Tubing specifications
The system will support refrigerant runs to
the inside unit as listed in Table 1, Page 11.
The units are furnished with sweat connec-
tions and are equipped with refrigerant valves
and Schrader fittings for charging and taking
pressure readings.
CAUTION
It is recommended that a
installed in the liquid line, at the indoor
unit on models without a factory-in-
stalled filter drier (i.e. 18K and larger).
Table 1
S1CG/S2CG tubing specifica-
tions (see Table 14, Page 11)
Model
Max.
Max.
Length
Lift
"H"
09
50'
20'
(15 m)
(6 m)
12
18
24
100'
35'
(30 m)
(11 m)
30
36
P/N 240007754, Rev. A [051509]
S1CG/S1HG
• Installation, Operation and Maintenance Manual •

Refrigerant Piping

be
filter drier
Max.
Liquid
Suction
Trap
Line
Line
Height
"P"
O.D.
O.D.
1/4"
1/2"
15'
(5 m)
1/4"
1/2"
3/8"
5/8"
3/8"
3/4"
20'
(6 m)
3/8"
3/4"
3/8"
3/4"
S2CG/S2HG
Single-Zone,
P-trap installation
A P-trap is recommended when the
suction riser is equal to or greater than
show in Figure 14, Page 11 and Table 1,
Page 11.
When the condenser is installed above the
evaporator, the P-trap will help the return
of oil back to the compressor.
Figure 14
P-trap placement (see
Page 11 for dimensions H & P)
A P-trap may be fabricated using (2) street
elbows and (2) regular elbow.
A prefabricated trap may be purchased
from a wholesaler or distributor however
the trap should be shallow as with the (3)
elbow configuration.
Each elbow is approximately 2 equivalent
feet.
One P-trap is equal to approximately
12 equivalent feet.
P-traps are not required at the foot of the
hot gas risers due to increased oil flow at
higher temperatures.
11
Dual-Zone
Table 1,