Table of Contents

Advertisement

3. Installation of outdoor unit
Clearance of side discharge unit [Unit:mm(inch)]
1) Where there is an obstacle on the air intake side:
n No obstacle above
• Obstacle on the suction side only
n Obstacle above, too
• Obstacle on the air intake side, too
2) Where there is an obstacle on the discharge side:
n No obstacle above
3) Where there are obstacles on both suction and discharge sides:
n Where the obstacles on the discharge side is higher than the unit:
• No obstacle above
• Obstacle above, too
The relations between H, A and L are as follows:
L
0 < L ≤ 1/2H
L ≤ H
1/2H < L
H < L
Set the stand as: L ≤ H
Close the bottom of the installation frame to prevent
the discharged air from being bypassed.
• Obstacle on the both sides
• Obstacle on the air intake side, and both sides
n Obstacle above, too
A[mm(inch)]
750(29 1/32)
1 000(39 3/8)
Heat pump
60Hz/R410A
_ 48