ProtoNode FPC-N34 and ProtoNode FPC-N35
Startup Guide
For Interfacing Cooper Lighting Solutions Products:
Greengate and iLUMIN
To Building Automation Systems:
BACnet MS/TP, BACnet/IP, Modbus TCP/IP, Modbus RTU
and LonWorks
APPLICABILITY & EFFECTIVITY
Explains ProtoNode FPC-N34 and FPC-N35 hardware and how to install it.
The instructions are effective for the above as of February 2016.
Document Revision: 1.H
Auto Discovery
Template Revision: 53

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the ProtoNode FPC-N34 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Cooper ProtoNode FPC-N34

  • Page 1 To Building Automation Systems: BACnet MS/TP, BACnet/IP, Modbus TCP/IP, Modbus RTU and LonWorks APPLICABILITY & EFFECTIVITY Explains ProtoNode FPC-N34 and FPC-N35 hardware and how to install it. The instructions are effective for the above as of February 2016. Document Revision: 1.H Auto Discovery...
  • Page 2 Thank you for purchasing the ProtoNode for Cooper Lighting Solutions. Please call Cooper Lighting Solutions for Technical support of the ProtoNode product. SMC does not provide direct support. If Cooper Lighting Solutions needs to escalate the concern, they will contact Sierra Monitor Corporation for assistance.
  • Page 3 2. Set the Device COM setting that will be connected to ProtoNode. (Section 2.3.2) 3. Connect ProtoNode FPC-N34’s 3 pin RS-485 port to the Field Protocol cabling (Section 3.2), or connect ProtoNode FPC-N35’s 2 pin LonWorks port to the Field Protocol cabling. (Section 3.3) 4.
  • Page 4 Cooper Lighting Solutions ProtoNode Startup Guide Certifications  BTL MARK – BACNET TESTING LABORATORY The BTL Mark on ProtoNode is a symbol that indicates that a product has passed a series of rigorous tests conducted by an independent laboratory which verifies that the product correctly implements the BACnet features claimed in the listing.
  • Page 5: Table Of Contents

    Configure Device IP Address settings ..................9 Interfacing ProtoNode to Devices ....................10 ProtoNode FPC-N34 and FPC-N35 Showing Connection Ports ..........10 BACnet MS/TP (FPC-N34): Wiring Field Port to RS-485 BMS Network ........11 LonWorks (FPC-N35): Wiring Field Port to LonWorks Network ........... 11 Power-Up ProtoNode........................
  • Page 6 Cooper Lighting Solutions ProtoNode Startup Guide Appendix D. Limited 2 Year Warranty ..................... 60 LIST OF FIGURES Figure 1: ProtoCessor Part Numbers ......................8 Figure 2: Supported Point Count Capacity ....................8 Figure 3: Greengate Point Count per Device ....................8 Figure 4: iLUMIN Point Count per Device .....................
  • Page 7: Introduction

    ProtoNode Gateway ProtoNode is an external, high performance Building Automation multi-protocol gateway that is preconfigured to Auto-Discover any of the Cooper Lighting Solutions’ products (hereafter called “device”) connected to the ProtoNode and automatically configures them for BACnet® MS/TP, BACnet/IP, Modbus TCP/IP or LonWorks®...
  • Page 8: Bacnet/Lonworks Setup For Protocessor Protonode Fpc-N34/Fpc-N35

    Cooper Lighting Solutions ProtoNode Startup Guide BACNET/LONWORKS SETUP FOR PROTOCESSOR PROTONODE FPC- N34/FPC-N35 Record Identification Data Each ProtoNode has a unique part number located on the side or the back of the unit. This number should be recorded, as it may be required for technical support. The numbers are as follows:...
  • Page 9: Configuring Device Ip Communications

    Cooper Lighting Solutions ProtoNode Startup Guide Configuring Device IP Communications 2.3.1 Set Greengate or iLUMIN IP Address Connected to the ProtoNode  The Greengate or iLUMIN device needs to be on the same IP subnet as the ProtoNode and the configuration PC.
  • Page 10: Interfacing Protonode To Devices

