Page 1
Oxygen is never to be used to pressure test any refrigerant system. These Safeties ARE Required at Startup to Maintain Hanbell Warranty a) Motor Module Trip (INT69HBY): Open for 1 second Low Oil Level Float Trip: Open for 30-60 seconds Unsafe Suction: Less than 5 psi for 3 seconds Low Differential Pressure: Less than 65 psi for 60 seconds (Oil Psi –...
Page 2
COMPRESSOR INSTALLATION & START-UP GUIDE REVISION M The MCS Commitment is to provide practical solutions for the industries needs and to be both a leader and partner in the effective use of microprocessor controls. Micro Control Systems, Inc. 5580 Enterprise Parkway Fort Myers, Florida 33905 PH:(239) 694-0089 FAX:(239) 694-0031 www.mcscontrols.com...
COMPRESSOR INSTALLATION & START-UP GUIDE REVISION M Chapter - 1. Compressor Crate Unpacking & Inspection 1. Inspect crate and compressor for any shipping damage. 2. The compressor is in an easy open crate, cut straps and lift off crate top from base.
The compressor has no oil and is not charged with oil. When adding or doing a complete change, use only the listed Hanbell approved oils. POE oils readily absorb moisture and cause acid formation in the system. Keep oil exposure to the atmosphere to a minimum.
COMPRESSOR INSTALLATION & START-UP GUIDE REVISION M Chapter - 3. Recommended Liquid Injection Piping 1. Liquid Injection Solenoid Valve and Expansion Valve (Required, Not included with compressor): The liquid injection system may be piped, but it is necessary to consider the required space for adjustment of the expansion valve while testing or running the compressor.
Page 7
COMPRESSOR INSTALLATION & START-UP GUIDE REVISION M Chapter - 4. Electrical Wiring 1. If the compressor application is low voltage, the following items should be considered: 2. Use conduit to insulate and protect the main power cables between the control panel and compressors’ electrical terminal box.
Page 8
COMPRESSOR INSTALLATION & START-UP GUIDE REVISION M Chapter - 5. Wiring Procedures - Y-Delta / Part Winding...
Page 9
COMPRESSOR INSTALLATION & START-UP GUIDE REVISION M Motor Terminals The method to tell the terminals for wiring (V-Phase) 1. Star-Delta Motor - refer to Letter by terminal bolt. 2. PWS Motor - refer to Number by terminal bolt. Old Style Motor Terminals Number to right of Bolt Smaller Compressors...
Page 10
COMPRESSOR INSTALLATION & START-UP GUIDE REVISION M Figure 5-A Motor Wiring...
5.1. Electrical Power Terminals The power terminals of Hanbell compressors are made from ceramic materials and are insulated more than 1000MΩ. Be careful connecting the wiring and follow the list below. ► The ceramic part on the power terminal should not be tighten by hitting otherwise the insulation of the power terminal could be degraded.
COMPRESSOR INSTALLATION & START-UP GUIDE REVISION M Chapter - 6. Across the Line Jumper Bar Installation Photo shows extra nuts installed under jumper bar for clearance of power bolt Insulation Connect line voltage directly on Terminal post...
The module has built in flash codes that are helpful for diagnosing safety faults. In order to protect the compressor, each RC2 series compressor has been built with three PTC temperature sensors inside the motor coil and one at the discharge port neck of the compressor. These sensors are connected to the motor module to monitor coil temperature and discharge temperature.
COMPRESSOR INSTALLATION & START-UP GUIDE REVISION M 7.6. How to Wire INT69HBY Diagnose The following diagram shows the proper wiring connections for the module. The module is connected to L1, L2 and L3 for phase monitoring. Stake on connectors at terminal “A” are connected in series with the discharge PTC and wired back to S1 and S2.
8. The suction and discharge flanges are forged steel that can be welded directly with piping connectors (standard size for copper piping, if connecting to steel piping contact your Hanbell representative) After welding the flanges and pipes, they should be cooled down by ambient air; water quenching is prohibited. Do not use water to cool down the pipes and...
Chapter - 13. Pre-Start-Up Procedure 1. Oil Charging: Only lubricants listed in Hanbell’s Technical Manual are to be used. NO SUBSTITUTES. Make sure the oil level is to the middle of the high side sight glass, which is the terminal box side of the compressor. (For compressors with internal oil separators) 2.
COMPRESSOR INSTALLATION & START-UP GUIDE REVISION M 13.1. Oil Types Note: For other applicable oil types, please consult with MCS / HANBELL first for approval...
Also, on the return line from the oil sump to the compressor you must have an oil filter and oil flow switch. Please follow the piping diagram below. Please ensure there is oil charged in the piping feeding the compressor to avoid a dry start-up. 7.3. HANBELL FLOODED TYPE WITH OIL SEPARATOR...
REVISION M 7.4. HANBELL FLOODED TYPE WITH OIL SEPARATOR & OIL COOLER To obtain high oil filtering efficiency low pressure drop loss and non-interruption with lubricant supply system, the oil separator is built outside the compressor. The installation of lubricant circuit is a very important issue during the whole procedures. So, before starting, please make sure to read all the instructions of this manual carefully and ensure each step is done in accordance with the specifications.
