Vav compact controller knx / pl-link

Advertisement

Group Objects Description
1
Fault information
2
Fault state
3
Fault transmission
4
Setpoint
5
Damper position
6
Volume flow relative
7
Volume flow absolute
8
Fault
9
Overridden
10 Override position 1
11 Override position 2
12 Balancing mode
13 Vmin
14 Vmax
15 Vnom
16 Opening direction
17 Diff. pressure
18 Coefficient
19 OEM-Reset
8 / 12
Siemens
Building Technologies
If group object #3 "fault transmission" is set to "on", the following faults can be transmitted if they
occur. In that case, group object #2 value changes to "alarm".
Error
Group obj. #1
Device jammed
03 00 0A 03 0C 05
Backup mode
00 01 01 02 0C 05
entered
Pressure sensor
00 01 0A 01 0C 05
tubes inverted
Pressure sensor
00 01 0A 01 0C 05
malfunction
Operating hours
00 01 0A 04 0C 05
notification
Indicates whether the actuator is in fault state. If yes, read out group object #1.
Enabling/ disabling the fault transmission. Fault transmission is disabled by default; therefore no
faults are transmitted from the actuator over the KNX bus.
Setpoint 0...100% for volume flow or position, depending on the operating mode.
Relative damper position 0...100%. An opening range less than 0...90° can be normalized to
0...100% if adaptive positioning is set to "on".
Volume flow relative to the settings of Vnom, Vmin, and Vmax.
3
3
Volume flow in m
/h or m
/s depending on the selected data type.
Same function as group object #2 (available for compatibility reasons).
Indicates whether the VAV controller is in override control either by a programming tool connected to
the HMI or by objects #10 / #11.
When the object is triggered, the actuator drives to the override position 1 defined by the respective
ETS parameter.
When the object is triggered, the actuator drives to the override position 2 defined by the respective
ETS parameter.
When the object is triggered, the actuator drives to Vmax for air balancing purposes.
Minimum air volume flow relative to Vnom.
Maximum air volume flow relative to Vnom.
Nominal air volume flow (absolute).
Opening direction of the air damper.
Actual value of the differential pressure over the VAV box measuring cross.
VAV box characteristic value to map a nominal differential pressure to the corresponding nominal
volume flow.
Resets all parameters to the value specified by the OEM.
Description
Target position can't be
reached due to blockage.
Actuator is in backup mode
(cf. respective parameter
setting)
Pressure sensor measures
the lower pressure on the
input marked with "+".
Malfunction of internal
communication to dp sensor
(200 ms timeout)
Appears after a cumulated
motor running time of 365
days
Resolution
Remove blockage (visual
inspection required) or
invert Opening direction,
if it is set wrongly
Or switch on adaptive
positioning, if mechanical
limits are intended.
Actuator leaves Backup
mode when receiving a
setpoint.
Correct the tubes
connection
1) Check tubes
connection, or
2) reboot device, or
3) replace device
Check device status and
control loop sensitivity
CE1N3547en_c
2018-10-10