    Cooper Lighting Solutions ProtoNode Startup Guide INTERFACING PROTONODE TO DEVICES ProtoNode FPC-N34 and FPC-N35 Showing Connection Ports Figure 5: ProtoNode BACnet FPC-N34 (upper) and ProtoNode FPC-N35 (lower) Page 10 of 60...
  • Page 11: Bacnet Ms/Tp (Fpc-N34): Wiring Field Port To Rs-485 Bms Network

    BACnet MS/TP (FPC-N34): W iring Field Port to RS-485 BMS Network  Connect the BACnet MS/TP RS-485 network wires to the 3-pin RS-485 connector on ProtoNode FPC-N34 as shown below in Figure The RS-485 GND (Pin 3) is not typically connected.
  • Page 12: Power-Up Protonode

    Cooper Lighting Solutions ProtoNode Startup Guide Power-Up ProtoNode Apply power to ProtoNode as show below in Figure 10. Ensure that the power supply used complies with the specifications provided in Appendix C.1.  ProtoNode accepts either 9-30VDC or 12-24 VAC on pins 4 and 5.
  • Page 13: Configure The Protonode Via Web Configurator Gui

    Cooper Lighting Solutions ProtoNode Startup Guide CONFIGURE THE PROTONODE VIA WEB CONFIGURATOR GUI Connect the PC to ProtoNode via the Ethernet Port  Connect a Cat 5 Ethernet cable (Straight through or Cross-Over) between the PC and ProtoNode.  The Default IP Address of ProtoNode is 192.168.1.24, Subnet Mask is 255.255.255.0. If the PC and ProtoNode are on different IP Networks, assign a static IP Address to the PC on the 192.168.1.xxx network.
  • Page 14: Connecting To The Protonode Web Configurator Gui

    Cooper Lighting Solutions ProtoNode Startup Guide Connecting to the ProtoNode Web Configurator GUI  After setting the PC on the same subnet as the ProtoNode (Section 4.1), open a web browser on the PC and enter the IP Address of the ProtoNode; the default address is 192.168.1.24.
  • Page 15: Set Bacnet/Ip And Modbus Tcp/Ip Address Of Protonode To Same Switch/Router Of The Device

    Cooper Lighting Solutions ProtoNode Startup Guide BACnet/IP Modbus TCP/IP Address ProtoNode Same Switch/Router of the Device  From the Web GUI’s landing page, click on “Network Settings” Tab to access the IP Settings menu. (Figure Figure 13: IP Address Settings via Web GUI ...
  • Page 16: 4.3.1 Select Network Protocol

    Cooper Lighting Solutions ProtoNode Startup Guide 4.3.1 Select Network Protocol  Going back to the Discovery and Configuration tab, and press BMS Settings button to view/ Change the Building Management System (BMS) Settings.  Select BACnet/IP, BACnet MS/TP, Modbus TCP/IP, or Modbus RTU protocols.
  • Page 17: Figure 15: Bacnet/Ip Settings Window

    Cooper Lighting Solutions ProtoNode Startup Guide 4.3.1.1 Set Device Instance for each lighting panel attached to the Device The Device Instance can be set independently of the site administrator. As an example:  A Device Instance is a BACnet Node-ID which is obtained by the network administrator.
  • Page 18: Figure 16: Bacnet Ms/Tp Settings Window

    Cooper Lighting Solutions ProtoNode Startup Guide 4.3.1.2 BACnet MS/TP (FPC-N34): Setting the MAC Address BACnet Network  Only 1 MAC address is set for ProtoNode regardless of how many light panels are connected to ProtoNode.  Set the BACnet MS/TP MAC address of the ProtoNode to a value between 1 to 127 (MAC Master Addresses);...
  • Page 19: Figure 17: Modbus Tc/Ip Settings Window

    Cooper Lighting Solutions ProtoNode Startup Guide 4.3.1.3 Modbus TC/IP and Modbus RTU Settings  Modbus TC/IP Figure 17: Modbus TC/IP Settings Window  Modbus RTU Figure 18: Modbus RTU Settings Window Page 19 of 60...
  • Page 20: Configure The Device On The Protonode And Automatically Discover Light Panels Connected To The Device

