3.1.3 Check AC

The Check AC (CAC) input detects the presence of the AC
supply and is used to check for AC power failure. The CAC line
should be connected to one of the transformer's SECONDARY
terminals. DO NOT connect this line to the mains.
The CAC input will detect AC voltages between 10 and 24V.
If the CAC line is not connected, the Falcon Fusion should not
be programmed to send AC Failure or Restoral signals.
The AC Failure and AC Restore signals have a programmable
delay (default set at 1 minute) in order to prevent false triggers.

3.1.4 Dry Contact Inputs

The dry contact inputs can be used to detect alarms generated
from the outputs of the alarm panel or from other sources.
If the external device generates the alarm by pulling the input to
ground (negative trigger), the pull-up jumper should be inserted
on the input of the Falcon Fusion.

3.1.5 Contact ID Inputs

The Falcon Fusion can 'intercept' signals sent by the alarm panel
on its telephone line (Contact ID) interface.
If the Contact ID interface is to be used, the alarm panel's TIP
10
I
Falcon Fusion Installation and Operation Manual