Appendix G
Modbus Communications
40009
Phase Status
NOTE: Since all sensors are normally enabled,
This register will normally be 0000H.
40010
Fan set point
40011
Alarm set point
40012
Trip set point
40013
Fan switching differential (hysteresis)
40014
Alarm switching differential (hysteresis)
40015
Trip Switching differential (hysteresis)
40016
Fan Exerciser interval
40017
Fan Exerciser run time
40018
Time since last Fan Exercise
40019
Firmware Version
40020
Auxiliary Relay 4 set point
40021
Auxiliary Relay 5 set point
40022
Auxiliary Relay 4 switching differential (hysteresis)
40023
Auxiliary Relay 5 switching differential (hysteresis)
48188
Device I.D.
Modbus
Register
Data Sent To Addressed Register
40050
Set Manual Fan Function ON/OFF
40051
Reset Max stored temperature
40052
Reset Unit
40053
Buzzer Control
Courtesy of NationalSwitchgear.com
Bit 4
"1" = Failed Display Driver
Bit 0
"1" = Some other bit is '1'
Bit 1
"1" = Left phase disabled
Bit 2
"1" = Center phase disabled
Bit 3
"1" = Right phase disabled
Bit 4
"1" = Left phase has a Failed Sensor
Bit 5
"1" = Center phase has a Failed Sensor
Bit 6
"1" = Right phase has a Failed Sensor
Bit 7
"1" = Fan Exerciser is disabled
Setpoints and switching differentials are 8-bit data
in the low-order byte.
1 to 720 hours (up to 30 Days)
1 to 120 minutes
1 to 720 hours (up to 30 Days)
Setpoints and switching differentials are 8-bit data
in the low-order byte.
15060D (15060 - 15069 reserved for ITM
0001 turns Fan ON, 0000 sets Fan to AUTO
0001 sets max temp stored to current max temp.
0001 resets the unit.
0001 turns ON Buzzer, 0000 turns Buzzer OFF
32