    Cooper Lighting Solutions ProtoNode Startup Guide 4.3.2 Configure the Device on the ProtoNode and Automatically Discover Light Panels Connected to the Device  Click on the “Start Discovery” button to enter the port, network address, Panel Address and Number of Panels for the Device.
  • Page 21: Figure 21: The Discovery Tree

    Cooper Lighting Solutions ProtoNode Startup Guide  After the discovery process is complete, the discovery tree will immediately come up.  The items being marked as green indicate that they have not been configured for protocol conversion. Figure 21: The Discovery Tree When clicking on gateways or gateways containing light panels a tick box will check or uncheck items for Protocol conversion.
  • Page 22: Figure 23: View Light Panel Parameters

    Cooper Lighting Solutions ProtoNode Startup Guide By clicking on a light panel, parameters for that panel will be shown. Figure 23: View Light Panel Parameters Clicking on a light displays and allows editing of the preconfigured BACnet parameters. Figure 24: View & Edit BACnet Parameters on a Lighting Panel...
  • Page 23: Figure 25: Saving Configurations Bar

    Cooper Lighting Solutions ProtoNode Startup Guide  Once the items for configuration are chosen, click on the “Save Configuration” button. The save configuration progress bar will appear. This process may take several minutes. Figure 25: Saving Configurations Bar  When this process is complete, the items on the tree will change from green to black to show that they have been configured.
  • Page 24: Figure 27: Clear Configuration Window

    Cooper Lighting Solutions ProtoNode Startup Guide  In order to clear a configuration, click on the “Clear Configuration” button. An additional option to clear all other device configurations will appear. Figure 27: Clear Configuration Window  After clicking on the Clear & Restart button the following message will appear.
  • Page 25: Bacnet Ms/Tp And Bacnet/Ip: Setting Node_Offset To Assign Specific Device Instances

    Cooper Lighting Solutions ProtoNode Startup Guide BACNET MS/TP AND BACNET/IP: SETTING NODE_OFFSET TO ASSIGN SPECIFIC DEVICE INSTANCES  After setting your PC to be on the same subnet as the ProtoNode (Section 4), open a web browser on your PC and enter the IP Address of the ProtoNode; the default address is 192.168.1.24.
  • Page 26: Lonworks (Fpc-N35): Commissioning Protonode On A Lonworks Network

    Cooper Lighting Solutions ProtoNode Startup Guide LONWORKS (FPC-N35): COMMISSIONING PROTONODE ON A LONWORKS NETWORK Commissioning may only be performed by the LonWorks administrator. Commissioning ProtoNode FPC-N35 on a LonW orks Network The User will be prompted by the LonWorks Administrator to hit the Service Pin on the ProtoNode FPC-N35 at the correct step of the Commissioning process which is different for each LonWorks Network Management Tool.
  • Page 27: Figure 31: Sample Of Fserver.xif File Being Generated

    Cooper Lighting Solutions ProtoNode Startup Guide  For Windows XP and Windows 7, select: Use the following IP Address  Click twice.  Open a web browser and go to the following address: IP Address of ProtoCessor/fserver.xif  Example: 192.168.1.24/fserver.xif.
  • Page 28: Cas Bacnet Explorer For Validating Protonode In The Field

    Cooper Lighting Solutions ProtoNode Startup Guide CAS BACNET EXPLORER FOR VALIDATING PROTONODE IN THE FIELD ProtoCessor has arranged a complementary 2 week fully functional copy of CAS BACnet Explorer (through Chipkin Automation) that can be used to validate BACnet MS/TP and/or BACnet/IP communications of ProtoNode in the field without having to have the BMS Integrator on site.
  • Page 29: Cas Bacnet Setup

