Start-Up Unit

DANGER
Electric shock hazard. Can cause injury or death.
Before attempting to perform any service or
maintenance, turn the electrical power to unit to OFF
at disconnect switch(es). Unit may have multiple
power supplies.
CAUTION
Use caution when removing access panels or other
unit components, especially while standing on a
ladder or other potentially unsteady base. Access
panels and unit components can be heavy and serious
injury may occur.
CAUTION
Do not operate without the filters and birdscreens
installed. They prevent the entry of foreign objects
such as leaves, birds, etc.
CAUTION
Do not run unit during construction phase. Damage to
internal components may result and void warranty.
WARNING
• Unit was factory tested. All blowers, fans,
and compressors are set-up to run correctly
when supplied power. If any one fan is running
backwards or the compressor is making loud
noises, immediately turn off the power. Switch two
leads on the incoming power to the disconnect.
This will ensure proper operation of the unit. Failure
to comply may damage the compressors and void
the warranty.
• Do not jumper any safety devices when operating
the unit. This may damage components within or
cause serious injury or death.
• Do not operate compressor when the outdoor
temperature is below 40ºF.
• Do not short-cycle the compressor. Allow
5 minutes between "on" cycles to prevent
compressor damage.
• DX system is charged with refrigerant. Start-up
must be performed by EPA Certified Technician.
22
Dedicated Outdoor Air Unit
WARNING
Prior to starting up the unit, power must be energized
for 24 hours without a call for cool to allow the
compressor crankcase heaters time to boil off any
liquid refrigerant present in the compressor.
Every installation requires a comprehensive start-up
to ensure proper operation of the unit. As part of that
process, the following checklist must be completed and
information recorded. Starting up the unit in accordance
with this checklist will not only ensure proper operation,
but will also provide valuable information to personnel
performing future maintenance. Should an issue arise
which requires factory assistance, this completed
document will allow unit experts to provide quicker
resolve. Qualified personnel should perform start-up to
ensure safe and proper practices are followed.
Unit Model No. ___________________________________
Unit Serial No. ____________________________________
Energy Wheel Date Code __________________________
Compressor 1 Model No. __________________________
Compressor 2 Model No. __________________________
Compressor 3 Model No. __________________________
Compressor 4 Model No. __________________________
Start-Up Date ____________________________________
Start-Up Personnel Name __________________________
Start-Up Company ________________________________
Phone Number ___________________________________