Occupancy detector

Advertisement

15. Settings with remote control (optional)
(see also section 24)
Settings with remote control override the potentiome-
!
ter and DIP settings.
The DIP settings are reactivated by
• setting the potentiometers to "TEST" and "SUN"
(see section 24), or
• pressing the RESET button on the remote control in open state
Infrared remote control LUXOMAT
IR-PD-DALI-E
®
1. Check Battery:
Open battery compartment by pressing
the plastic springs together and remo-
ving the battery-holder.
2. Note
Using the remote control, the occupancy detector can only be
operated brightness-depending. The setting "SUN" can only be
chosen with potentiometer A.
When using the remote control IR-PD-DALI-E, we recommand to
set potentiometer A to "SUN". Pressing the RESET button on the
remote control then resets the detector to brightness-independ-
ant mode (SUN).
IR-PD-DALI-E
Wall bracket for
remote control IR-PD-DALI-E
16. Settings by remote control when open
Resetting
DSI/
DALI
when open:
Deletes all
values set with
the remote
control, light
or
OFF.
+
or
max
1
to
min
min
max
ON
ON
OFF
OFF
1
to
min
min
50
1500
Lux
Lux
max
ON
OFF
17. Light regulation
The detector has two different integrated light control
algorithms. The set value for the first algorithm is adjusted by
potentiometer (LUX) on the device. Very small light amounts,
max
which shine directly to the detector, have as result that the set
value brightness is exceeded.
The second algorithm has an integrated daylight compensation.
ON
Therefore, it is necessary that the detector analyses the swit-
ched light quantity. This algorithm can only be used by remote
OFF
control. The programming of the set value and the measurement
of the light quantity is carried out in two steps:
In the open state
• The set value is adjusted without daylight (please darken
the room) by using the remote control.
• Measuring the light quantity will be initiated by a long press
(> 3 sec.) of the test button. The detector turns the light on
for 5 min. at 100 %. Then the light will turn on and off for a
short time and stays on after that. This measuring process
is shown by a flashing green LED (10 sec. off/ 1sec. on). This
measuring process is required for each change of the set
value. If the setting "permant orientation light" is chosen,
the function only will be active after the measuring process
is done.
max
If the measuring process is not performed, the detector
performs it automatically when the ambient light is less than
ON
50 Lux for 1 h.
18. Full / Semi-automatic mode
OFF
Full automatic operation
In this operating mode, the lighting switches automatically on and
off for increased comfort, depending on presence and brightness.
Semi-automatic operation
In this operating mode, the light turns on only after a manual
Unlock device –
switching, for an increased savings success (see section 22).
Activation of the
Switching off is automatically or manually (see section 22).
programming mode
The semi-automatic mode basically behaves like the full automatic
mode. The only difference is that the switching on has to be done
Switching between
by hand.
DSI and DALI
In case motion is detected within the 10 sec. after elapse of the
program.
follow-up time, the detector switches the light on again and the
The Factory setting
follow-up time starts again. If there is no motion detected within
is DALI.
the 10 sec. after elapse of the follow-up time, the light has to be
turned on manually.
Dimming of the
lighting to the
desired bright-
ness value
19. Settings during the Self-test cycle
Automatic reading
In the first 60 seconds after connecting the AC voltage, the
in the current light
following functions can be set:
value as new lumi-
nance set value
INI-OFF/O
Stepwise adjusting the
Turn off or turn on the light during the self-test cycle of
set value brightness
60 sec. The last state is active. Factory setting is that the
from 50 to 1500 Lux:
light is on during initialisation.
+/–
step
When INI OFF is chosen, the detector does not switch on
5 Lux
+/–
step
the light after voltage supply. Even upon detected mo-
10 Lux
+
/
step
vement the light is switched on only after
20 Lux
50
1500
Lux
Lux
Startup behavior
50
The set value can be reached in two ways after switching
1500
Lux
Lux
Follow-up time
on. The detector switches the lights on at 10 % and then
30
light
adjusts upwards (min button) or it switches the light on at
100 % and regulates down (max button). This is confirmed
by a short flashing of the red and white LED as well as the
Orientation light
lighting. Factory setting is that the detector switches the
on/off
light on at 100 %.
Follow-up time
Reset of electronic ballasts (manually or automatically)
60
orientation light
If required the connected EB can be reset and preset
parameter can be deleted. Press the button "Reset"
briefly in self-test cycle.
Preset/User-mode
