Siemens 3WN6 Operating Instructions Manual page 13

Hand-held unit for overcurrent release, power unit adapter for hand-held unit, power unit 24 v dc for power unit adapter
Hide thumbs Also See for 3WN6:
Table of Contents

Advertisement

Menu structure
status
relay
menu
value I
value I
value I
g
L3
N
value I L3
value I N
value I g
valueIPhSeq
= 1405 A
= 463 A
= 77 A
Measure values are examples
Menu value I
In this menu option, all measured currents are displayed. If
the value is less than 18% of I n , display of the value is
suppressed. The characters o and ¤ will then appear alter-
nately on the display.
value I aktL :
current in the highest-loaded phase
value I maxL :
maximum current which has flowed in
the last 15 minutes
value I minL :
minimum current which has flowed in
the last 15 minutes
value I L1, L2, L3: operating current in phases L1, L2, L3
value I N :
current in neutral conductor
value I g :
earth-fault current
value IPhSeq:
phase direction of rotation L1, L2, L3
indicated by " → " or L3, L2, L1 by " ← "
status
relay
menu
value I
value U
value UL
value UL
value UL
L2
L3
aktL
value ULL3
value ULL2
value UaktL
= 390 V
= 385 V
= 390 V
Measure values are example
Menu value U
(only possible with measurement module and voltage
transformer)
In this menu option, all measured voltages are displayed.
value UL aktL :
highest value of the three voltages
L1-L2, L2-L3, L3-L1
value UL maxL :
maximum voltage measured in the
last 15 minutes
value UL minL :
minimum voltage measured in the last
15 minutes
value UL L1, L2, L3:
value of the voltage L1-L2, L2-L3, L3-L1
misc.
protec
value P
value U
value I
value I
value I
value I
value I
PhSeq
aktL
maxL
minL
value IaktL
value ImaxL
value I minL
= < --
= 1580 A
= 1467 A
= 870 A
misc.
protec.
value P
value f
value UL
value UL
value UL
maxL
minL
L1
valueUmaxL
value UminL
value ULL1
= 400 V
= 420 V
= 370 V
menu
value I
value f
value I
value I
L1
L2
value I L1
value I L2
= 1580 A
= 870 A
Measure values are examples
Menu value f
(only possible with measurement module and voltage
transformer)
In this menu option, all measured frequencies are displayed.
value f aktL :
value f maxL :
value f minL :
value I
value U
value P
Wkh
value PWkh
value Phi
= 5 kWh
Measure values are example
Menu value P
(only possible with measurement module and voltage
transformer)
In this menu option, all measured power values and the
power factor are displayed.
value Phi:
value Pb:
value Ps:
value Pw:
value Pmax:
value PWkh:
relay
status
value U
value f
value f
value f
value f
min
akt
value fmin
value fakt
value fmax
= 49 Hz
= 50 Hz
= 51 Hz
present frequency
maximum frequency measured in the
last 15 minutes
minimum frequency measured in the
last 15 minutes
menu
relay
value f
value P
value P
value P
value P
value P
hi
b
s
w
value Pb
value Ps
value Pc
= +0,83
= 131 kVa
= 650 kVA
= 540 kW
present power factor (mean of the three
phases)
reactive power
apparent power
active power
power demand (15 min.)
energy kWh
misc.
protec.
value P
max
status
misc.
protec.
value P
max
value Pmax
= 20 kW
13