Servicing the Series 6100 & 8000 with the FPC-902 Hand Terminal
After the operator has been mechanically installed, the arms attached to the
door, and 120VAC connected to the power supply, connect the FPC902 Hand
Terminal to the operator control. The following sequence of screens will occur.
The final screen shown below is the base point from which various settings for
the operator are accessed and modified.
AKKU
FLASH
EEPROM
RTC
CAN
FPC902
Version 3.20
Feb 16 2018
14:32: 06
FPC902
Service STG
Service STG Slave
Service sensor
Flash-Programmer
Setup
The screen sequences on the following pages start from this point and document the various
adjustable parameters in the control. When at any of the screens shown below, the above
1
screen can be accessed by pressing the "ESC" key one or more times.
PASS
PASS
PASS
PASS
PASS
>
>
Connect with STG ...
Accept all parameter
from the STG?
Offline
>
Press "OK"
>
>
Press "OK"
Yes
Parameter download
from STG ...
DFA127 V2.60
USA Low Energy
Manual
52 No running parameters
Continue
SERVICE STG
SERVICE STG
Configure System
Configure System
Learning System
Learning System
Parameter
Parameter
Maintenance
Maintenance
Functions
Functions
Operation Mode
Aug2018
Press "OK"
>
>
>
>
>
>
>
>
>
>
>
BG

Advertisement

loading
Need help?

Need help?

Do you have a question about the 6100 Series and is the answer not in the manual?

