return temperature probe Flow switch Teva evaporator temperature probe Flow temperature probe Air-vent manual valve Limit thermostat Installation, use and maintenance manual –...
Features and technical data WIRING DIAGRAMS Figure 1.9 Unit GAHP-AR wiring diagram SCH1 Controller S61 Gas solenoid valve Ambient air temperature sensor SCH4 AR11 electronic board Generator limit thermostat Generator temperature sensor Power supply terminal block Water flow switch TEVA Evaporator outlet temperature sensor CNTBOX Flame controller Defrosting valve Fumes temperature sensor or generator fin...
Page 15
Features and technical data Figure 1.10 Gitié package wiring diagram (unit AY00-120) SCH5 electronic boards S70+AY10 exhausted gas thermostat IGNTR ignition transformer room temperature probe differential water pressure switch ignition electrodes THPC delivery water temperature probe (appliance internal circuit) flame sensor (appliance internal circuit) differential water pressure switch CNTBOX flame control unit...
Page 16
Features and technical data Figure 1.11 Gitié package wiring diagram - base version Terminal block SCH5 S70+AY10 electronic boards MOD.0 GAHP or ACF unit Package power supply terminal box MOD.1 AY00-120 unit J2-J10 Control jumpers of system water pumps ("closed") SCH1 Controller S61 Figure 1.12 ...
Page 17
Features and technical data Figure 1.13 Gitié package wiring diagram with KIT/2 C1 or with KIT/4 C1 MOD.0 GAHP or ACF unit J2-J10 Control jumpers of system water pumps ("closed") MOD.1 AY00-120 unit Terminal block SCH1 Controller S61 PM0-PM1 System water pumps SCH5 S70+AY10 electronic boards Position of pumps flow rate adjustment screw...
Features and technical data ELECTRONIC BOARDS GAHP-AR Unit electronic boards (S61+AR11) programmed by interacting with the display and the knob. Satellite WAR11 electronic board (Figure 1.16 p. 19 ), in- In the electrical panel on the GAHP-AR unit there are: ▶...
Page 19
Features and technical data Figure 1.16 Eletronic board AR11 T 2A fuse T 2A fuse Satellite board AR11 connector Jumper N.O. contact Display appliance state Reversible valve motor power supply Controller power supply Defrosting valve N.O. contact AY00-120 Unit electronic boards (S70+AY10) and operative codes.
Paragraph 4.4 p. 31 . Data display and parameters setting. ▶ Hourly programming. ▶ Climatic curve control. ▶ Diagnostics. ▶ Errors reset. ▶ Possibility to interface with a BMS. ▶ DDC functionality may be extended with auxiliary Robur devices...
Features and technical data TECHNICAL CHARACTERISTICS 1.7.1 ARAY Integrated package technical specifications Table 1.2 Technical data Gitié ARAY ARAY/4 ARAY/4 ARAY/2 ARAY/2 ARAY/4 C0 ARAY/4 C1 ARAY/2 C0 ARAY/2 C1 C0 S C1 S C0 S C1 S Heating mode medium-temperature Seasonal space heating application (55 °C) energy efficiency class...
Page 22
Features and technical data ARAY/4 ARAY/4 ARAY/2 ARAY/2 ARAY/4 C0 ARAY/4 C1 ARAY/2 C0 ARAY/2 C1 C0 S C1 S C0 S C1 S sound pressure L at 5 metres (max) dB(A) 57,6 (6) 53,0 (6) minimum storage temperature °C maximum water pressure in operation Water content inside the apparatus ±10% depending on power voltage and absorption tolerance of electric motors.
Transport and positioning cycles. Figure 2.1 Instruction for lifting To prevent overflowing and damage provide for a drain- age system. Acoustic issues Pre-emptively assess the appliance's sound effect in connec- ▶ tion to the site, taking into account that building corners, en- closed courtyards, restricted spaces may amplify the acous- tic impact due to the reverberation phenomenon.
