IMI NORGREN 34D Series Operation Manual

IMI NORGREN 34D Series Operation Manual

Electronic pressure sensor

Advertisement

Electronic
Pressure Sensor
34D
Operation manual
for versions:
34D-xxxxx-DDx-xx
2 x PNP (1 x IO-Link,
Configurable)

Advertisement

Table of Contents
loading

Summary of Contents for IMI NORGREN 34D Series

  • Page 1 Electronic Pressure Sensor Operation manual for versions: 34D-xxxxx-DDx-xx 2 x PNP (1 x IO-Link, Configurable)
  • Page 2: Table Of Contents

    Electronic Pressure Sensor 34D Operation manual Content 1. Preliminary note 1.1 Symbols used 2. Safety instructions 3. Intended Use 3.1 Applications 4. Function 4.1 Communication, parameter setting, evaluation 4.2 Switching function 4.3 IO-Link 5. Installation 6. Electrical connection 7. Operating and display elements 8.
  • Page 3 Electronic Pressure Sensor 34D Operation manual 9.4.4 Read min-/max values for the system pressure 9.4.5 Reset all parameters to factory setting 9.4.6 Set colour change of the display 9.4.7 Graphical illustration of the colour change of the display 10. Operation 10.1 Read set parameters 10.2 Self-diagnosis / error indications 11.
  • Page 4: Preliminary Note

    Electronic Pressure Sensor 34D Operation manual Preliminary note 1.1 Symbols used ► Instructions > Reaction, result […] Designation of keys, buttons or displays → Cross-reference Important note, Non-compliance can result in malfunction or interference. Information Supplementary note 2. Safety instructions ...
  • Page 5: Intended Use

    Electronic Pressure Sensor 34D Operation manual 3. Intended Use The device monitors the system pressure of machines and installations. 3.1 Applications Type of pressure: relative pressure Order number Measuring range Permissible Bursting pressure overpressure * Pressure sensors with internal thread G¼ 34D-P600…...
  • Page 6: Function

    Electronic Pressure Sensor 34D Operation manual Function  The unit displays the current system pressure.  It generates output signals according to the operating mode and the parameter setting.  It moreover provides the process data via IO-Link.  The unit is laid out for fully bidirectional communication. So, the following options are possible: o Remote display: reading and display of the current system pressure.
  • Page 7: Io-Link

    Electronic Pressure Sensor 34D Operation manual 4.3 IO-Link General Information This unit has an IO-Link communication interface which requires an IO-Link-capable module (IO- Link master) for operation. The IO-Link interface enables direct access to the process and diagnostic data and provides the possibility to set the parameters of the unit during operation.
  • Page 8: Electrical Connection

    Electronic Pressure Sensor 34D Operation manual Electrical connection The unit must be connected by a qualified electrician. The national and international regulations for the installation of electrical equipment must be adhered to. Voltage supply according to EN 50178, SELV, PELV. ►...
  • Page 9: Operating And Display Elements

    Electronic Pressure Sensor 34D Operation manual Operating and display elements 1 to 8: Indicator LEDs LED 1 Switching status OUT1 (lights when output 1 is switched). LED 8 Switching status OUT2 (lights when output 2 is switched). LED 2 - 7 System pressure in the indicated unit of measurement.
  • Page 10: Menu

    Electronic Pressure Sensor 34D Operation manual Menu 8.1 Menu structure: Main menu 7503755000000050 05/2019...
  • Page 11: Explanation Of The Menu

    Electronic Pressure Sensor 34D Operation manual 8.2 Explanation of the menu 8.2.1 Explanation of the menu level 1 SPx/rPx Upper / lower limit value for system pressure at which OUT1 switches with hysteresis setting. SPx/rPx is displayed if the parameter [Hno] or [Hnc] for OUTx was set in the extended functions "EF"...
  • Page 12: Parameter Setting