    Cooper Lighting Solutions ProtoNode Startup Guide CAS BACnet Setup These are the instructions to set CAS Explorer up for the first time on BACnet MS/TP and BACnet/IP. 7.2.1 CAS BACnet MS/TP Setup  Using the Serial or USB to RS-485 converter, connect it to your PC and the 3 Pin BACnet MS/TP connector on ProtoNode FPC-N34.
  • Page 30: Appendix A. Troubleshooting

    Cooper Lighting Solutions ProtoNode Startup Guide Appendix A. Troubleshooting Appendix A.1. Lost or Incorrect IP Address  Ensure that FieldServer Toolbox is Loaded on the PC that is currently being used, or download FieldServer-Toolbox.zip on the Sierra Monitor webpage, under Customer Care: Resource Center, Software Downloads: http://www.sierramonitor.com/customer-care/resource-center?filters=software-downloads...
  • Page 31: Appendix A.2. Viewing Diagnostic Information

    Cooper Lighting Solutions ProtoNode Startup Guide Appendix A.2. Viewing Diagnostic information  Type the IP Address of the ProtoNode into your web browser or use the FieldServer Toolbox to connect to the ProtoNode.  Click on Diagnostics and Debugging Button, then click on view, and then on connections.
  • Page 32: Appendix A.3. Check Wiring And Settings

    Cooper Lighting Solutions ProtoNode Startup Guide Appendix A.3. Check Wiring and Settings  No COMS on Greengate or iLUMIN side. Check the following: Check Greengate or iLUMIN IP Address Check Ethernet Switch Check Ethernet LEDs Verify Ethernet Cable  Field COM problems: Visual observations of LEDs on ProtoNode.
  • Page 33 Cooper Lighting Solutions ProtoNode Startup Guide  Step 1: Take a Log Click on the diagnose icon of the desired device. Select full Diagnostic. Page 33 of 60...
  • Page 34 Cooper Lighting Solutions ProtoNode Startup Guide If desired, the default capture period can be changed. Click on Start Diagnostic. Wait for Capture period to finish. Diagnostic Test Complete window will appear.  Step 2: Send Log Once the Diagnostic test is complete, a .zip file will be saved on the PC.
  • Page 35: Appendix A.5. Bacnet: Setting Network_Number For More Than One Protonode On Subnet

    Cooper Lighting Solutions ProtoNode Startup Guide Appendix A.5. BACnet: Setting Network_Number for more than one ProtoNode on Subnet For both BACnet MS/TP and BACnet/IP, if more than one ProtoNode is connected to the same subnet, they must be assigned unique Network_Number values.
  • Page 36: Appendix A.6. Led Diagnostics For Communications Between Protonode And Devices

    Cooper Lighting Solutions ProtoNode Startup Guide Appendix A.6. LED Diagnostics for Communications Between ProtoNode and Devices Please see the diagram below for ProtoNode FPC-N34 and FPC-N35 LED Locations. Diagnostic LEDs Description The SPL LED will light if the ProtoNode is off line.
  • Page 37: Appendix B. Vendor Information - Cooper Lighting Solutions

    Cooper Lighting Solutions ProtoNode Startup Guide Vendor Information – Cooper Lighting Solutions Appendix B. Appendix B.1. 3264640000 Greengate Mappings to BACnet, Modbus and LonWorks BACnet BACnet Modbus Point Name Object Object Lon Name Lon SNVT Register Type Reset 1001 nviXXX_Reset...
  • Page 38 Cooper Lighting Solutions ProtoNode Startup Guide Remote09 nvi/nvoXXX_Remote009 SNVT_switch Remote010 nvi/nvoXXX_Remote010 SNVT_switch Remote011 nvi/nvoXXX_Remote011 SNVT_switch Remote012 nvi/nvoXXX_Remote012 SNVT_switch Remote013 nvi/nvoXXX_Remote013 SNVT_switch Remote014 nvi/nvoXXX_Remote014 SNVT_switch Remote015 nvi/nvoXXX_Remote015 SNVT_switch Remote016 nvi/nvoXXX_Remote016 SNVT_switch Remote017 nvi/nvoXXX_Remote017 SNVT_switch Remote018 nvi/nvoXXX_Remote018 SNVT_switch Remote019 nvi/nvoXXX_Remote019 SNVT_switch Remote020...
  • Page 39 Cooper Lighting Solutions ProtoNode Startup Guide Remote059 nvi/nvoXXX_Remote059 SNVT_switch Remote060 nvi/nvoXXX_Remote060 SNVT_switch Remote061 nvi/nvoXXX_Remote061 SNVT_switch Remote062 nvi/nvoXXX_Remote062 SNVT_switch Remote063 nvi/nvoXXX_Remote063 SNVT_switch Remote064 nvi/nvoXXX_Remote064 SNVT_switch Switch01 10001 nvoXXX_Switch001 SNVT_switch Switch02 10002 nvoXXX_Switch002 SNVT_switch Switch03 10003 nvoXXX_Switch003 SNVT_switch Switch04 10004 nvoXXX_Switch004 SNVT_switch...
  • Page 40: Appendix B.2. 4864643204 Greengate Mappings To Bacnet, Modbus And Lonworks

