6.
Make sure that cylinder is situated on the scales before recovery takes place.
7.
Start the recovery machine and operate in accordance with manufacturer's instructions.
8.
Do not overfill cylinders. (No more than 80 % volume liquid charge).
9.
Do not exceed the maximum pressure of the cylinder, even temporarily.
10. When the cylinders have been filled correctly and the process completed, make sure that the cylinders and the equip
ment are removed from site promptly and all isolation valves on the equipment are closed off.
11. Recovered refrigerant shall not be charged into another refrigeration system unless it has been cleaned and checked.
15. LABELLING
Equipment shall be labelled stating that it has been de-commissioned and emptied of refrigerant. The label shall be dated
and signed. Ensure that there are labels on the equipment stating the equipment contains flammable refrigerant.
16. RECOVERY
When removing refrigerant from a system, either for servicing or decommissioning, it is recommended good practice
that all refrigerants are removed safely. When transferring refrigerant into cylinders, ensure that only appropriate refrige-
rant recovery cylinders are employed. Ensure that the correct number of cylinders for holding the total system charge is
available. All cylinders to be used are designated for the recovered refrigerant and labelled for that refrigerant (i.e. special
cylinders for the recovery of refrigerant). Cylinders shall be complete with pressure relief valve and associated shut-off
valves in good working order. Empty recovery cylinders are evacuated and, it possible, cooled before recovery occurs. The
recovery equipment shall be in good working order with a set of instructions concerning the equipment that is at hand
and shall be suitable for the recovery of flammable refrigerants. In addition, a set of calibrated weighing scales shall be
available and in good working order. Hoses shall be complete with leak-free disconnect couplings and in good condition.
Before using the recovery machine, check that it is in satisfactory working order, has been properly maintained and that
any associated electrical components are sealed to prevent ignition in the event of a refrigerant release. Consult manufac-
turer if in doubt. The recovered refrigerant shall be returned to the refrigerant supplier in the correct recovery cylinder, and
the relevant Waste Transfer Note arranged. Do not mix refrigerants in recovery units and especially not in cylinders.
If compressors or compressor oils are to be removed, ensure that they have been evacuated to
an acceptable level to make certain that flammable refrigerant does not remain within the lubricant. The evacuation pro-
cess shall be carried out prior to returning the compressor to the suppliers. Only electric heating to the compressor body
shall be employed to accelerate this process. When oil is drained from a system, it shall be carried out safely.
9 (48)
2019-276-V01
Need help?
Do you have a question about the ALT-PAC3200C and is the answer not in the manual?