Section: GENERAL INFORMATION

Professional Installer's Responsibility:

Explosion, Fire, and
Asphyxiation Hazard
Professional Service Required.
Please read all instructions before proceeding.
Follow all instructions completely.
This equipment must be installed, adjusted
and started by a qualified service agency that
is licensed and experienced with all applicable
codes and ordinances and responsible for the
installation and commissioning of the equipment.
The installation must comply with all local codes
and ordinances having jurisdiction and the latest
edition of the National Fuel Gas Code ANSI
Z223.1 (NFPA 54) and CAN1-B149.1 in Canada.
Burner must be used within the limits of Table 1 .
Fire Hazard: Overheating
Should over-heating occur:
Shut off the manual gas control to
the appliance.
DO NOT shut off power to the
equipment, allow the blower and pumps
to continue running.
Special Requirements:
When contacting Beckett for service information —
Please have the burner serial number and contractor
start-up form available when calling or writing. You
will find the serial number on the label located on the
left rear of the burner.
Concealed damage – If you
discover damage to the burner
or controls during unpacking, notify the carrier at
once and file the appropriate claim forms. Do not
install a burner or control that has been damaged.
This burner is UL listed for use
in the US or Canada per ANSI/UL
295 & CSA /CGA 3.4. For use with
natural gas or propane.
If any of these instructions are not clear,
Call Beckett at
for assistance.
4
1-800-645-2876

Specifications

Table 1 – Burner Specifications
Input Firing Rate Available*
Firing Mode
Fuel
Required Gas Supply
Pressure (to gas train)
Input Voltage **
Input Current
Gas Train
Life Cycle
Application Type
Burner Control
Flame Detection
Igniter
Motor
Combustion Air Proving
Weight
Mounting Orientation
Dimensions
Acceptable Ambient
Temperature Range
Acceptable Ambient
Humidity
* For altitudes higher than 2,000 feet, derate the burner capacity 4%
for each 1,000 feet above sea level.
** This burner is not approved for use in 50 Hz applications.
FOR OUTDOOR USAGE it is the
responsibility of the OEM
equipment manufacturer to protect the burner
system and components from exposure to water in
the end-use application.
Table 2 – Available Models
Model No.
Input Firing Rate (MBH)
CG10.1
CG10.2
CG10.3
CG10.4
CG10.5
CG10.6
CG10.1S
CG10.2S
CG10.3S
CG10.4S
CG10.5S
CG10.6S
300 - 1200 MBH
On-Off or On/Off with Low Fire Start
Natural gas - 0.64 specific gravity
LP gas - 1.53 specific gravity
6" WC minimum (std)
4.5" WC minimum (special)
120 Vac + 10% / -15%; 60 Hz
5.3 Amp
24V Valves High/Low gas pressure
switch
Gas valves are rated for 100-000
cycles (regarding valve seat leakage).
Indoor, Stationary. See notice below
for outdoor use.
Programmable Pre-purge
Flame Rectification
Electronic - Direct Spark
Thermally Protected - Manual Reset
Differential Pressure Switch
40 lbs.
Up to 90° from upright with motor
shaft horizontal
11.9" x 16.0" x 20.5"
-4°F to +104°F
5% - 95% RH non-condensing
300-378
379-476
477-600
601-756
757-952
953-1,200
300-378
379-476
477-600
601-756
757-952
953-1,200