Part 4 – Operation & Maintenance
assures the supply return is referenced to ground.
3) Battery output connection
Connect '+' of battery output with positive female copper bar of power plant, and '-'
with negative female copper bar or breaker (optional).
If multi battery modules will be connected in parallel, connect '+' of battery output of
each battery module with positive female copper bar of power plant, and '-' with
negative female copper bar of power plant or breaker (optional) separately, see Fig4.3.
Length of cable between battery module and power plant shall be less than 2.0m. To
make sure similar voltage drop of cable for each battery, length of all positive and
negative cables should be the same.
Color for cable between '+' and positive bar is suggested as BLACK, and cable between
'-' and negative or breaker as BLUE.
Fig. 4.3 – Layout of paralleling connection for NPFC Series Batteries
4) Power on for battery module
When installation is accomplished, battery module is in dormant state. Once power on
for the power plant and battery module, battery will go into normal running status, and
discharge/charge can be available.
Parameter settings for lithium battery modules in power plant are shown in Table 4.2.
5) RS232/RS485 connection
If there is only one battery module in operation, communication between battery
module and computer can available through both RS232 and RS485.
If there are more than one battery modules in operation, parallel communication can