    Cooper Lighting Solutions ProtoNode Startup Guide Switch044 10044 nvoXXX_Switch044 SNVT_switch Switch045 10045 nvoXXX_Switch045 SNVT_switch Switch046 10046 nvoXXX_Switch046 SNVT_switch Switch047 10047 nvoXXX_Switch047 SNVT_switch Switch048 10048 nvoXXX_Switch048 SNVT_switch Switch049 10049 nvoXXX_Switch049 SNVT_switch Switch050 10050 nvoXXX_Switch050 SNVT_switch Switch051 10051 nvoXXX_Switch051 SNVT_switch Switch052 10052...
  • Page 41 Cooper Lighting Solutions ProtoNode Startup Guide Relay021 nvi/nvoXXX_Relay021 SNVT_switch Relay022 nvi/nvoXXX_Relay022 SNVT_switch Relay023 nvi/nvoXXX_Relay023 SNVT_switch Relay024 nvi/nvoXXX_Relay024 SNVT_switch Relay025 nvi/nvoXXX_Relay025 SNVT_switch Relay026 nvi/nvoXXX_Relay026 SNVT_switch Relay027 nvi/nvoXXX_Relay027 SNVT_switch Relay028 nvi/nvoXXX_Relay028 SNVT_switch Relay029 nvi/nvoXXX_Relay029 SNVT_switch Relay030 nvi/nvoXXX_Relay030 SNVT_switch Relay031 nvi/nvoXXX_Relay031 SNVT_switch Relay032...
  • Page 42 Cooper Lighting Solutions ProtoNode Startup Guide Remote022 nvi/nvoXXX_Remote022 SNVT_switch Remote023 nvi/nvoXXX_Remote023 SNVT_switch Remote024 nvi/nvoXXX_Remote024 SNVT_switch Remote025 nvi/nvoXXX_Remote025 SNVT_switch Remote026 nvi/nvoXXX_Remote026 SNVT_switch Remote027 nvi/nvoXXX_Remote027 SNVT_switch Remote028 nvi/nvoXXX_Remote028 SNVT_switch Remote029 nvi/nvoXXX_Remote029 SNVT_switch Remote030 nvi/nvoXXX_Remote030 SNVT_switch Remote031 nvi/nvoXXX_Remote031 SNVT_switch Remote032 nvi/nvoXXX_Remote032 SNVT_switch Remote033...
  • Page 43 Cooper Lighting Solutions ProtoNode Startup Guide Switch07 10007 nvoXXX_Switch007 SNVT_switch Switch08 10008 nvoXXX_Switch008 SNVT_switch Switch09 10009 nvoXXX_Switch009 SNVT_switch Switch010 10010 nvoXXX_Switch010 SNVT_switch Switch011 10011 nvoXXX_Switch011 SNVT_switch Switch012 10012 nvoXXX_Switch012 SNVT_switch Switch013 10013 nvoXXX_Switch013 SNVT_switch Switch014 10014 nvoXXX_Switch014 SNVT_switch Switch015 10015...
  • Page 44 Cooper Lighting Solutions ProtoNode Startup Guide Switch057 10057 nvoXXX_Switch057 SNVT_switch Switch058 10058 nvoXXX_Switch058 SNVT_switch Switch059 10059 nvoXXX_Switch059 SNVT_switch Switch060 10060 nvoXXX_Switch060 SNVT_switch Switch061 10061 nvoXXX_Switch061 SNVT_switch Switch062 10062 nvoXXX_Switch062 SNVT_switch Switch063 10063 nvoXXX_Switch063 SNVT_switch Switch064 10064 nvoXXX_Switch064 SNVT_switch AI_State01 10101...
  • Page 45: Appendix B.3. 808640000 Greengate Mappings To Bacnet, Modbus And Lonworks

