Download Print this page

CBS ArcSafe RRS-3 WL Installation And Operation Manual

For siemens wl breakers with racking rails

Advertisement

Quick Links

RRS-3 WL
Published and distributed by:
CBS ArcSafe®
2616 Sirius Road
Denton, Texas 76208
A division of:
Distance
GroupCBS, Inc.®
P.O. Box 1557
Gainesville, Texas 76241
®
Copyright CBS ArcSafe
2019
Printed in the United States of America
Reproduction, adaptation, or translation without prior written permission is prohibited except as is allowed by law.
is
|
2616 Sirius Road
Denton, TX 76208
Safety
®
|
(877) 4-SAFETY
Rev. 2/19/2019
For Siemens WL Breakers
with Racking Rails
W H A T S T A N D S
B E T W E E N Y O U A N D
A R C - F L A S H D A N G E R ?
|
www.cbsarcsafe.com
WE
DO.

Advertisement

loading

Summary of Contents for CBS ArcSafe RRS-3 WL

  • Page 1 RRS-3 WL For Siemens WL Breakers with Racking Rails Published and distributed by: CBS ArcSafe® 2616 Sirius Road Denton, Texas 76208 A division of: Distance Safety GroupCBS, Inc.® ® W H A T S T A N D S P.O. Box 1557...
  • Page 2 RRS-4 – PLC Based Universal Remote Racking System (Rotary) The CBS ArcSafe® RRS-4 universal remote racking system is an updated PLC based version of the best selling RRS-1. The dual mode, source programmable, PLC based control system offers two different operating modes to choose from based on user preference or the application.
  • Page 3 About the User’s Guide This user’s guide describes the functions and features of the CBS ArcSafe® Single Application Remote Racking System (RRS-3). This technical document is intended to act as a simplified reference for users of the equip- ment; allowing for safe, quick, and efficient use of the RRS-3 features.
  • Page 4: Installation

    Ensure that the equipment to be remotely operated matches the equipment shown and de- scribed on the cover page. If the equipment does not match, please contact CBS ArcSafe® for more information regarding remote operating applications for the equipment in question.
  • Page 5 Ensure that the handle extension is pulled fully out as shown below. 7. Pull upwards on the black locking pin until the slide assembly is released. When released, the slide assembly will gently slide forward on its own. RRS-3 WL Installation and Operation...
  • Page 6 8. Ensure that the breaker’s racking handle fits properly into the racking operator on the RRS-3, as shown. If it does not align, slowly rotate the adapter on the RRS-3 until it aligns properly with the handle. The RRS-3 is now ready for operation. RRS-3 WL Installation and Operation...
  • Page 7: Operation

    REMOVE button on the RSO-IV control panel or remote pendant to rack the breaker out. 7. Press and release the INSTALL button on the RSO-IV control panel or remote pendant to rack the breaker in. RRS-3 WL Installation and Operation...
  • Page 8: Torque Limiter

    Installation section of this manual. 3. To determine the proper torque required to rack the breaker, first rack the breaker out, measuring the maximum amount of torque needed. Record this value. RRS-3 WL Installation and Operation...
  • Page 9 ANGER Inaccurate setting of the torque limiter may result in excessive slip during racking operations or, if over-tightened, the remote rack placing excessive torque on the breaker racking mecha- nism; possibly leading to equipment damage. RRS-3 WL Installation and Operation...
  • Page 10 1. Loosen the four bolts on the side L-brackets as indicated below. 2. Next, move the assembly up or down as required to align the RRS-3 racking adapter with the breaker racking handle. 3. Re-tighten the bolts loosened previously. RRS-3 WL Installation and Operation...
  • Page 11 To adjust horizontal positioning of the slide assembly: 1. Loosen the two bolts on the angle brackets above the slide assembly as shown. 2. Next, move the assembly left or right as required. 3. Re-tighten the bolts loosened previously. RRS-3 WL Installation and Operation...
  • Page 13 Notes RRS-3 WL Installation and Operation...
  • Page 14 RRS-3 WL Installation and Operation...
  • Page 16 RRS-3 WL Installation and Operation 2616 Sirius Road Denton, TX 76208 Tel: 877-4-SAFETY Fax: 940-382-9435 Website: www.CBSArcSafe.com Email: info@CBSArcSafe.com ANGER Ensure that personnel using this equipment are adequately trained in the operation of the switchgear they are planning to work with; that they are correctly stationed outside the arc flash boundary;...