Dimensions ..............18 The information contained in this document is assumed to be accurate. However, VDH Products BV does not accept any liability for eventual mistakes or errors, and retains the right to adapt or change this document without notice.
Version: V1.1 MC 785T-DF Client: General Page: 3 of 20 Technical specifications General Type : MC 785T-DF Wall mounting: Housing : Grey plastic Material : Polystyrol 454h KG 2 natur BASF Dimensions : 213 x 180 x 85mm (whd) Front...
(NO, 250Vac/10A not inductive) RY5 Defrost (NO-NC, 250Vac/10A not inductive) Functional specifications The MC 785T-DF has three different operating modes. These are: Mode 0 - 2x cooling Mode 1 - cooling/heating Mode 2 - 2x heating The MC 785DF has an analog P(I)-output with a range of 0/+10 Vdc. The function of this output is programmable as measuring signal, setpoint signal or a P(I) output for the cooling or heating.
Operating Manual Document no.: 042036 Version: V1.1 MC 785T-DF Client: General Page: 5 of 20 Control of the thermostat Normally the display shows the temperature of the control sensor(s). Read-out of the sensors. Press the SENS key. The display shows the temperature of sensor 1. The LED 1 next to the SENS key will start to flash, to indicate that sensor 1 is being shown.
Operating Manual Document no.: 042036 Version: V1.1 MC 785T-DF Client: General Page: 6 of 20 Programming the DAY and NIGHT switching times. Press the SET-CLOCK key. The MO LED (monday) will flash, the DAY LED will flash and the switch-on time of the DAY stand for Monday will appear in the time display. This time can be varied by using the UP and DOWN keys.
Operating Manual Document no.: 042036 Version: V1.1 MC 785T-DF Client: General Page: 7 of 20 Parameter table. Number Description Range Value Default P 01 Function thermostat 0..2 0 = 2x cooling 1 = cooling/heating 2 = 2x heating P 02...
Page 8
Operating Manual Document no.: 042036 Version: V1.1 MC 785T-DF Client: General Page: 8 of 20 Number Description Range Value Default P 50 Defrost 0..2 0 = none 1 = natural 2 = electric/hotgas P 51 Defrost-interval 1..99 hours P 52 Maximum defrost time 1..99...
Page 9
Operating Manual Document no.: 042036 Version: V1.1 MC 785T-DF Client: General Page: 9 of 20 Number Description Range Value Default P 90 Control off when all control sensors are defective 0 = no, 1 = yes P 91 Control off at external alarm...
Operating Manual Document no.: 042036 Version: V1.1 MC 785T-DF Client: General Page: 10 of 20 Operation of relay outputs Operation of cooling and heating. 2x cooling: Cooling 1 (RY2) switches on if the temperature is higher than the setpoint + offset_1 + differential_1 and switches off if the temperature is lower than setpoint + offset_1.
Operating Manual Document no.: 042036 Version: V1.1 MC 785T-DF Client: General Page: 11 of 20 Operating the defrost. There are three different methods for defrost. No defrost. Natural defrost. Before defrost is started, a check is made to see if the temperature of the defrost-sensor is lower than the defrost-release-temperature (P 54).
Operating Manual Document no.: 042036 Version: V1.1 MC 785T-DF Client: General Page: 12 of 20 Sensor calibration The sensors can be calibrated with the parameters P14 (Sensor-1), P15 (Sensor-2), P16 (Sensor-3) and P17 (Defrost Sensor-4). Should a sensor indicate 0.2°C too much, for example, then the corresponding offset-parameter must be set at -0.2°C.
Operating Manual Document no.: 042036 Version: V1.1 MC 785T-DF Client: General Page: 13 of 20 Front views Front view of MC 785T - DF drawing 950393 Front view of MC 785T-DF panel mounting. Drawing 970050...
Operating Manual Document no.: 042036 Version: V1.1 MC 785T-DF Client: General Page: 18 of 20 10. Dimensions Dimensions MC 785T-DF wall mount Fibox...
Page 19
Operating Manual Document no.: 042036 Version: V1.1 MC 785T-DF Client: General Page: 19 of 20 Dimensions MC 785T-DF wall mount with door Fibox...
Page 20
Operating Manual Document no.: 042036 Version: V1.1 MC 785T-DF Client: General Page: 20 of 20 Dimensions MC785T-DF panel mount drawing 961271 -.-.-.-.-.-.-.-.-.-...