    Electronic Pressure Sensor 34D Operation manual Parameter setting During parameter setting the unit remains in the operating mode. It continues to monitor with the existing parameters until the parameter setting has been completed. 9.1 Parameter setting in general Select parameter ►...
  • Page 13 Electronic Pressure Sensor 34D Operation manual Each parameter setting requires 3 steps: If [C.Loc] is displayed when an attempt is made to modify a parameter value, an IO-Link communication is active (temporary locking). If [S.Loc] is displayed, the sensor is permanently locked via software. This locking can only be removed using a parameter setting software.
  • Page 14 Electronic Pressure Sensor 34D Operation manual  Locking / unlocking The unit can be locked electronically to prevent unintentional settings. ► Make sure that the unit is in the normal operating mode. ► Press [▲] + [▼] simultaneously for 10 s. >...
  • Page 15: Configure Display (Optional)

    Electronic Pressure Sensor 34D Operation manual 9.2 Configure display (optional) ► Select [Uni] and set the unit of measurement: [bAr], [mbAr], [MPA], [kPA], [PSI], [inHG] The selectable units of measurement depend on the respective unit. ► Select [diS] and set the update rate and orientation of the display: [d1]: update of the measured values every 50 ms.
  • Page 16: Define Switching Limits For The Hysteresis Function

    Electronic Pressure Sensor 34D Operation manual 9.3.2 Define switching limits for the hysteresis function ► [ou1] / [ou2] must be set as [Hno] or [Hnc]. ► Select [SP1] / [SP2] and set the value at which the output is set. ►...
  • Page 17: Read Min-/Max Values For The System Pressure

    Electronic Pressure Sensor 34D Operation manual 9.4.4 Read min-/max values for the system pressure ► Select [HI] or [Lo] and briefly press [●]. [HI] = maximum value, [LO] = minimum value. Delete memory: ► Select [HI] or [LO]. ► Press and hold [▲] or [▼] until [----] is displayed. ► Briefly press [●]. 9.4.5 Reset all parameters to factory setting ►...
  • Page 18: Graphical Illustration Of The Colour Change Of The Display

    Electronic Pressure Sensor 34D Operation manual Display colour change for the parameters Display colour change for the parameters [r1ou] / [r2ou], mode hysteresis [G1ou] / [G2ou], mode hysteresis function function OUT1/ OUT1/ OUT2 OUT2 Measured value > switch point Measured value > switch point OUT1/OUT2;...
  • Page 19 Electronic Pressure Sensor 34D Operation manual Display colour change for the parameters [r-12], Display colour change for the parameters [G- mode hysteresis function 12], mode hysteresis function OUT2 OUT 2 OUT1 OUT 1 Measured value between OUT1 and OUT2; Measured value between OUT1 and OUT2; Display = green Display = red Display colour change for the parameters [r-12],...
  • Page 20 Electronic Pressure Sensor 34D Operation manual Display colour change with parameter [r-cF] Display colour change with parameter [G-cF] independent of OUT1 / OUT2. independent of OUT1 / OUT2 Measured value between cFL and cFH; Display Measured value between cFL and cFH; Display = red = green 7503755000000050 05/2019...
  • Page 21: Operation

    Electronic Pressure Sensor 34D Operation manual Operation After power on, the unit is in the Run mode (= normal operating mode). It carries out its measurement and evaluation functions and provides output signals according to the set parameters. Operating indicators → 7 Operating and display elements. 10.1 Read set parameters ►...
  • Page 22: Technical Data

    Electronic Pressure Sensor 34D Operation manual Technical data 11.1 Setting ranges SP1 / SP2 rP1 / rP2 ΔP 34D-P600… 8700 8680 0,20 59,8 0,20 34D-P400… 5800 5780 0,20 39,8 0,20 34D-P250… 3620 3600 0,20 24,9 159,5 34D-P160… 14,5 2320 2313 7,25 0,05 15,9...
  • Page 23: Factory Setting

    Electronic Pressure Sensor 34D Operation manual Factory setting Factory setting User setting / Comments 25% MEW* 23% MEW* 75% MEW* 73% MEW* 0,06 bAr / mbAr colr * = The indicated percentage of the final value of the measuring range (VMR) of the respective sensor is set.
  • Page 24 Electronic Pressure Sensor 34D Operation manual The data specified above only serve to describe the product. No statements concerning a certain condition or suitability for a certain application can be derived from our information. The given information does not release the user from the obligation of own judgement and verification.