Lqa600 (Current Outputs, 4 Points); Figure 3-95 Lqa600 Appearance; Table 3-46 Lqa600 Specifications - Hitachi S10mini Hardware Manual

Hide thumbs Also See for S10mini:
Table of Contents

Advertisement

3 INDIVIDUAL SPECIFICATIONS

3.35 LQA600 (Current outputs, 4 points)

Table 3-46 LQA600 Specifications

Item
Output range
Number of output channels
Insulation method
Load resistance
Number of D/A conversion bits
Conversion rate
Ambient temperature
25°C
Total accuracy
Ambient temperature
0 to 55°C
MODE 1
Maximum
response time
MODE 2
Internal current dissipation
Dielectric voltage
Connection method
Compatible wire
External
wiring
Tightening torque
Allowable wiring length 200 m or less (shielded twisted-pair cable)
Mass
TRC denotes a remote I/O transfer time.
RC denotes a refresh cycle time set from J.NET.
While a data transfer on remote I/O or J.NET is suspended, the output data is held at its
value in effect just before the suspension of the transfer, regardless of the status of the
OUTPUT HOLD terminal.
Power off the module before setting the MODE switch.
Specification
4 to 20 mA DC
Four channels
Photocoupler insulation (common to four
channels)
600 Ω or less
12 bits (unsigned)
16 mA/4,000 digit
4 mA: 0 digit
±0.04 mA or less
±0.1 mA or less
4 ms + TRC (remote I/O transfer)
4 ms + RC (J.NET transfer)
4 ms + 4TRC (remote I/O transfer)
4 ms + RC (J.NET transfer)
Module REV A: 500 mA or less
Module REV B or later: 530 mA or less
1,500 VAC, 1 minute (between external
terminals in a batch and ground)
18-point terminal block connector (screw: M3)
2
0.3 to 1.25 mm
Approx. 6 to 8 N・m
240 g
CAUTION
LQA600
A.OUTPUT
1
2
MODE
DC4~20mA
B1
A1
B2
A2
B3
A3
B4
A4
B5
A5
B6
A6
B7
A7
B8
A8
B9
A9

Figure 3-95 LQA600 Appearance

3-78
MODE switch
Switches output data transfer areas.
Remote I/O
J.NET
Setting
transfer area
transfer area
Fixed at the
MODE1
Area as set
XW area
Fixed at the
MODE2
Area as set
EW area