Heating engineer Anti vibration mountings Use anti-vibration mountings. ▶ Also provide anti-vibration joints between the appliance Although the appliance's vibrations are minimal, resonance ▶ and water and gas pipes. phenomena might occur in roof or terrace installations. HEATING ENGINEER WARNINGS A (= out) 1 1/4"F - WATER OUTLET AY00-120 (m = AY00-120 ▶...
Heating engineer self-protection system to prevent icing. The anti-icing function with glycol). (activated by default) automatically starts the primary circula- Glycol modifies the physical properties of water (densi- tion pump and, if required, the burner too, when the outside ty, viscosity, specific heat...).
Heating engineer FUEL GAS SUPPLY Chemical conditioning and washing Water treatment/conditioning or system washing car- Gas connection ried out carelessly may result in risks for the appliance, 3/4 "M the system, the environment and health. ▶ on the right, at the bottom, connection plate (Figure 1.5 p. 10 ). ...
Heating engineer 3.10 GAHP-AR UNIT COMBUSTION the left panel of the appliance. 4. Fasten the condensate trap (L) on the T fitting (I). PRODUCTS EXHAUST 5. Fasten the T fitting (I) on the appliance's flue gas exhaust (Ø 80 mm); Compliance with standards 6.
Electrical installer flue, NO check valves must be installed. suitable discharge manifold. The junction between the pipe and the manifold must re- ▶ main visible. To avoid corrosion phenomena, convey the GAHP-AR The connection of the discharge to the sewerage system ▶...
Provide (by the installer) a protected single phase line (230 V 1-N motely control one or more Robur appliances with the DDC con- 50 Hz) with: trol device.
Page 32
Electrical installer Table 4.1 CAN bus cables type CABLE NAME SIGNALS / COLOR MAX LENGTH Note Robur Ordering Code OCVO008 ROBUR NETBUS H= BLACK L= WHITE GND= BROWN 450 m Honeywell SDS 1620 BELDEN 3086A H= BLACK L= WHITE GND= BROWN...
Electrical installer Figure 4.5 Connection diagram of simultaneous hot external enables Figure 4.6 Connection diagram of separate hot external enables R24V unit terminal block unit terminal block Components NOT SUPPLIED Components NOT SUPPLIED Two-pole switch GAHP-AR unit request SELV safety transformer AY00-120 heating request General request Hot/cold diverter (summer/winter) GAHP-AR unit request...
TAC shall not perform first start-up and the appliance tion parameters and may exclusively be carried out by a shall not be commissioned. Robur TAC. NEITHER the user NOR the installation tech- These situations may be: nician is authorised to perform such operations, under Appliance installed inside a room.
First start-up ELECTRONIC ADJUSTMENT ON THE Knob MACHINE - MENUS AND PARAMETERS One of the following actions may be done with the board knob OF THE S61 BOARD AND OF THE AY10 (Detail B in Figure 5.1 p. 35 and in Figure 5.2 p. 35 ): BOARD Enter the menu list (by pressing the first time).
This may be harmful and dangerous for the First startup by TAC appliance and for the system. First start-up may exclusively be carried out by a Robur Checks before switching on TAC (Chapter 5 p. 34 ). Before switching on the appliance, ensue that: Never power the appliance off while it is running ...
Maintenance see Paragraph 1.6 p. 20 ), the appliance is switched on/off relevant manual to modify settings. by the ON/OFF positions of the external control devices. After switching on with the control, in normal operating condi- Do not modify complex settings tions, the appliance starts/stops automatically according to the user's heating/cooling needs, supplying hot or chilled water at Specific technical and system knowledge is required for...
Maintenance Table 7.1 GAHP A GAHP GS/WS AY00-120 GA ACF GAHP-AR Guidelines for the preventive maintenance operations visually check of the general condition √ (1) √ (1) √ (1) of the unit and of its finned coil check the correct op- eration of the device √...
