Mounting The Unit - ECR EMI AmericaSeries S1CG Installation, Operation And Maintenance Manual

Single-zone and dual-zone side-discharge ductless split-system condensing units for r410 refrigerant
Table of Contents

Advertisement

Before installing, consider:
Locate the unit as close to the indoor sec-
tion as possible. (see page 11.)
S1CG/S2CG — If the unit is used for low
ambient cooling down to 32°F, S1CG/
S2CG require CCH.
Avoid high traffic areas and prevailing
wind locations.
Surface must be flat and level.
Mount unit above typical snow fall level.
This is particularly important for heat
pump applications (S1HG/S2HG).
NOTICE
Ensure free flow of air through the
unit.
Air must not recirculate from dis-
charge to intake — air is drawn
through the coil and side discharged
through the fan grille.
A minimum 48" clearance is neces-
sary for the condenser discharge.
Rear intake (coil side) clearance is
12" minimum.
Consider how power will be run to
the unit from the power source.
Refrigerant piping should be a direct
line to the indoor unit.
Site preparation
1.
Place the unit on a flat concrete surface
or pad if on the ground. Roof mounting
should use a build up platform to avoid
intake of hot air from the roof.
Comfort where it counts
S1CG/S1HG
Single-Zone,
• Installation, Operation and Maintenance Manual •

Mounting the Unit

2.
In areas of heavy snowfall, condensers
should be set above the maximum antici-
pated snow line (12" is usually adequate
for most locations).
Unit Mounting Instructions
Model S1CG is shown for example in the
following sequence.
The side-discharge unit allows for permanent
mounting through the feet. This is highly
recommended due to the vertical design of
the unit.
1. Figure 1, Page 7:
2. Figure 2, Page 7:
Slide front panel forward to clear side
screws and remove.
3. Figure 3, Page 7:
Insert lag bolts through the holes in the
bottom of the unit and tighten to secure.
4. Figure 4, Page 7:
Insert lag bolts through the holes in the
feet on the back of the unit and tighten
to secure.
5.
Replace the front panel, do not tighten
the side screws at this time.
6
S2CG/S2HG
Bullet 1 — Loosen the screws on left
and right sides of the front panel. (Do
not remove these screws.)
Bullet 2 — Remove the screws on the
front of the panel.
P/N 240007754, Rev. A [051509]