Installation and Operating Instruction for B.E.G. - Occupancy detector PD2-M-DALI/DSI-SM/FC
1. Product information
·
Occupancy detector for daylight-dependent lighting control
·
DALI / DSI interface for controlling digitally dimmable
electronic ballasts as a group
·
Switching between DSI and DALI program by remote
control or DIP switch
·
Extension of the detection area by slave devices is possible
·
Other functions adjustable by remote control (optional)
·
Manual switching and dimming via pushbutton possible
·
Orientation light function
2. Operation
The presence detector controls the light automatically according
to people present (movements) and the ambient brightness.
The integrated light sensor constantly measures the ambient
light and compares it with the set value brightness on the
detector.
If the ambient light is sufficient, lighting will not be switched.
If the ambient light level is below the set value brightness, a
movement activates the lighting in the room.
The detector switches the light off despite of a person being
present if there is enough natural light for 5 min or if no move-
ment is detected for one follow-up time.
3. Safety information
Work on the 110-240 V mains supply may only
be carried out by qualified professionals or by
!
instructed persons under the direction and super-
vision of qualified skilled electrical personnel in
accordance with electrotechnical regulations.
Disconnect supply before installing!
This device is not suitable for disconnection.
Mounting the cover ring after introduction of the
power cable (FC version).
4. Mounting
In master/slave mode, the master device must al-
!
ways be installed at the location with least daylight.
The light sensor must be positioned facing away from
!
the window.
4a. Mounting SM
The detector has to be mounted on
a plane and solid surface. Before
mounting, cover ring has to be
removed. To do so, twist the cover
ring anticlockwise through approx. 5°
and lift off.
open
close
Having connected up the cables in
accordance with regulations, put
on the cover ring by turning in a
Figure 1
clockwise direction (see fig. 1). Apply
mains voltage.
4b. Mounting FC
68 mm
A circular opening of diameter
68 mm
68 mm must be produced in the
ceiling. Having connected up the
cables in accordance with regula-
tions, the detector is inserted into
the opening and fixed into position
with the assistance of the spring
clips (see figure 2).
Figure 2
®
PD2-M-DALI/DSI
5a. Position DIP switches, LEDs and
Potentiometers SM
Light
measurement
C
B
A
2
PD2 Surface
mounting
5b. Position DIP switches, LEDs and Poten-
tiometer FC
I
II III
A
B
C
Light
measurement
PD2
False ceiling
mounting
DIP switch functions
DIP 1
Full automatic mode
(VA)
DIP 2
LED ON
DIP 3
Operation mode DALI
Potentiometer A Brightness set value (constant light control)
Potentiometer B Follow-up time light
Potentiometer C Follow-up time (orientation light)
LED I
green
LED II
red
LED III white
6. Self test cycle/Startup behavior
The product enters an initial 60-second self-test cycle, when the
supply is first connected. During this time the device does not
TIME
respond to movement and stays on.
18 16
10
6
22
3
25
1
30
7. Putting into operation/Settings
TE
Brightness set value for constant light control
(Potentiometer A)
LUX
2000
The brightness set value can be defined between
1200
600
10 and 2000 Lux. The potentiometer enables a free
200
TIME
selection of the brightness value.
40
18 16
10
6
22
Symbol :
Night-time operation
3
25
1
Symbol
: Daytime operation
30
TE
(light evaluation inactive)
20%
50 30
10
5
60
Follow-up time "Light" (Potentiometer B)
The follow-up time can be set to 1 to 30 minutes.
TIME
LUX
2000
Symbol TE: test mode
1200
18 16
10
600
6
22
Irrespective of the brightness, every movement
200
3
25
1
40
30
switches the light on for 1sec., then off again for
TE
2 sec.
9s
2s
LED ON
20%
Follow-up time orientation light (Potentiometer C)
LED OFF
Manually switching the orientation light on/off.
50 30
10
LUX
5
2000
60
"ON" for permanent orientation light OFF" for
1200
600
switching off the orientation light
200
40
8. Wiring diagram
Schematic diagram - when connecting the detector, please res-
pect the labelling of the terminal connections at the detector!
DIP
II
1
Standard mode with Master/Slave device(s)
I
III
L
N
T1
3
Connected Slave devices must have the same phase as the
!
Master device.
DIP
9. Manual switching and dimming (see section 23)
By pressing the push button, the phase can be given to the S
terminal.
To turn on or off the light, press the push button briefly. The light
will remain on or off, as long as people are detected plus the
follow-up time.
With a long press of the push button the light will be dimmed
manually. When releasing the button, the current brightness
value is retained.
3
1
2
With renewed long press of the push button, the dimming
direction is reversed.
10. Range
Semi-automatic mode
(HA)
LED OFF
Operation mode DSI
·
·
1
·
2 28m�
11. Exclude sources of interference
3 13m�
SM
FC
If the detection zone is too large, or areas are covered that should not
be monitored, use the blinds to reduce or limit those areas.
L
N
E1
DALI /DSI
DA
DA
S
N
L
+
-
R
R
DA1
Master device
Slave device
2
3
1
Walking across
79m�
Walking towards
Smaller movements / Seated
EN
DE
N
L

Advertisement

loading

Summary of Contents for B.E.G. LUXOMAT PD2-M-DALI

  • Page 1 LUXOMAT ® PD2-M-DALI/DSI Installation and Operating Instruction for B.E.G. - Occupancy detector PD2-M-DALI/DSI-SM/FC 1. Product information 5a. Position DIP switches, LEDs and 8. Wiring diagram · Potentiometers SM Occupancy detector for daylight-dependent lighting control · Schematic diagram - when connecting the detector, please res-...
  • Page 2 1. electromagnetic compatibility (2014/30/EU) 2. low voltage (2014/35/EU) 3. restriction of the use of certain hazardous substances in electrical and electronic equipment (2011/65/EU) 13. Article / Part nr. / Accessory Type PD2-M-DALI/DSI 92280 92258 LUXOMAT Remote control: ® IR-PD-DALI-E (incl. wall bracket) -...
  • Page 3 15. Settings with remote control (optional) 21. 100 h function (see also section 24) (> 3 sec.) long press when closed Red LED flashes t < 5 s Settings with remote control override the potentiome- ter and DIP settings. Before the lamp can be dimmed, the dimming function has to be suppressed for a certain time in order to burn in the The DIP settings are reactivated by lamps.