    Cooper Lighting Solutions ProtoNode Startup Guide Appendix B.3. 808640000 Greengate Mappings to BACnet, Modbus and LonWorks BACnet BACnet Modbus Point Name Object Object Lon Name Lon SNVT Register Type Reset 1001 nviXXX_Reset SNVT_switch Relay01 nvi/nvoXXX_Relay001 SNVT_switch Relay02 nvi/nvoXXX_Relay002 SNVT_switch Relay03...
  • Page 46: Appendix B.4. 344640003 Greengate Mappings To Bacnet, Modbus And Lonworks

    Cooper Lighting Solutions ProtoNode Startup Guide Remote035 nvi/nvoXXX_Remote035 SNVT_switch Remote036 nvi/nvoXXX_Remote036 SNVT_switch Remote037 nvi/nvoXXX_Remote037 SNVT_switch Remote038 nvi/nvoXXX_Remote038 SNVT_switch Remote039 nvi/nvoXXX_Remote039 SNVT_switch Remote040 nvi/nvoXXX_Remote040 SNVT_switch Remote041 nvi/nvoXXX_Remote041 SNVT_switch Remote042 nvi/nvoXXX_Remote042 SNVT_switch Remote043 nvi/nvoXXX_Remote043 SNVT_switch Remote044 nvi/nvoXXX_Remote044 SNVT_switch Remote045 nvi/nvoXXX_Remote045 SNVT_switch Remote046...
  • Page 47 Cooper Lighting Solutions ProtoNode Startup Guide Relay03 nvi/nvoXXX_Relay003 SNVT_switch Remote01 nvi/nvoXXX_Remote001 SNVT_switch Remote02 nvi/nvoXXX_Remote002 SNVT_switch Remote03 nvi/nvoXXX_Remote003 SNVT_switch Remote04 nvi/nvoXXX_Remote004 SNVT_switch Remote05 nvi/nvoXXX_Remote005 SNVT_switch Remote06 nvi/nvoXXX_Remote006 SNVT_switch Remote07 nvi/nvoXXX_Remote007 SNVT_switch Remote08 nvi/nvoXXX_Remote008 SNVT_switch Remote09 nvi/nvoXXX_Remote009 SNVT_switch Remote010 nvi/nvoXXX_Remote010 SNVT_switch Remote011...
  • Page 48 Cooper Lighting Solutions ProtoNode Startup Guide Remote049 nvi/nvoXXX_Remote049 SNVT_switch Remote050 nvi/nvoXXX_Remote050 SNVT_switch Remote051 nvi/nvoXXX_Remote051 SNVT_switch Remote052 nvi/nvoXXX_Remote052 SNVT_switch Remote053 nvi/nvoXXX_Remote053 SNVT_switch Remote054 nvi/nvoXXX_Remote054 SNVT_switch Remote055 nvi/nvoXXX_Remote055 SNVT_switch Remote056 nvi/nvoXXX_Remote056 SNVT_switch Remote057 nvi/nvoXXX_Remote057 SNVT_switch Remote058 nvi/nvoXXX_Remote058 SNVT_switch Remote059 nvi/nvoXXX_Remote059 SNVT_switch Remote060...
  • Page 49: Appendix B.5. 1664643204 Greengate Mappings To Bacnet, Modbus And Lonworks

