Infra-red flicker detector IRD 1020.1
Flame detection device for
oil and gas flames
INTRODUCTION
The IRD 1020.1 detector is used to supervise gas or oil
flames. This flame monitoring device should be connected
to a Satronic oil burner control box. Monitoring is based on
the infra-red flicker principle, in other words, the flickering
infra-red light of the flame is detected. The steady radiation
from, for example, the glowing refractory layer on the inside
of the boiler, has no effect on the detector. The IRD 1020.1
replaces the IRD 1020 and 920.
When exchanging the IRD 1020, care must be taken that the
corresponding IRD 1020.1 with the same imprint (blue or
white) is used (see page 3 and 4).
When exchanging the IRD 920, care must be taken to wire
the sensor correctly (see page 3), and the existing holder
must be exchanged with the magnetic holder M93.
For replacement of the IRD 920 with IRD 1020.1 is the
sensor cable also needed.
The infra-red flicker detector can be used with any one of the
following control boxes:
IRD 1020.1
DKG 972
DLG 974, 976
DMG 970, 971, 972, 973
TFI 812.2
MMI 810, 811, 812, 815, 816, 962
TMG 740-2, 740-3
SGU 930, 930i
IRD 1020.1 D DVI 980, 982
MMG 810, 811
FFW 930
DKG 972
DLG 974, 976
DMG 970, 971, 972, 973
TFI 812.2
MMI 810, 811, 812, 815, 816, 962
TMG 740-2, 740-3
SGU 930, 930i
CONSTRUCTIONAL FEATURES
The infra-red sensor and the pre-amplifier are hermetically
sealed in glass and along with the electronics form an
integrated unit in the flame detector. Wiring is by way of a
plug connection. The sensitivity control and two LED's for
indication of the flame signal are situated on the rear of the
flicker detector.
TECHNICAL DATA
Supply voltage
or
Nominal current input
Power consumption
Ambient temperature
Insulation standard
Mounting attitude
Weight
Flame viewing attitude
Spectral response
(with daylight filter)
Frequency range
Sensitivity adjustment range
Switch-on delay
(after connecting
operating voltage)
Response time
Cut-out time
Approved ambient parameter
- for operation
- for storage
Build-up of ice, penetration of
water and condensing water are inadmissible
Approvals according
to European standards
1
220 / 240 V (-15... +10%)
50 Hz (50 - 60 Hz)
110/120 V (-15... +10%)
50 - 60 Hz (±5%)
approx. 4 mA
1 VA
-20° C to +60° C
IP 41
any
40 g
side-on or end-on according
to type
800 - 1100 nm
maximum 950 nm
15 Hz.... 250 Hz (-12 dB)
approx. 1 : 20 (26 dB)
< 3.5 sec.
< 0.1 sec.
< 1 sec.
max. 95% at 30° C
-20° C... +60° C
-20° C... +80° C
EN 298, as well as all other
relevant Directives and
standards

Advertisement

loading

Summary of Contents for Honeywell IRD 1020.1

  • Page 1 220 / 240 V (-15... +10%) from, for example, the glowing refractory layer on the inside 50 Hz (50 - 60 Hz) of the boiler, has no effect on the detector. The IRD 1020.1 110/120 V (-15... +10%) 50 - 60 Hz (±5%) replaces the IRD 1020 and 920.
  • Page 2 -20° to +60° C. to the detector unit or burner system. - The flickering detector IRD 1020.1 becomes active not 2. Adjust to maximum sensitivity and start the burner: If the before a minimum threshold-level of steady light is LED indicator is lit after the start impulse, carefully adjust exceeded.
  • Page 3 IRD flange M93 defective (cracks or other mechanical defects) g) wrong IRD flange, special magnetic IRD flange M93 is needed. CONNECTION OF IRD 1020.1 TO SATRONIC BURNER CONTROL BOXES Control box type TFI 812 DKG 97. DMG 97. DLG 97.
  • Page 4 230V 1653104 optional Flicker detector IRD 1020.1 end-on viewing blue 230V 16532 Flicker detector IRD 1020.1 D end-on viewing blue 230V 16552 Flicker detector IRD 1020.1 end-on viewing white 230V 1653204 Flicker detector IRD 1020.1 end-on viewing blue 115V 16572 Flicker detector IRD 1020.1 side-on left blue...