Figure 13. Customer input power outlet, three-phase
Single-phase power
Each PowerBrick in a PowerMax 2000 system on single-phase power is powered by a separate line cord. Each line cord energizes the
circuit breakers and corresponding PDU outlets, as follows:
Table 27. PowerMax 2000 line cord and jumper configurations, single-phase
PowerBrick
Components
PowerBrick 2
DAE 4
(Upper System)
DAE 3
SPS 2A/2B
PowerBrick 1
DAE 2
(Upper System)
DAE 1
SPS 3A/3B
PowerBrick 2
DAE 4
(Lower System)
DAE 3
SPS 2A/2B
PowerBrick 1
DAE 2
(Lower System)
DAE 1
SPS 3A/3B
40
Power Cabling, Cords and Connectors
Line cord
Jumper location
location
(from/to)
P6
No additional power
jumpers required
P4
J4<>P5
PN: 038-004-186
This jumper must be
installed in the field with
a second system.
P3
No additional power
jumpers required
P1
J1<>P2
PN: 038-004-186
This jumper is pre-
installed at the factory
and should not be
removed.
Circuit breakers
PDU outlets
11-12
31-37
7-10
19-30
5-6
13-18
1-4
1-12