Recommended Electrical And Gas Supply Entry Locations; Optional Gas Piping; Alternate Supply Entry Locations; Gas Connections - valent VX Series Installation, Operation And Maintenance Manual

Dedicated outdoor air unit
Hide thumbs Also See for VX Series:
Table of Contents

Advertisement

Recommended Electrical and Gas Supply Entry Locations

Manufacturer recommends that electrical service and
gas supply be brought into the cabinet through the
end wall, as shown below. There are three penetrations
into the cabinet that are required; one for high voltage
supply wiring, one for low voltage control wiring and one
for either gas supply or high voltage supply wiring for an
electric heater.
Optional Unit
Disconnect
Indirect
Gas
Supply
Location
Recommended Gas and Electric Supply Entry Locations

Alternate Supply Entry Locations

Each installation is unique and as a result, alternate
entry locations may be field-located. Before using any
alternate entry location, verify the suitability of the
location and ensure the use of an alternate location
does not interfere with unit wiring, components or
functionality.
WARNING
Never drill holes in the roof of the unit! There is high
voltage wiring located between the inner and outer
roof panels. Damage to the wiring could cause severe
bodily harm or death.
Field Wiring

Optional Gas Piping

Units with indirect gas-fired furnaces require field-
supplied and installed gas supply piping. The unit gas
connection is 3/4-inch NPT. The maximum allowable
gas pressure is 14 in. wg.
Total Heating
Housing
Capacity
Size
(Input in MBH)
100
150
XV-112/
200
VXE-112
250
300
300
XV-212/
400
VXE-212
500
200
250
300
350
XV-311/
400
VXE-311
500
600
700
800
600
800
XV-352/
VXE-352
1000
1200

Gas Connections

If this unit is equipped with an indirect gas-fired furnace,
connection to an appropriate gas supply line will be
required. For complete information on installation
procedures for the optional gas furnace, refer the
PVF/PVG Indirect Gas-Fired Heat Module Installation,
Operation, and Maintenance Manual.
Gas Cock
From Gas Supply
Bleeder Valve or
1/8 in Plugged Tap
Typical Gas Supply
Piping Connection
Gas
Max Gas
Connection
Pressure
Size
¾" NPT
14 in. wg.
¾" NPT
14 in. wg.
¾" NPT
14 in. wg.
1" NPT
13.5 in. wg.
2" NPT
Ground
Gas to
Joint
Controls
Union
8 in. Trap
Dedicated Outdoor Air Unit
11