Via dell'Industria 2/4 - z.i. San Giacomo di Veglia
31029 Vittorio Veneto Treviso
Tel. +39 0438 - 500044 / Fax. +39 0438 - 501516
- TOLL FREE NUMBER IN ITALY 800 904474
info@tecnosystemi.com -
www.tecnosystemi.com
WALL-MOUNTED LEM RF ROOM PROBE WITH BATTERIES
IN RADIO FREQUENCY
CODE GAZ100001
proAIR
multi-zone
1. TECHNICAL SPECIFICATIONS
The LEM RFroom probe IS a proair system element which, when installed in a room,
detects the zone temperature and the humidity threshold and sends the values to
the polaris 2X / 3X CONTROL PANEL.
The LEM RF room probe replaces all the system chrono-thermostats, except for the
master chrono-thermostat. The configurations of the probe to the system and the
setting are done directly from the polaris 2X/3X CONTROL PANEL, the master chrono-
thermostat or from the App (if installed).
TECHNICAL SPECIFICATIONS
• Power supply: 2 x 1.5 V AAA BATTERIES (LR03) included
• Battery duration: 18 months
• Data transmission: in rf radio frequency at 868 Mhz
• RF signal range 50 metres max in open field between the probe and polaris 2X/3X control
panel
• Room temperature sensor
• Humidity sensor
• Blue LED indicator which comes on every 60 seconds
• Fastening: on the wall using template, screws and wall plugs included.
2. DIMENSIONS AND COMPONENTS
19
106
19
106
LEM
WITH INSTALLATION
TEMPLATE
CODE CLI00060
3. FASTENING THE LEM PROBE
REV. 00 / 09-06-2020
WALL PLUG
SCREWS
4. CONFIGURING THE LEM RF SENSOR IN A PROAIR SYSTEM
IT is important that a Proair system with one or more LEM RF room probes includes at least one
Discovery 2X RF master chrono-thermostat or a STEALTH 2X cabled chrono-thermostat. A
Proair system CANNOT work with LEM RF room probes only.
5
5
17
17
STATUS LED FOR LEM RF SENSOR
INSTALLATION
WALL-MOUNTED
TEMPLATE
LEM
INSTALLATION TEMPLATE
WALL PLUG
SCREWS
LEM ROOM PROBE
View from above
Front view
CONFIGURATION
AND RESET BUTTON
Rear view
BATTERY SLOT
1.5V TYPE AAA
• Insert the batteries supplied respecting the polarity
CAUTION: Always replace both the old batteries with new ones. The batteries are
considered to be special waste and must be disposed of accordingly. Observe the
regulations in force at the collection points in your area.
CAUTION: Do not use rechargeable or lithium batteries because they do not last
as long. Tecnosystemi recommends using alkaline batteries.
• When switching on the first time (if it has never been associated with a zone before),
check that the blue status LED flashes rapidly (the LEM RF room probe searches for
the control panel ID signal for 2 minutes before switching off).
• Power on the Polaris 3X control panel or, if it is already powered on, allow visibility of
the control panel ID from the menu Configuration - Control panel info. This procedure
must occur within 2 minutes before the status LED stops flashing rapidly. If necessary,
press the button on the back of the LEM RF room probe to start searching for the ID
again.
• When the Polaris 3X starts sending the ID signal, the status LED will stop flashing
rapidly and flash just once. Now, assign the desired zone based on the info in the table.
CONFIGURING THE LEM RF ROOM PROBE
NUMBER OF TIMES
ZONE No.
CONFIRM
TO PRESS
TO ASSIGN
ZONE
THE BUTTON
2
1 press
Press for 5 sec.
3
2 presses
Press for 5 sec.
4
3 presses
Press for 5 sec.
5
4 presses
Press for 5 sec.
6
5 presses
Press for 5 sec.
7
6 presses
Press for 5 sec.
8
7 presses
Press for 5 sec.
9
8 presses
Press for 5 sec.
10
9 presses
Press for 5 sec.
11
10 presses
Press for 5 sec.
12
11 presses
Press for 5 sec.
13
12 presses
Press for 5 sec.
14
13 presses
Press for 5 sec.
15
14 presses
Press for 5 sec.
16
15 presses
Press for 5 sec.
BATTERY SLOT
1.5V TYPE AAA
CHECK
ZONE
2 LED flashes
3 LED flashes
4 LED flashes
5 LED flashes
6 LED flashes
7 LED flashes
8 LED flashes
9 LED flashes
10 LED flashes
11 LED flashes
12 LED flashes
13 LED flashes
14 LED flashes
15 LED flashes
16 LED flashes
Need help?
Do you have a question about the Galaxy Proair GAZ100001 and is the answer not in the manual?