Flush-Mount PIR Switching Sensor (SF-PIR-SW-01)
The SF-PIR-SW-01 is a PIR-triggered switch suitable for mounting into a ceiling void. It allows simple selection of presence or
absence detection to control both lighting and nonlighting loads.
Configurable for any room occupancy style, it switches on the connected load if the area is occupied and the illuminance is
lower than the specified level (with the photocell activated). Similarly, it switches off the load if the area is unoccupied for the
set time.
In absence mode, the unit can also be operated from a mains-rated retractive wall switch.
Features
Operation
Presence Mode (Default Mode)
Out of the box, the time-out adjuster is set to 10 s, and the illuminance threshold adjuster is set to maximum (photocell
inactive). With the illuminance threshold adjuster set to maximum, the sensor will always switch on the connected load
when movement is detected. There are nine time periods available from the time-out adjuster (from 10 s to 40 min).
Multiple sensors can be connected to the same load in order to extend the detection zone (see 'Multiple sensors' on
page 2).
Absence Mode
With the mode selector set to absence detection mode, pressing a retractive switch connected to the sensor will switch
on the connected load. Then, if no presence is detected for the selected time period, or if the retractive switch is pressed
shortly, the load will be switched off
Helvar Flush-Mount PIR Switching Sensor: Installation Guide
Illuminance
threshold adjuster
Time adjuster
Presence/Absence
mode selector
.
1000 lx
Photocell
inactive
10 lx
2.5 min
2,5 min
80 s
5 min
40 s
10 min
20 s
20 min
10 s
40 min
1

Advertisement

loading
Need help?

Need help?

Do you have a question about the SF-PIR-SW-01 and is the answer not in the manual?

Questions and answers

Summary of Contents for HELVAR SF-PIR-SW-01

  • Page 1 Installation Guide Flush-Mount PIR Switching Sensor (SF-PIR-SW-01) The SF-PIR-SW-01 is a PIR-triggered switch suitable for mounting into a ceiling void. It allows simple selection of presence or absence detection to control both lighting and nonlighting loads. Configurable for any room occupancy style, it switches on the connected load if the area is occupied and the illuminance is lower than the specified level (with the photocell activated).
  • Page 2 • Do not connect on a circuit with large inductive loads, as induced spikes can cause false triggering or damage the sensor. • Protect the sensor by a 6 A MCB or fuse. • Disconnect the sensor from the circuit before performing insulation testing of the wiring circuit. www.helvar.com Helvar | Data is subject to change without notice.
  • Page 3 • Washrooms with total coverage: 10 min • Washrooms with entry coverage only: 40 min • 2D fittings: Not less than 20 min, due to potential lamp failure. If in doubt, contact your lamp manufacturer. Helvar Flush-Mount PIR Switching Sensor: Installation Guide...
  • Page 4 4 °C. Relative humidity: Max. 90 %, noncondensing Storage –10 °C to +70 °C temperature: Helvar Ltd Hawley Mill Hawley Road DARTFORD DA2 7SY UNITED KINGDOM www.helvar.com Helvar | Data is subject to change without notice. Doc. 7860341, issue 2, 2015-12-15...