    Cooper Lighting Solutions ProtoNode Startup Guide Switch034 10034 nvoXXX_Switch034 SNVT_switch Switch035 10035 nvoXXX_Switch035 SNVT_switch Switch036 10036 nvoXXX_Switch036 SNVT_switch Switch037 10037 nvoXXX_Switch037 SNVT_switch Switch038 10038 nvoXXX_Switch038 SNVT_switch Switch039 10039 nvoXXX_Switch039 SNVT_switch Switch040 10040 nvoXXX_Switch040 SNVT_switch Switch041 10041 nvoXXX_Switch041 SNVT_switch Switch042 10042...
  • Page 50 Cooper Lighting Solutions ProtoNode Startup Guide Remote010 nvi/nvoXXX_Remote010 SNVT_switch Remote011 nvi/nvoXXX_Remote011 SNVT_switch Remote012 nvi/nvoXXX_Remote012 SNVT_switch Remote013 nvi/nvoXXX_Remote013 SNVT_switch Remote014 nvi/nvoXXX_Remote014 SNVT_switch Remote015 nvi/nvoXXX_Remote015 SNVT_switch Remote016 nvi/nvoXXX_Remote016 SNVT_switch Remote017 nvi/nvoXXX_Remote017 SNVT_switch Remote018 nvi/nvoXXX_Remote018 SNVT_switch Remote019 nvi/nvoXXX_Remote019 SNVT_switch Remote020 nvi/nvoXXX_Remote020 SNVT_switch Remote021...
  • Page 51 Cooper Lighting Solutions ProtoNode Startup Guide Remote060 nvi/nvoXXX_Remote060 SNVT_switch Remote061 nvi/nvoXXX_Remote061 SNVT_switch Remote062 nvi/nvoXXX_Remote062 SNVT_switch Remote063 nvi/nvoXXX_Remote063 SNVT_switch Remote064 nvi/nvoXXX_Remote064 SNVT_switch Switch01 10001 nvoXXX_Switch001 SNVT_switch Switch02 10002 nvoXXX_Switch002 SNVT_switch Switch03 10003 nvoXXX_Switch003 SNVT_switch Switch04 10004 nvoXXX_Switch004 SNVT_switch Switch05 10005 nvoXXX_Switch005...
  • Page 52 Cooper Lighting Solutions ProtoNode Startup Guide Switch045 10045 nvoXXX_Switch045 SNVT_switch Switch046 10046 nvoXXX_Switch046 SNVT_switch Switch047 10047 nvoXXX_Switch047 SNVT_switch Switch048 10048 nvoXXX_Switch048 SNVT_switch Switch049 10049 nvoXXX_Switch049 SNVT_switch Switch050 10050 nvoXXX_Switch050 SNVT_switch Switch051 10051 nvoXXX_Switch051 SNVT_switch Switch052 10052 nvoXXX_Switch052 SNVT_switch Switch053 10053...
  • Page 53: Appendix B.6. 6464643200 Greengate Mappings To Bacnet, Modbus And Lonworks

