Condition Monitoring Functions; Communication Functions - ABB REF 54 Series Technical Reference Manual, General

Feeder terminal
Hide thumbs Also See for REF 54 Series:
Table of Contents

Advertisement

1MRS750527-MUM
Table 5.1.1.4-1 Control functions available for REF 54_ (Continued)
Function
ANSI device no. IEC symbol
MMIDATA1
MMIDATA1
MMIDATA2
MMIDATA2
MMIDATA3
MMIDATA3
MMIDATA4
MMIDATA4
MMIDATA5
MMIDATA5
5.1.1.5.
Table 5.1.1.5-1 Condition monitoring functions available for REF 54_
Function
ANSI device no. IEC symbol
CMBWEAR1
CB wear1
CMBWEAR2
CB wear2
CMCU3
MCS 3I
CMGAS1
CMGAS1
1)
CMGAS3
CMGAS3
CMSCHED
CMSCHED
CMSPRC1
CMSPRC1
CMTCS1
TCS1
CMTCS2
TCS2
CMTIME1
TIME1
CMTIME2
TIME2
CMTRAV1
CMTRAV1
CMVO3
MCS 3U
5.1.1.6.
Feeder Terminal
Technical Reference Manual, General
Description
MMIDATA1
MIMIC data monitoring point 1
MMIDATA2
MIMIC data monitoring point 2
MMIDATA3
MIMIC data monitoring point 3
MMIDATA4
MIMIC data monitoring point 4
MMIDATA5
MIMIC data monitoring point 5
1) This function is only supported in the feeder terminal revisions of Release 2.0 or later, refer to Section
"Revision identification" on page 105.

Condition monitoring functions

Description
CB wear1
Circuit-breaker electric wear 1
CB wear2
Circuit-breaker electric wear 2
MCS 3I
Supervision function of the energizing current input circuit
GAS1
Gas pressure monitoring
GAS3
Three-pole gas pressure monitoring
SCHED
Scheduled maintenance
SPRC1
Spring charging control 1
TCS1
Trip circuit supervision 1
TCS2
Trip circuit supervision 2
TIME1
Operate time counter 1 for the operate time used (e.g. motors)
TIME2
Operate time counter 2 for the operate time used (e.g. motors)
TRAV1
Breaker travel time 1
MCS 3U
Supervision function of the energizing voltage input circuit
1) This function is only supported in the feeder terminal revisions of Release 2.0 or later, refer to Section
"Revision identification" on page 105.

Communication functions

The REF 54_ feeder terminal provides the IEC_103, Modbus, DNP 3.0, SPA and
LON serial communication protocols.
In a customer-specific feeder terminal configuration, special events can be generated
via an EVENT230 event function.
For more information about communication in the REF 54_ feeder terminal, refer to
Section "Serial communication" on page 67.
REF 54_
25

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ref 541Ref 543Ref 545

Table of Contents