Control circuit terminals
The control circuit terminal block is common to all equipment.
Terminal
Input /
Function
symbol
output
Multifunction programmable relay contact output.
FLA
Detects the operation of the inverter's protection
FLB
Output
function.
FLC
Contact across FLA-FLC is closed and FLB-FLC is
Note 3)
opened during protection function operation.
Multifunction programmable relay contact output.
RY
Default settings detect and output low-speed signal
RC
Output
output frequencies.
Note 3)
Multifunction output terminals to which two different
functions can be assigned.
Note 3) A chattering (momentary ON/OFF of contact) is generated by external factors of the vibration and
the impact, etc. In particular, please set the filter of 10ms or more, or timer for measures when connecting
it directly with input unit terminal of programmable controller. Please use the OUT terminal as much as
possible when the programmable controller is connected.
Note 4) OVC II: Overvoltage category II
11
Electrical
specifications
Note 4)
Max. switching capacity
250Vac (OVC II) -2A,
30Vdc-2A
(cosφ=1)
: at resistive load
250Vac (OVC II) -1A
(cosφ=0.4)
30Vdc-1A
(L/R=7ms)
Min. permissible load
5Vdc-100mA
24Vdc-5mA