    Cooper Lighting Solutions ProtoNode Startup Guide AI_State030 10130 nvoXXX_State30 SNVT_switch AI_State031 10131 nvoXXX_State31 SNVT_switch AI_State032 10132 nvoXXX_State32 SNVT_switch AI01 30001 nvoXXX_AI01 SNVT_switch AI02 30002 nvoXXX_AI02 SNVT_switch AI03 30003 nvoXXX_AI03 SNVT_switch AI04 30004 nvoXXX_AI04 SNVT_switch Appendix B.6. 6464643200 Greengate Mappings to BACnet, Modbus and LonWorks...
  • Page 54 Cooper Lighting Solutions ProtoNode Startup Guide Relay034 nvi/nvoXXX_Relay034 SNVT_switch Relay035 nvi/nvoXXX_Relay035 SNVT_switch Relay036 nvi/nvoXXX_Relay036 SNVT_switch Relay037 nvi/nvoXXX_Relay037 SNVT_switch Relay038 nvi/nvoXXX_Relay038 SNVT_switch Relay039 nvi/nvoXXX_Relay039 SNVT_switch Relay040 nvi/nvoXXX_Relay040 SNVT_switch Relay041 nvi/nvoXXX_Relay041 SNVT_switch Relay042 nvi/nvoXXX_Relay042 SNVT_switch Relay043 nvi/nvoXXX_Relay043 SNVT_switch Relay044 nvi/nvoXXX_Relay044 SNVT_switch Relay045...
  • Page 55 Cooper Lighting Solutions ProtoNode Startup Guide Remote019 nvi/nvoXXX_Remote019 SNVT_switch Remote020 nvi/nvoXXX_Remote020 SNVT_switch Remote021 nvi/nvoXXX_Remote021 SNVT_switch Remote022 nvi/nvoXXX_Remote022 SNVT_switch Remote023 nvi/nvoXXX_Remote023 SNVT_switch Remote024 nvi/nvoXXX_Remote024 SNVT_switch Remote025 nvi/nvoXXX_Remote025 SNVT_switch Remote026 nvi/nvoXXX_Remote026 SNVT_switch Remote027 nvi/nvoXXX_Remote027 SNVT_switch Remote028 nvi/nvoXXX_Remote028 SNVT_switch Remote029 nvi/nvoXXX_Remote029 SNVT_switch Remote030...
  • Page 56 Cooper Lighting Solutions ProtoNode Startup Guide Switch04 10004 nvoXXX_Switch004 SNVT_switch Switch05 10005 nvoXXX_Switch005 SNVT_switch Switch06 10006 nvoXXX_Switch006 SNVT_switch Switch07 10007 nvoXXX_Switch007 SNVT_switch Switch08 10008 nvoXXX_Switch008 SNVT_switch Switch09 10009 nvoXXX_Switch009 SNVT_switch Switch010 10010 nvoXXX_Switch010 SNVT_switch Switch011 10011 nvoXXX_Switch011 SNVT_switch Switch012 10012...
  • Page 57 Cooper Lighting Solutions ProtoNode Startup Guide Switch054 10054 nvoXXX_Switch054 SNVT_switch Switch055 10055 nvoXXX_Switch055 SNVT_switch Switch056 10056 nvoXXX_Switch056 SNVT_switch Switch057 10057 nvoXXX_Switch057 SNVT_switch Switch058 10058 nvoXXX_Switch058 SNVT_switch Switch059 10059 nvoXXX_Switch059 SNVT_switch Switch060 10060 nvoXXX_Switch060 SNVT_switch Switch061 10061 nvoXXX_Switch061 SNVT_switch Switch062 10062...
  • Page 58: Appendix B.7. Scene Ilumin Mappings To Bacnet, Modbus And Lonworks

    Cooper Lighting Solutions ProtoNode Startup Guide Appendix B.7. Scene iLUMIN Mappings to BACnet, Modbus and LonWorks BACnet BACnet Modbus Point Name Object Object Lon Name Lon SNVT Register Type scene 40001 nvi/nvoXXXscene SNVT_count_f sceneFT 40002 nvi/nvoXXXsceneFT SNVT_count_f Appendix B.8. Channel iLUMIN Mappings to BACnet, Modbus and LonWorks...
  • Page 59: Appendix C. Reference

    Cooper Lighting Solutions ProtoNode Startup Guide Appendix C. Reference Appendix C.1. Specifications ProtoNode FPC-N34 ProtoNode FPC-N35 One 6-pin Phoenix connector with: One 6-pin Phoenix connector with: RS-485 port (+ / - / gnd) RS-485 port (+ / - / gnd)
  • Page 60: Appendix D. Limited 2 Year Warranty

    Cooper Lighting Solutions ProtoNode Startup Guide Appendix D. Limited 2 Year Warranty Sierra Monitor Corporation warrants its products to be free from defects in workmanship or material under normal use and service for two years after date of shipment. Sierra Monitor Corporation will repair or replace any equipment found to be defective during the warranty period.