• Recheck oil level. The oil level should be to the middle of the high side sight glass. • Hanbell recommends suction superheat 10°F to 20°F, discharge superheat 30°F and a pressure differential of at least 70 psig.
COMPRESSOR INSTALLATION & START-UP GUIDE REVISION M Chapter - 15. Hanbell with VFD 15.1. Wiring & Controls Set Up • For a new installation, DO NOT CONNECT the L1, L2, and L3 Red, White and Blue wires to the INT69HBY motor module.
COMPRESSOR INSTALLATION & START-UP GUIDE REVISION M 15.3. Solenoids 15.3.1 ��������� tion (Normally Open / Normally Closed) NORMALLY OPEN SOLENOID NORMALLY CLOSED SOLENOID THERE ARE NO NOTCHES ON THE NUT CAN BE IDENTIFIED BY NOTCHES ON NUT...
Page 28
START UNLOAD 1. For new continuous (step less) capacity control system, Hanbell equipped all solenoid valves a Normally Closed. If it is necessary to be equipped with other type solenoid valve, please specify it with MCS / Hanbell before order confirmation.
COMPRESSOR INSTALLATION & START-UP GUIDE REVISION M 15.3.5 Solenoid Alignment IMPORTANT SOLENOID ALIGNMENT IS CRITICAL TO PROPER FUNCTIONING OF COMPRESSOR WHEN INSTALLING SOLENOIDS ON THE WHEN INSTALLING A LOAD CAP, MAKE SURE COMPRESSOR, ENSURE THAT THE HOLES THAT THE CIRCULAR HOLE IN THE GASKET MATCH FOR PROPER OIL FLOW TO OCCUR.
Page 31
COMPRESSOR INSTALLATION & START-UP GUIDE REVISION M ALSO MAKE SURE HOLES LINE UP IF INSTALLING ORIFICE PLATE (FOR COMPRESSORS MANUFACTURED BEFORE APRIL 2013) NOT ALL OIL FLOW HOLES ARE ORIENTED THE SAME WAY. BE SURE TO DOUBLE CHECK THAT THE SOLENOID HOLES LINE UP PROPERLY AS SHOWN BELOW.
Page 32
COMPRESSOR INSTALLATION & START-UP GUIDE REVISION M PROPER INSTALLATION OF A SOLENOID PROPER INSTALLATION OF A SOLENOID WITH ORIFICE PLATE WITHOUT ORIFICE PLATE...
Page 33
COMPRESSOR INSTALLATION & START-UP GUIDE REVISION M ATTENTION ORIFICE PLATES WERE REPLACED BY ORIFICE PLUGS IN COMPRESSORS MANUFACTURED AFTER APRIL 2013...
REVISION M Chapter - 16. Slide Amp Calculation 16.1. Slide Amp Calculation through MCS-Connect MCS Controls with a Hanbell Infinite Control (stepless) compressor, you need to follow these Revision 09-17-2019 steps when commissioning the compressor to ensure correct operation. General Concept Not all compressors will run exactly at the full load amperage rating that the manufacturer provides.
Page 35
COMPRESSOR INSTALLATION & START-UP GUIDE REVISION M Revision 09-17-2019 1. Setting the Lower Limit Now that you have finished calibrating the upper FLA% you may now work on setting the minimum FLA% limit. a. Begin by turning the LOAD relay manually OFF, and UNLOAD relay manually ON.
Compressor Warranty Information and Suggested Guidelines for Preventive Maintenance All HANBELL screw compressors are put through strict quality and performance testing prior to shipping from the factory. Provided that terms of payment are observed, a two-year (24 month) Manufacturer’s Warranty against factory defects is offered from the date of installation or 27 months from date of shipment;...
Page 37
6 months to ensure the condition remains safe. In the case of being unable to do the oil analysis periodically, consult Hanbell oil change schedule because the interval of oil change varies by the oil type and compressor operating condition.
COMPRESSOR INSTALLATION & START-UP GUIDE REVISION M Chapter - 18. Handling POE Oils Please read as improper handling can cause compressor failure and void the compressor warranty. POE oils are more hygroscopic than mineral oils, so exposing POE oils to air will result in their absorbing moisture quicker than mineral oils.
20°C; Please check vibration level of bearings in compressor every 10000hrs. Oil Change; use only Hanbell authorized HBR lubricant and do not mix difference brands of the oil together. Oil remaining in the compressor and system should be totally evacuated prior to changing the oil. It may be necessary to change the compressor oil a second time to ensure that there is no oil mix.
COMPRESSOR INSTALLATION & START-UP GUIDE REVISION M 19.1. Hanbell Warranty Startup Form A fillable form is available on our website, download and fill out: https://mcscontrols.com/Documents/Hanbell/Other/Hanbell%20Warranty%20Startup%20Form.pdf...
Page 41
Description of Changes Update Manual to REV H • Updated Hanbell Liquid Injection Piping M. Schreiber / X. • ATTENTION: Step Control Loading Plate Design In RC2 Series 12/03/12 Beltran • Added Revision Chart • Updated / Added Solenoid Installation & Alignment Pictures...