The use of some electronic ballasts may require to send
(see section 23)
a reset command automatically after each start of the
detector (auto reset). In order to activate (red LED) oder
Full automatic-/semi-
deactivate (green LED) the function press the „reset"
automatic mode (see 18)
button in open state for 3 seconds.
Start light measurement
by long press of the
button (see section 17)
20. Test mode/Reset
Test mode
Use "Test" button for activating the test mode and the
Exit programming
"Reset" button to deactivate it.
mode
Reset in closed state
If there is no entry
The lighting is switched off, and the follow-up times are
for about 3 min.
reset.
the programming
mode is ended
Reset in open state
automatically.
Pressing the button for >3 sec. deletes all settings
(except of INI ON/OFF) and the detector is reset to
factory state.
Red LED flashes
t < 5 s
Double lock
50
1500
Lux
Lux
50
1500
Lux
Lux
max
ON
OFF
N mode:
.
60 sec
:
ON
21. 100 h function
(
(> 3 sec.)
)
long press
when closed
OFF
Before the lamp can be dimmed, the dimming function has
!
to be suppressed for a certain time in order to burn in the
lamps.
T5 fluorescent lamps: 80 h
T8 fluorescent lamps: 100 h
For activating the function, press button "Light ON/OFF" in closed
state. During this time, the detector only switches the light ON or
OFF. A dimming to the set value does not take place. After having
activated the function, the red and green LED flash alternately. By
pressing the button "Light ON/OFF" again, it is possible to deacti-
vate the function before the time has elapsed.
50
1500
Lux
Lux
Failure to comply to the burn-in would lead to reducing the life
of the lamp. A further disadvantage could be unwanted random
max
variations in light intensity.
ON
22. Manual Switching
(
short press when closed
)
OFF
You can switch the lighting on and off manually by pressing the
pushbutton or the remote control button "Light ON/OFF" for a
short time. It will stay on or off as long as people are detected
plus the configured follow up time.
23. Manual Dimming - Preset / User
(long press when closed)
You can dim manually by pressing the external push button or
the remote control buttons "min/max" – for a long time
(> 2 sec.). When the button is released, the current dimming
value is retained. Upon renewed dimming, the dimming direction
is reversed.
Two different operating modes are selected
in the opened state.
Changing the mode is done by pressing the "double lock" button.
Each time the button is pressed, the current operating mode is
indicated:
Red shines for 3 sec. = Preset
50
1500
Lux
Lux
Green shines for 3 sec. = User
PRESET – the set value brightness is set during start-up operation
by the installer and remains unchanged. The set value brightness
configured through manual dimming is only applied for the time
being.
The constant light regulation is now deactivated! The current set
artificial light is retained independent of the ambient/daylight
brightness! After switching off and then back on, the original
set set value brightness is reset = constant light regulation is
activated.
USER can only be activated via the remote control
The set value brightness is changed upon each manual dimming
and re-adjusted by the user. The constant light regulation
remains activated!
24. Reset the detector
If the double lock is activated, the detector can be opened again as
follows:
Disconnect operating voltage
Connect operating voltage for 31sec. to 59 sec.
Disconnect operating voltage again
Connect operating voltage again and wait for the self testing
Open detector
With this procedure, the remote control programmed values are not
deleted (before activation of the double lock).
If the setting is not changed by remote control after deactivation
of the double lock, the detector changes in the double locked mode
again after a period of 30 minutes. This way the detector cannot be
unlocked during an accidental power failure.
Alternatively, the detector can be reset in this way:
Set potentiometer A to "Sun" and potentiometer B to "Test". The de-
tector now is in test mode and the potentiometer settings are active.
All operating LEDs are flashing for three seconds.
Except of the INI ON/OFF setting, the detector is reset to factory
setting or the setting of the potentionmeter.
Pushing the "RESET" button on the remote control, in opened mode,
will delete all of the values which were set by the remote control
(beside of INI ON/OFF) and set the detector back to
its factory settings.
Factory settings
The detector is delivered with the following factory
settings: Brightness set value: 500 Lux, follow-up time:
10 minutes. Auto reset: off. Starting the detector in the factory
program the self-test cycle starts with a constant flashing of the
three operating LEDs.

Advertisement

loading

This manual is also suitable for:

Pd2-m-dsiPd2-m-dali-smPd2-m-dali-fcPd2-m-dsi-smPd2-m-dsi-fc