Addressable visual indicator

Advertisement

Setting the address
The visual indicator includes an eight-segment DIP switch
(SW1). Switch SW1-1 though SW1-7 are used to assign device
addresses. Each switch segment has a decimal value as
shown in Figure 3. The address is the sum of all the switch
segments (SW1-1 though SW1-7) in the ON position. The
switch may be set to represent any address from 1 to 127.
For example, to select a device address of 007, set SW1-1,
SW1-2, and SW1-3 to the ON position and the remaining
switch segments to the OFF position.
Figure 3: Address switch setting
1
1.
Device mode
Setting the device mode
SW1-8 selects whether the visual indicator operates as a
stand-alone visual indicator or in ZP755 sounder emulation
mode as described in Table 1. Refer to Figure 3.
Table 1: SW1-8 mode selection switch
Mode
SW1-8
Output Signal
ZP755V
OFF
Stand-alone
visual indicator
ON
ZP755 sounder
ZP755
emulation
Mounting the visual indicator onto the base
Align the addressable visual indicator to the plug-in base. Push
up, and then turn the visual indicator until it clicks into place.
Push the visual indicator up once more to engage.
Note:
To prevent unauthorized removal, a plastic breakout tab
is provided in the addressable visual indicator housing. Once
the breakout tab is removed, the sensor can only be released
by use of a small flat screwdriver.
2 / 4
1
4 16
64
2
8
32
Requirement
This setting is not
currently supported
ZP3 panel
Visual indicators per loop
The visual indicator can be powered directly from the loop of a
ZP3 panel. Use Figure 4, in conjunction with Table 2, to
determine the quantity of detectors and visual indicators that
can be connected to a two-core shielded loop.
Figure 4: Visual indicators per loop
A.
Cable length panel to first visual indicator
B.
Cable length first to last visual indicator
C.
Cable length last visual indicator to panel
1.
Detectors and visual indicators
Table 2: Maximum detectors and visual indicators per loop
A
B
C
10 m
980 m
10 m
100 m
800 m
100 m
200 m
600 m
200 m
300 m
400 m
300 m
[1] Using a two-core shielded loop of 1000 meters cable size 1.5 mm²
P/N 501-1782ZE-1-07 • REV 07 • ISS 23JAN14
Quantity allowed [1]
60 detectors and 60 visual
indicators
80 detectors and 40 visual
indicators
60 detectors and 60 visual
indicators
80 detectors and 40 visual
indicators
60 detectors and 60 visual
indicators
80 detectors and 40 visual
indicators
60 detectors and 60 visual
indicators
80 detectors and 40 visual
indicators