Canbus user interface with lcd graphic display (22 pages)
Summary of Contents for Evco Vcolor EPV4CBR
Page 1
EVCO S.p.A. Vcolor | Hardware manual ver. 1.0 | Code 144VCOE104 Vcolor Programmable remote user interfaces, with color touch-screen TFT graphic display Hardware manual | ENGLISH Code 144VCOE104 page 1 of 38...
Page 2
EVCO S.p.A. Vcolor | Hardware manual ver. 1.0 | Code 144VCOE104 Important Read this document thoroughly before installation and before use of the device and follow all recommendations; keep this document with the device for future consultation. Only use the device in the way described in this document; do not use the same as a safety device.
EVCO S.p.A. Vcolor | Hardware manual ver. 1.0 | Code 144VCOE104 Index INTRODUCTION ..........4 Introduction ............ 4 Summary table of the available models, the main features and the purchase codes......5 SIZE AND INSTALLATION ......... 6 Size ............... 6 Panel mounting ..........
The interfaces can easily be integrated both in residential and in commercial environments; at their front it is possible to apply the frontal plates CPVP EVCO (to order separately) or the plates belonging to the series "Living" and to the series "Light"...
• alarm and signalling buzzer • For further information look at chapter 10 “TECHNICAL DATA”. The following table shows the purchase codes. Purchase codes: EPV4CBR For further information contact the EVCO sales network. page 5 of 38...
Through the gasket 0027000007 (to order separately) it is possible to guarantee a protection rating IP65; through the frontal plates CPVP EVCO (to order separately) or the plates belonging to the series "Living" and to the series "Light" BTicino it is possible to integrate the devices both in residential and commercial environments.
It is necessary to install the box vertically. Through the frontal plates CPVP EVCO (to order separately) or the plates belonging to the series "Living" and to the series "Light" BTicino it is possible to integrate the devices both in residential and commercial environments.
The following drawing shows the wall mounting of the devices (in wall mounting support CPVW00 EVCO, to order separately). Through the frontal plates CPVP EVCO (to order separately) or the plates belonging to the series "Living" and to the series "Light"...
EVCO S.p.A. Vcolor | Hardware manual ver. 1.0 | Code 144VCOE104 WIRING DIAGRAM Connectors The following drawing shows the connectors of the devices. Meaning of connectors The following tables show the meaning of the connectors of the devices. CANBUS CAN port CAN port with CANBUS communication protocol.
EVCO S.p.A. Vcolor | Hardware manual ver. 1.0 | Code 144VCOE104 The following table shows the Function codes supported by the device, on condition that it works in commander modality and the communication protocol is MODBUS. Function code Meaning FC 01...
EVCO S.p.A. Vcolor | Hardware manual ver. 1.0 | Code 144VCOE104 Plugging-in line termination network with CANBUS communication protocol To reduce the reflections on the signal transmitted along the cables connecting the devices to a CAN network with CANBUS communication protocol it is necessary to plug-in the line termination of the first and of the last element of the network.
EVCO S.p.A. Vcolor | Hardware manual ver. 1.0 | Code 144VCOE104 Example of wiring diagram The following drawing shows an example of wiring diagram of the devices. page 12 of 38...
CAN network with CANBUS communication protocol using a twisted pair connect the power cables the most possible away from the signal’s ones for repairs and information on the device please contact the EVCO’s sales network. page 13 of 38...
EVCO S.p.A. Vcolor | Hardware manual ver. 1.0 | Code 144VCOE104 DESCRITPION Description of the front The following drawing shows the aspect of the front of the devices. The following table shows the meaning of the parts of the front of the devices.
EVCO S.p.A. Vcolor | Hardware manual ver. 1.0 | Code 144VCOE104 Description of the back The following drawing shows the aspect of the back of the devices The following table shows the meaning of the parts of the back of the devices.
EVCO S.p.A. Vcolor | Hardware manual ver. 1.0 | Code 144VCOE104 FIRST USE First use Operate as follows: Make the installation of the device with the modality shown in chapter 2 “SIZE AND INSTALLATION” following all the additional information related in paragraph 3.7 “...
EVCO S.p.A. Vcolor | Hardware manual ver. 1.0 | Code 144VCOE104 PRELIMINARY INFORMATION Switching on/off the device To switch on the device, operate as follows: Connect the power supply: i twill be started an internal test. The test takes typically a few seconds.
EVCO S.p.A. Vcolor | Hardware manual ver. 1.0 | Code 144VCOE104 CONFIGURATION Setting the date and the time According to the factory settings the date is shown in the format dd mm yy and the time in the format 24 h.
EVCO S.p.A. Vcolor | Hardware manual ver. 1.0 | Code 144VCOE104 Setting language showing foreseen) words of the application project To set the language for showing (if foreseen) the words of the application project, operate as follows: Switch on the device and show the sensitive areas;...