Questions and answers

Summary of Contents for Record 6100 Series

  • Page 1 Servicing the Series 6100 & 8000 with the FPC-902 Hand Terminal After the operator has been mechanically installed, the arms attached to the door, and 120VAC connected to the power supply, connect the FPC902 Hand Aug2018 Terminal to the operator control. The following sequence of screens will occur. The final screen shown below is the base point from which various settings for the operator are accessed and modified.
  • Page 2 SERVICE STG Typically set to either; USA - for full power operation ANSI156.10 Configure System Configure System > Learning System > Door Type USA Low Energy - for units expected to Door Type Parameter > be opened manually. ANSI156.19 Lock Type Maintenance >...
  • Page 3 NOTE: If this operator is to be set up for low SERVICE STG PARAMETER energy operation, opening and closing speeds Configure System > must be adjusted to conform to the requirements DRIVING CYCLE Learning System > Driving cycle > of ANSI A156.19; full power installations CLOSING SPEED Parameter >...
  • Page 4 SERVICE STG PARAMETER Parameter > TIME DELAY OPEN Maintenance > Driving cycle > 0 thru 20 are in 1 sec. intervals; 21 thru TIME DELAY OPEN Functions > Time delay open > Time delay open 40 are in 2 sec. intervals providing 60 Operation mode >...
  • Page 5 SERVICE STG PARAMETER Configure System > DRIVE Learning System > Driving cycle > BRAKE Parameter > Not applicable unless the operator Time delay open > Opening angle Maintenance > Drive > has been configured with the Obstruction close 20 0 Without Functions >...
  • Page 6 SERVICE STG PARAMETER Parameter > DRIVE DRIVE Maintenance > Driving cycle > TYPES OF ARMS Setting the Arm Type will adjust the Functions > Time delay open > Opening angle Opening angle open and close check points based Operation mode >...
  • Page 7 SERVICE STG SERVICE STG PARAMETER Configure System Configure System > > ENTRANCE SYSTEM Not currently used in the North Learning System Learning System > > DRIVE Measure A Driving cycle > America. Parameter Parameter > > Time delay open > Measure A Maintenance Maintenance...
  • Page 8 SERVICE STG SERVICE STG PARAMETER Configure System Configure System > > MANUAL CONTROL If the Mechanical Panel has been set Learning System Learning System Driving cycle > > > DURING CLOSING to either “8 3 Pos. (OFF-M)” or “10 3 Parameter Parameter Time delay open...
  • Page 9 SERVICE STG SERVICE STG PARAMETER With Manual Control / During Closing enabled Configure System Configure System > > MANUAL CONTROL MANUAL CONTROL (above) - Learning System Learning System > > Driving cycle > SUPP. DUR. CLOS. 0 disabled - provides no latch check Parameter Parameter >...
  • Page 10 3 Pos.(AUTO) is used on units when SERVICE STG SERVICE STG no rocker switch is connected. PARAMETER 4 Pos.(VDAH) not used in the US. Configure System Configure System > > CONTROL PANEL 3 Pos.(OFF-M) is the normal setting. Learning System Learning System >...
  • Page 11 SERVICE STG SERVICE STG PARAMETER Configure System Configure System > > CONTROL PANEL Learning System Learning System > > Driving cycle > DISPLAY PANEL Parameter Parameter > > If a Display Control Panel Mechanical Panel Time delay open > BRIGHTNESS BDE1 Maintenance Maintenance >...
  • Page 12 SERVICE STG SERVICE STG SERVICE STG SERVICE STG PARAMETER Configure System Configure System Configure System Configure System > > > > LOCKING When enabled, a short between Learning System Learning System Learning System Learning System > > > > Time delay open >...
  • Page 13 SERVICE STG SERVICE STG SERVICE STG SERVICE STG PARAMETER Configure System Configure System Configure System Configure System > > > > INPUT / OUTPUT Learning System Learning System Learning System Learning System > > > > Manual control > Parameter Parameter Parameter Parameter...
  • Page 14 SERVICE STG SERVICE STG SERVICE STG SERVICE STG PARAMETER Configure System Configure System Configure System Configure System INPUT / OUTPUT > > > > Manual control > Learning System Learning System Learning System Learning System > > > > FEM 1 Control panel >...
  • Page 15 SERVICE STG Sets the length of time a continuous PARAMETER safety signal (terminals 5, 8, 10 & 12) Configu MISCELLANEOUS will initiate an alarm status (red LED Learning System > Manual control > ALARM DISPLAY blinking on control panel or message Control panel >...
  • Page 16 If a Display Control Panel is SERVICE STG connected to the operator, this MAINTENANCE telephone number will momentarily Configu SETUP MAINTENANCE display when the unit it turned on, Learning System > Reset maintenance > PHONE and if an error display occurs, will Parameter >...
  • Page 17 SERVICE STG An alternate location for setting a custom MAINTENANCE telephone number. If a Display Control Panel Configu PHONE is connected to the operator, this telephone Learning System > Setup maintenance > number will momentarily display when the unit Parameter >...
  • Page 18 SERVICE STG OPERATION MODE Indicates the current operational mode of the door. Learning System Note this screen does not dynamically update in Parameter One-way > response to changes to the control panel. Manual Maintenance > The Status screen, accessible anytime the terminal Functions Automatic >...
  • Page 19 SERVICE STG SERVICE STG Cycle indicates the total number of cycles the DIAGNOSTICS Learning System > operator has performed. Parameter > Protocol > Hours indicates the total number of Maintenance > Cycle XXXX hours the operator has been functional. Functions >...
  • Page 20 AKKU PASS FLASH PASS EEPROM PASS PASS PASS This sequence of screens will access and display the files currently stored on the removable MMC FPC902 card located in the top of the FPC-902 Terminal. Version 2.80 The next page will document the transfer of the Jan 1, 2015 appropriate files into the operator control.
  • Page 21 AKKU PASS FLASH PASS EEPROM PASS PASS PASS FPC902 Version 2.80 Jan 1 2015 10:04:54 FPC902 Service STG > Service STG Slave > Flash-Programmer > Setup > SETUP Not available in North America Renew license > Select language > RENEW LICENSE Lapse counter: 500 ID: 3 076 305 230 KEY:...
  • Page 22 Screens Available when synchronizing two operators Both Simultaneous Pairs and Double Egress SERVICE STG PARAMETER Learnin MS 2-LEAVES Parameter > Driving cycle > FUNCTION EXT. SW Maintenance Time delay open > > Function Ext. Sw This is automatically set by the controls Functions Drive >...
  • Page 23 ALARM CODES AND ERROR MESSAGES Display text Type Comments and possible troubleshooting AKI > 60 sec. active Inside radar longer than 60 sec. active and door remains open. Check tt h h a e t r n a o d m a ro . ving objects are activating AKA >...
  • Page 24 Wiring list Manual unlocking switch Locking device Locking device K KA Cable exit Z ZLP Supplementary printed circuit Supplementary printed circuit board board L LED Light-emitting diode Light-emitting diode Wiring diagram Wiring diagram page 56 Rev. C Manual record 19 STA...

This manual is also suitable for:

8000 series