Download Print this page

Sealey SAC00015 Instructions page 3

Compressor (belt drive) 1.5hp oil free

Advertisement

WArNiNG! ensure that you have read, understood and apply section 1 safety instructions.
5.1.
the compressor should be located and operated in a position that allows good air circulation around the unit. locate the compressor
in a convenient position for the work to be undertaken. Ensure that it is standing on a stable and level surface. Ensure the feet/wheels
are in direct contact with the surface.
5.2.
Attach the required air tool to the air outlet.
5.3.
Plug the mains plug into a mains electrical socket, but do not switch the compressor on until the workpiece and air tool are fully prepared.
Switch on the unit by pushing the switch to the On position (SAC00015 - Fig.1.6) or pulling the red On/Off switch upwards (Figs.2.6 &
3.6).
5.4.
On the SAC00615 and SAC02415 models, the output pressure is regulated by the pressure regulator tap (Figs.2.3 & 3.3). Adjust the
pressure regulator tap to the pressure required. the tap can then be locked at the required setting by tightening the locking ring
(Figs.2.2 & 3.2) behind the tap. When the compressor is not being used, set the regulated pressure to zero so as to avoid damaging
the pressure reducer.
Note:
a) On the SAC00615 and SAC02415 models, if the motor does not cut in and out, but runs continuously when using an air appliance,
the capacity of the compressor may be too small for the tool being used.
b) The larger gauge (figs.2.4 & 3.4) indicates the pressure inside the main tank. The smaller gauge (fig.2.5 & 3.5) indicates the
pressure supplied to the air equipment. The pressure switch (figs.2.7 & 3.7) stops the motor when the maximum tank pressure is
reached and restarts it when pressure falls below the minimum threshold - approximately 2 bar (29psi) less than the maximum pressure.
WArNiNG! for this reason do Not tamper with, or adjust, the pre-set switch or safety valve.
c) Should there appear to be any loss of efficiency when using the compressor, ensure first that the air tool is clean and functioning
properly. If the air tool is satisfactory then refer to the Troubleshooting guide, section 7.
5.5.
do not leave the compressor running for any length of time with the air tool attached, but not being used. if there is a pause in the
work, switch the compressor off. these compressors have a duty-cycle of 25%. for each period of use, a rest period of three times
that length should be left before using it again (for example: after 2½ minutes use, a rest period of 7½ minutes should follow). If the
motor overheats, the thermal cut-out will operate and cut the motor out. When the temperature has returned to normal, the motor will
re-start automatically.
5.6.
if the operating note of the compressor changes, there may be a blockage within the tool, or the air hose may be pinched. the
unit should be switched off immediately, and the source of the blockage investigated and eliminated, before re-starting.
When work is complete, switch the compressor off. by pushing the switch to the Off position (SAC00015 - Fig.1.6) or pushing the red
On/Off switch downwards (Figs.2.6 & 3.6). Operate the air tool to clear any pressure left in the air hose. Disconnect the air tool from
the compressor. for models with air tanks, vent any pressure remaining in the tank by manually operating the safety valve (pull on the
metal ring) situated next to the pressure switch assembly. open the drainage tap at the bottom of the tank, to allow any
moisture to be drained from the tank. this prevents corrosion on the inside of the tank. close drainage tap.
5.7.
if it is intended to store the compressor away, allow it to cool before storing it carefully in a safe, dry, dust free, childproof location.
6.
mAiNteNANce
a
before carrying out any maintenance, switch compressor off, unplug it from the mains electricity supply, depressurise the tank
and allow unit to fully cool down.
6.1.
Keep the compressor clean and free of dust. Do not use cleaning agents. Wipe the compressor using a slightly dampened cloth and
blow it over with compressed air.
6.2.
ensure that the ventilation openings are clear. do not allow any extraneous material to enter the unit via any of the ventilation
openings.
6.3.
to prevent corrosion to the tank, drain it on a regular basis by opening the drainage tap at the bottom of the tank, after draining ensure
the drainage tap is fully closed.
7. troUbleshootiNG
7.1.
the troubleshooting guide below is intended to give an indication of the type of fault which may develop with the compressor over a
long period of service. the chart is not intended as a guide on how to repair the fault, it is recommended that the compressor is
returned to an authorised service agent for rectification of serious faults.
fault
reduction in performance. frequent start-up.
low pressure values.
the compressor stops, then restarts
automatically after a few minutes.
Air leakage from the valve of the pressure
switch whilst the compressor is off.
the compressor does not stop and the safety
valve is tripped.
© Jack sealey limited
possible cause
excessive air consumption, leaks from
the couplings and/or pipes.
tripping of the thermal cutout due to
overheating of the motor.
Pressure switch valve, due to wear or dirt
on the seal, does not perform correctly.
irregular functioning of the compressor or
broken pressure switch.
Original Language Version
remedy
Air tool requires higher spec. compressor.
Check / replace the seals of the fitting.
clean the air vents and ensure the work area is
ventilated. do not over-run the compressor's duty
cycle.
unscrew the head of the valve, clean the valve seat
and the rubber disc (replace if worn).
reassemble and tighten carefully.
switch off compressor and contact
Authorised service Agent.
sAC00015, SAC00615, SAC02415 | Issue:3 (I) 04/10/17

Advertisement

loading

This manual is also suitable for:

Sac00615Sac02415