Dismounting, Maintenance, And Repair - Pepperl+Fuchs MFT Series Manual

Multifunction terminal
Table of Contents

Advertisement

Multifunction Terminal MFT-***.****(.L)

Dismounting, Maintenance, and Repair

5
Dismounting, Maintenance, and Repair
Danger!
Danger to life from using damaged or repaired devices.
Using a defective or repaired device can compromise its function and its electrical safety.
Do not use a damaged or polluted device.
The device must not be repaired, changed or manipulated.
If there is a defect, always replace the device with an original device from Pepperl+Fuchs.
Danger!
Explosion hazard from contact with potentially explosive atmosphere
When working in hazardous areas, there is an explosion hazard from sparking.
The sparks can ignite the surrounding explosive atmosphere.
Only open the surrounding enclosure in the hazardous area, if the non-
intrinsically safe circuits are protected by a cover with a degree of protection IP30
according to IEC/EN 60529.
Only remove the plug-in module in the hazardous area, if the non-intrinsically safe circuits
are protected by a cover with a degree of protection IP30 according to IEC/EN 60529.
Danger!
Explosion hazard from missing cover
If non-intrinsically safe circuits come into contact with electrically conductive objects, a spark
can occur that can ignite an explosive mixture.
Protect the non-intrinsically safe circuits with a cover that is rated with the degree
of protection IP30 according to IEC/EN 60529.
Use the supplied parts to ensure the required degree of protection.
Place warning marking "Warning – Non-intrinsically safe circuits protected by internal
cover with a degree of protection IP30!" visibly next to base module.
The national requirements apply to maintenance, servicing, and inspection
of associated apparatus.
No maintenance is necessary if the devices are operated properly, observing the mounting
instructions and ambient conditions.