Installation and Maintenance
Switched Live connections
Typical Uses: PIR. / Light Switch. / BMS.
N L
L SL L FL L1
SUPPLY
SWITCHED
LIVE
230V ac 50Hz
Remove
control signal
connection
this link
Figure 10.
Connections for Switched Live.
A control signal must be routed from the 230V line via the PIR or
light switch to the SL terminal on the unit and the factory link
between the terminals L / SL must be removed. (See figure
10). When 230V ac. is sensed on these terminals, the control will
be actuated.
NOTE:
If you do not require SL switching you should retain the
factory fitted link between terminals L & SL and set the run
on timer to 0 minutes.
Remote Run and Remote Fail connections
A volt free relay is included to provide status if any fan is running
(Maximum load is 5amp 230V ac.) When a fan is running, A&B
are connected. When a fan has failed, C&D are connected.
BL RD BK Y
RUN
ICP
RR
(A) (B) (C) (D)
Figure 11.
Remote Run & Remote Fail connections
FAN
L
SL
LIVE
P.I.R. sensor
or Light Switch
FAULT
RF
TWINFAN CONTROL
Using a Speed Control with a Quietwin
(SINGLE PHASE TWINFANS ONLY)
When using a Single Phase Twinfan it is possible to connect a
Speed Control to modify the output of the fan when commission-
ing the system. Details of suitable Speed Controls are shown
below.
When using a speed control with a single phase Twinfan, the
factory link between terminals L and FL must be removed.
The output of the Speed control should then be connected to the
FL terminal (See figure 12).
N L
L SL L FL L1 L2 N
SUPPLY
SWITCHED
FAN
FAN UNIT
LIVE
LIVE
230V 1ph
230V 1ph
50Hz
50Hz
Supply
Supply
Remove
factory link
between
L & FL
Figure 12.
Using a speed control
(1 phase only).
Speed Control
selection
Fan Unit Code
Speed Control
QTI, QTE, QTR 1 - 5
QTI, QTE, QTR 6
QTI, QTE, QTR 7 - 8
Internal user selectable function switches
A configuration switch block is provided so that the installer can
enable or disable certain functions. The small switch block is
located just above the 'NET' sockets near the run on timer
adjuster (see figure 13)
Configuration
Switches
Figure 13.
Function switches
N
L
L SL L FL L1 L2 N
ON
FAN UNIT
LIVE
LIVE
1 2 3 4
Switch
Switch
number
position
ON
/
OFF
1 Do not reset this particular switch (retain as set by factory)
2
OFF
3
OFF
4
Do not reset this particular switch (retain as set by factory)
H
BL RD BK Y
N L
RUN
FAULT
L SL L FL L1 L2 N
SUPPLY
SWITCHED
FAN
FAN UNIT
ICP
RR
RF
LIVE
LIVE
Regulated output
from speed control
to FL terminal
L N L2 N L1
ESC1 Speed Control
ESC1-3A
ESC1-6A
ESC1-10A
ON
1 2 3 4
H BL RD BK Y
RUN
FAULT
ICP
RR
RF
Switch
function
Disables audible alarm
Unit will not switch off.
H
BL RD BK
ICP
5