Maintenance Signals in normal operation letter "E" twice, and go back to the normal display of de- tected temperature data. During normal operation, water temperature values alter- ▶ nate on the display: output, input and the difference be- PERIODS OF INACTIVITY tween the two.
Diagnostics DIAGNOSTICS OPERATIVE CODES Table 8.1 Operative codes GAHP-AR Code Description Warning (u) Error (E) Power cycle the appliance. Flame controller reset circuit fault If the code persists, shows up again or in case of doubt, contact the TAC. Limit thermostat trip Contact authorised Technical Assistance Flue gas thermostat trip Contact authorised Technical Assistance...
Page 41
Diagnostics Reset may be performed from the DDC or from the S61 board (menu High flue gas or generator fins Reset is automatic when the triggering condi- 2, parameter 1). temperature tion ceases. If the code persists, shows up again or in case of doubt, contact the TAC.
Page 42
Diagnostics Transformer or 24 Vac fuse fault Contact the TAC. Invalid module type configuration Contact the TAC. parameters ROM board fault Contact the TAC. pRAM board fault Contact the TAC. xRAM board fault Contact the TAC. Registers board fault Contact the TAC. Reset may be performed from the DDC or from the S61 board (menu 2, parameter 1).
Page 43
Diagnostics Incomplete functional parameters Contact the TAC. Reset is automatic when the triggering condi- Invalid bank 1 parameters Contact the TAC. tion ceases. Reset is automatic when the triggering condi- Invalid bank 2 parameters Contact the TAC. tion ceases. Transformer or 24 Vac fuse fault Contact the TAC.
Contact details Robur SPA, Via Parigi 4/6, I-24040 Zingonia (BG) (*) For heat pump space heaters and heat pump combination heaters, the rated heat output Prated is equal to the design load for heating Pdesignh , and the rated heat output of a supplementary heater Psup is equal to the supplementary capacity for heating sup(Tj) .
Page 45
Contact details Robur SPA, Via Parigi 4/6, I-24040 Zingonia (BG) (*) For heat pump space heaters and heat pump combination heaters, the rated heat output Prated is equal to the design load for heating Pdesignh , and the rated heat output of a supplementary heater Psup is equal to the supplementary capacity for heating sup(Tj) .
180 °C ± 7 °C code 60R180H02/04154 J-TLT015 generator contact type (normally closed) or similar* Robur S.p.A. Bypass valve Valve and actuator 25,5 + 0/-2 bar — code H-VLV108 * The manufacturer guarantees the functioning and the safety of the unit only if it is equipped with original spare parts...
Page 47
Appendices 1. move the appliance front panel; Figure 9.5 Safety valve kit - Componenents required for service 2. identify the thermostat, which is found in the lower part of the generator pipe, on the right side above the combustion chamber (see figure 9.4 p. 47 ); 3.
Page 48
Appendices 2. Replace the o-ring as indicated in Figure 9.9 p. 48 . Figure 9.10 Inspection valve - Detail A of fixed part, detail B of remov- 3. Tighten part "B" of the inspection valve to part "A" (see Figure able part 9.10 ...
Page 49
Appendices to be evaporated in the generator and causes the same over-heating phenomenon. In both cases, the over-heating of the generator makes the man- ual-rearm safety thermostat intervene, which is installed on the wall of the generator. As a consequence, if there are no generator thermostat interven- tions, all corrosion phenomena can be excluded and no inspec- tion or additional action is necessary.
Page 52
Robur mission Robur is dedicated to dynamic progression in research, development and promotion of safe, environmentally-friendly, energy-efficiency products, through the commitment and caring of its employees and partners. Robur S.p.A. advanced technologies for climate conditioning via Parigi 4/6 24040 Verdellino/Zingonia (BG) Italy +39 035 888111 - F +39 035 884165 www.robur.it robur@robur.it...