EVCO S.p.A. Vcolor | Hardware manual ver. 1.0 | Code 144VCOE104 To quit the procedure, operate as follows: Press and release over and over again the area “ESCAPE”. Switch off/on the power supply of the device after the parameters setting.
EVCO S.p.A. Vcolor | Hardware manual ver. 1.0 | Code 144VCOE104 Uploading and downloading the configuration parameters 7.5.1 Uploading the configuration parameters The upload of the configuration parameters can be done on condition that the firmwares coincide. To make the upload of the configuration parameters, operate...
Page 22
EVCO S.p.A. Vcolor | Hardware manual ver. 1.0 | Code 144VCOE104 Press and release the area “ENTER”: it will be started upload configuration parameters. The upload takes typically a few seconds; if the operation is not completed succesfully, the display will show an error indication (for example “Status:...
Page 23
EVCO S.p.A. Vcolor | Hardware manual ver. 1.0 | Code 144VCOE104 Press and release the area “DOWN” to select “Save on USB” or “Save on memory” (according to the option selected in step 9). Press and release the area “ENTER”: it will be...
EVCO S.p.A. Vcolor | Hardware manual ver. 1.0 | Code 144VCOE104 Configuring an element of a network with CANBUS communication protocol To configure an element of a CAN network with CANBUS communication protocol, operate as follows: Disconnect the power supply of the device and of the other element of the network.
EVCO S.p.A. Vcolor | Hardware manual ver. 1.0 | Code 144VCOE104 List of the configuration parameters 7.7.1 Configuration parameters of the menu “Info” The following table shows the meaning of the configuration parameters of the menu “Info”. PARAM. MIN. MAX.
Page 26
EVCO S.p.A. Vcolor | Hardware manual ver. 1.0 | Code 144VCOE104 7.7.3 Configuration parameters of the menu “Parameters” The following table shows the meaning of the configuration parameters of the menu “Parameters”. PARAM. MIN. MAX. U.M. DEF. DESCRIPTION Date Char...
Page 27
EVCO S.p.A. Vcolor | Hardware manual ver. 1.0 | Code 144VCOE104 kind of beep when pressing a sensitive area of the display of the device Beep Mode - - - no beep always on condition the area is sensitive showing frames instead small size pages...
Page 28
EVCO S.p.A. Vcolor | Hardware manual ver. 1.0 | Code 144VCOE104 Press and release key “RIGHT” to show the section “CAN Status” of the submenu “CAN bus” of the menu “Networks” . PARAM. MIN. MAX. U.M. DEF. DESCRIPTION Cnt Rx...
Page 29
EVCO S.p.A. Vcolor | Hardware manual ver. 1.0 | Code 144VCOE104 7.7.5 Configuration parameters of the submenu “UART” of the menu “Networks” The following table shows the meaning of the configuration parameters of the submenu “UART” of the menu “Networks”.
Page 30
EVCO S.p.A. Vcolor | Hardware manual ver. 1.0 | Code 144VCOE104 7.7.7 Configuration parameters of the menu “Diagnostics” The following table shows the meaning of the configuration parameters of the menu “Diagnostics”. PARAM. MIN. MAX. U.M. DEF. DESCRIPTION status of the non volatile memory...
EVCO S.p.A. Vcolor | Hardware manual ver. 1.0 | Code 144VCOE104 SIGNALS Signals The following tables shows the meaning of the LED of the device. LED colour Meaning LED power supply device green if it is lit, the device will be powered...
EVCO S.p.A. Vcolor | Hardware manual ver. 1.0 | Code 144VCOE104 ACCESSORIES Connecting cables 0810500018/0810500020 9.1.1 Preliminary information Through the cables it is possible to make more accessible the USB port of the devices. The cable 0810500018 is 2.0 m long; the cable 0810500020 is 0.5 m long.
EVCO S.p.A. Vcolor | Hardware manual ver. 1.0 | Code 144VCOE104 Gasket 0027000007 9.4.1 Preliminary information Through the gasket it is possible to guarantee an IP65 protection rating in case of panel mounting. page 33 of 38...
(in box like “506e” BTicino and self-threading screws) Mounting: by wall (in wall mounting support CPVW00 EVCO, to order separately and with self-threading screws). Protection rating: IP40 (IP65 in case of panel mounting with gasket 0027000007, to order separately).
Page 35
EVCO S.p.A. Vcolor | Hardware manual ver. 1.0 | Code 144VCOE104 24 VAC (±15%), 50 / 60 Hz (±3 Hz), 3 VA max not isolated 24 VDC (-15%, +65%), 2 W max not isolated supplied by a class 2 circuit.
Page 37
Vcolor Programmable remote user interfaces, with colour touch- screen TFT graphic display Hardware manual ver. 1.0 PT - 38/13 Code 144VCOE104 This document belongs to EVCO; EVCO does not take any responsibility about possible mistakes related. customer (OEM, installer final...