10.

Flashing sequences:

Transient fault:
5s
GREEN
Comments:
 On transient fault, only the green LED flash until timeout after 24h.
 The indicator is ready for new fault within this 24 hour period.
 The red LED's will NOT flash on transient fault.
Permanent fault:
5s
GREEN
RED
70s
Comments:
 The Permanent Fault indication (red LED's) is delayed 70 sec to verify a permanent
fault.
 Both red and green LED's will flash on permanent faults until reset (timer, automatic
on energizing of line or manual by use reset-tool).
Flashing frequency for both red & green LED's are 1/5 Hz the first 12 hours and thereafter
1/10 Hz of the remaining time.
12h
f=1/5 Hz
24h
12h
f=1/5 Hz
LINETROLL 110E /110Eµr User Guide February 2010
f=1/10 Hz
f=1/10 Hz
timer- or automatic reset
up to 24h