Carrier 48/50PG Series Controls, Start-Up, Operation, Service And Troubleshooting Instructions page 110

Single package rooftop units
Table of Contents

Advertisement

APPENDIX A — LOCAL DISPLAY AND CCN TABLES (CONT)
ITEM
EXPANSION
AIR.Q
Air Quality Config.
IA.CF
IAQ Analog Input Config
IA.FN
IAQ Analog Fan Config
II.CF
IAQ Switch Input Config
II.FN
IAQ Switch Fan Config
AQ.MN
Econo Min IAQ Position
EC.MN
Econo Minimum Position
OVR.P
IAQ Override Position
OA.CF
OAQ Analog Input Config
OAQ.L
OAQ Lockout Limit
AQD.L
AQ Differential Low
AQD.H
AQ Differential High
DF.ON
Fan On AQ Differential
DF.OF
Fan Off AQ Differential
I.4M
IAQ Sensor Value at 4mA
IAQ Sensor Value at
I.20M
20mA
OAQ Sensor Value at
O.4M
4mA
OAQ Sensor Value at
O.20M
20mA
H.4M
RH Sensor Value at 4mA
H.20M
RH Sensor Value at 20mA
A.FAN
Adaptive Fan
AF.EN
Adaptive Fan Operation
FS.VN
Fan Speed --- Ventilation
Fan Speed --- IAQ Over-
FS.AQ
ride
Fan Speed --- Free Cool
FS.E1
Lo
Fan Speed --- Free Cool
FS.E2
Hi
Fan Speed --- Mech Cool-
FS.CL
ing
FS.HT
Fan Speed --- Heating
FS.RH
Fan Speed --- Reheat2
ALM.O
Alarm Relay Config.
A.SPC
SPT/SPRH Sensor Failure
A.SRT
SAT/RAT Sensor Failure
A.OAT
OAT Thermistor Failure
A.CS
Current Sensor Failure
A.CMP
Compressor Failure
A.CKT
Refrig Circuit Failure
A.SSP
SSP Transducer Failure
A.SCT
SCT Thermistor Failure
A.FAN
Indoor Fan Failure
A.FIL
Dirty Filter
A.TST
Thermostat Failure
A.ECO
Economizer Failure
PID
PID Configurations
EC.P
Economizer PID --- kP
EC.I
Economizer PID --- kI
EC.D
Economizer PID --- kD
EC.DT
Economizer PID --- rate
Economizer PID Dead-
EC.DB
band
Linkage Staging PID ---
LK.P
kP
LK.I
Linkage Staging PID --- kI
Linkage Staging PID ---
LK.D
kD
Linkage Staging PID ---
LK.DT
rate
MODE — CONFIGURATION (cont)
RANGE
UNITS
DEFAULT
0=No IAQ
0: no FIOP
1=DCV
1: FIOP
2=Override
IAQ
3=Ctrl Min
Pos
0=Never
0
1=Occupied
2=Always
0=No IAQ
0
1=DCV N/O
2=DCV N/C
3=Override
N/O
4=Override
N/C
0=Never
0
1=Occupied
2=Always
0 to 100
%
10
0 to 100
%
30
0 to 100
%
100
0=No OAQ
0
1=DCV
2=Lockout
OAQ
0 to 5000
600
0 to 5000
100
0 to 5000
700
0 to 5000
600
0 to 5000
200
0 to 5000
0
0 to 5000
2000
0 to 5000
0
0 to 5000
2000
0 to 50
%
0
60 to 100
%
100
No/Yes
No
0 to 100
%
50
50 to 100
%
50
50 to 100
%
60
90 to 100
%
90
60 to 100
%
100
65 to 100
%
100
65 to 100
%
100
Yes/No
Yes
Yes/No
Yes
Yes/No
Yes
Yes/No
Yes
Yes/No
Yes
Yes/No
Yes
Yes/No
Yes
Yes/No
Yes
Yes/No
Yes
Yes/No
Yes
Yes/No
Yes
Yes/No
Yes
0.00 to 99.90
sec
2.5
0.00 to 99.90
sec
0.12
0.00 to 99.90
sec
1
10.00 to
sec
15
180.00
0 to 25
%
3
0.00 to 99.90
10
0.00 to 99.90
5
0.00 to 99.90
5
10.00 to
secs
30
180.00
110
CCN TABLE/
CCN POINT
SUB--- TABLE
IAQ_CFG
IAQANCFG
IAQANFAN
IAQINCFG
IAQINFAN
IAQMINP
ECONOMIN
IAQOVPOS
OAQANCFG
OAQLOCK
DAQ_LOW
DAQ_HIGH
DAQFNON
DAQFNOFF
IAQ_4MA
IAQ_20MA
OAQ_4MA
OAQ_20MA
RH_4MA
RH_20MA
AFAN_CFG
ADAPTFAN
FSPDVENT
FSPDAQOR
FSPDECO1
FSPDECO2
FSPDCOOL
FSPDHEAT
FSPDREHT
ALM_CFG
ALARM RELAY
ACTIVE FOR:
SPACE_AL
SATRATAL
OAT_AL
CS_AL
COMP_AL
CKT_AL
SSP_AL
SCT_AL
FAN_AL
FILT_AL
TSTAT_AL
ECON_AL
PID_CFG
ECONO_P
ECONO_I
ECONO_D
ECONO_DT
ECONBAND
LINK_P
LINK_I
LINK_D
LINK_DT
PAGE NO.
10
31
10
35
31
31
31
10
34
32
32
28
28
31
12
35
35
35
35
35
35
35
38