Installation; Selection The Best Location - LG MULTI V ARNU07GBHA4 Installation Manual

Ceiling concealed duct - high static
Hide thumbs Also See for MULTI V ARNU07GBHA4:
Table of Contents

Advertisement

Installation

Read completely, then follow step by step.
Selection of the best location
Install the air conditioner in the location that satisfies the following conditions.
• The place shall easily bear a load exceeding four times the indoor unit's weight.
• The place shall be able to inspect the unit as the figure.
• The place where the unit shall be leveled.
• The place shall allow easy water drainage.(Suitable dimension "H" is necessary to get a slope to drain as
figure.)
• The place shall easily connect with the outdoor unit.
• The place where the unit is not affected by an electrical noise.
• The place where air circulation in the room will be good .
• There should not be any heat source or steam near the unit.
In case that the unit is installed near the sea, the installation parts may be corroded
by salt, The installation parts (and the unit) should be taken appropriate anti-corro-
sion measures.
[Inspection Hole Standard]
Number of
Inspection hole
1
2
Hole size should be
more than the size of IDU.
Top view
Inspection hole
(unit: mm)
(600X600)
Control box
600
Front view
Distance between
False ceiling & Actual ceiling
More than 100cm
20cm to 100cm
Less than 20cm
600
Front
H = 20 or more
Remarks
Sufficient space in the ceiling for servicing.
Insufficient space. Difficult for servicing
Minimum height for motor replacement.
Installation
Installation Manual 7